Series 8700 / 8800 Unitized Curtain Wall Installation Instructions
Section 15 - Deglaze / Re-glaze Procedures - SSG System
1/8” Shim
FM12 Temporary
Glazing Retainer
WNA3 Gasket
1/2” Nominal
Shim
FM12 Temporary
Glazing Retainer
WNA3 Gasket
WNA3 Gasket
1/8” Nominal
Shim
FM12 Temporary
Glazing Retainer
Figure 145
3. When re-glazing an opening or openings at a captured unit follow these instructions:
a. Carefully insert new setting blocks in the locations as noted in the approved shop drawings.
b. Clean the new glass or panel and set it in place, centered in the opening, setting on the setting blocks. Do not contaminate the sealant contact
surfaces of the glazing during handling. Press the glazing firmly against the spacer gaskets. Avoid sliding the glazing around on the spacers, as this
can force sealant into visible areas seen from the interior.
c. Apply temporary retainers (FM12) with wedge gaskets (WNA3) at 18” on center of the D.L.O. on all four sides of the opening.
Figure 146
Set the glazing in
place, pressing the
glazing firmly against
the spacer gaskets.
Set the glazing in place,
pressing the glazing firmly
against the spacer gaskets.