SPECIFICATIONS
N
LEAD
PRODUCT SPECIFICATIONS:
Dimensions: 13.5” H x 5” W x 4” D
Weight: 8 lbs.
Cover: Steel Powder Coated
Color: Sandstone
Temperature: Factory set to 105°F
Element: Replaceable Ni Chrome cartridge insert
MT Fittings: 3/8” compression ttings at TOP of unit
MB Fittings: 1/2” compression ttings at BOTTOM of unit
UL Listed: E86887
U.S. PATENT PENDING TECHNOLOGY
WARNING: THE TEMPERATURE OF THIS HEATER
HAS BEEN EEMAX FACTORY SET AT 105°F FOR HAND
WASHING APPLICATIONS AND MUST NOT BE ADJUSTED.
TAMPERING WITH ANY ADJUSTMENTS WILL VOID
WARRANTY AND MAY CAUSE A LOSS OF COMPLIANCE
TO UNIFORM PLUMBING CODE 413.1. FOR FURTHER
INFORMATION PLEASE CONTACT OUR TECHNICAL
SUPPORT DEPARTMENT AT 1-800-543-6163.
VOLTAGE
POWER (kW)
# AERATORS SUPPLIED/UNIT
SUPPLY CIRCUITS REQUIRED
RECOMMENDED WIRE SIZE
TURN-ON (GPM)
MAX EFFECTIVE FLOW (GPM)
WATER CONNECTIONS
COMPRESSION FITTINGS
TEMP RISE AT 0.5 GPM (F)
TEMP RISE AT 1.0 GPM (F)
TEMP RISE AT 1.5 GPM (F)
120
240*
240*
240*
277
277
120
240*
240*
240*
240*
277
277
3.5
4.8
6.5
9.5
8.0
10.0
3.5
4.8
6.5
9.5
11.5
8.0
10.0
1
1
2
3
2
3
1
1
2
3
4
2
3
29A
20A
27A
40A
29A
40A
29A
20A
27A
40A
50A
29A
40A
10AWG
12AWG
10AWG
8AWG
10AWG
8AWG
10AWG
12AWG
10AWG
8AWG
6AWG
10AWG
8AWG
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
3/8”
3/8”
3/8”
3/8”
3/8”
3/8”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
1/2”
Top
Top
Top
Top
Top
Top
Bottom
Bottom
Bottom
Bottom
Bottom
Bottom
Bottom
48°
64°
89°
––
––
––
48°
64°
89°
––
––
––
––
––
31°
44°
65°
55°
68°
24°
31°
44°
65°
79°
55°
68°
––
21°
30°
43°
36°
46°
16°
21°
30°
43°
52°
36°
46°
3/8” COMPRESSION FITTINGS AT TOP OF UNIT
MT PRODUCT LINE
–
MT004120T
MT005240T
MT007240T
MT010240T
MT008277T
MT010277T
MB PRODUCT LINE
–
MB004120T
MB005240T
MB007240T
MB010240T
MB012240T
MB008277T
MB010277T
5.1 2.7
2.2
4.1
6.8
13.4
2.4
13.4
5.1
2.7
2.2
4.1
6.8
13.4
2.4
13.4
1/2” COMPRESSION FITTINGS AT BOTTOM OF UNIT
MB PRODUCT LINE
–
SPECIAL DESIGN SERVICE
INQUIRIES FOR UNITS FOR UNIQUE APPLICATIONS ARE WELCOME.
CALL OUR TECHNICAL SERVICE DEPT. 1-800-543-6163.
PRODUCT DIAGRAM (in inches)
*240V units can be used on 208V with 25% reduced temperature output.
EEMAX SUBMITTAL
Engineer/Architect: _______________________________________________________________________________
Job Name/Customer: _____________________________________________________________________________
Location: ________________________________________________________________________________________
Contractor: ______________________________________________________________________________________
Representative: ___________________________________________________________________________________
HEATER SPECIFICATIONS:
Quantity kW Voltage AMPS GPM
AccuMix Model # MB___________________ __________ __________ __________ __________ _________
AccuMix Model # MT ___________________ __________ __________ __________ __________ _________
MODEL # VOLTAGE
SUGGESTED SPECIFICATION
Tankless Water Heater shall be an Eemax Thermostatic Model, with digital microprocessing temperature
control capable of maintaining outlet temperature of +/– 1°F accuracy, and uses an ASSE 1070 approved
integrated mixing valve,
__________________, with _______________ kW, _________ vac, and _________ to heat _________ GPM @ a
temperature rise of ____ degrees F. Unit shall have ABS-UL 94Vo rated cover. Element shall be replaceable
cartridge insert. Unit shall have replaceable lter in the inlet connector. Element shall be iron free, Nickel
Chrome material. Heater shall be tted with 1/2” pipe compression nuts (5/8” OD) or 3/8” sleeves, to
eliminate need for soldering. Maximum operating pressure of 150 PSI. Hot water storage tanks prohibited.
Unit shall be Eemax or approved equal.
kW RATING AMPERAGE