UPS Uninterruptible Power Supply ME 400/500/600/650/800 Instruction Manual Item number: ACX11MES40000000 ACX11MES50000000 ACX11MES60000000 ACX11MES65000000 ACX11MES80000000 Juni 2008 USB USB USB USB USB
USV ME400/500/600/650/800 Instruction Manual Contents ME series 1 Presentation 4 2 2.1 Warranty conditions Limitation of liability 5 6 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Safety General safety instructions Transportation and storage Setup Connection Operation Handling batteries Maintenance, servicing and faults 7 7 7 7 8 8 9 9 4 Introduction 10 5 System description 11 6 6.1 6.1.1 6.1.2 6.1.3 6.2 6.
USV ME400/500/600/650/800 ME series Instruction Manual 11 Troubleshooting 23 12 Software 25 13 13.1 13.2 13.3 13.4 Maintenance and servicing Measuring the bridging time (support time) Service log Service hotline Maintenance and service contracts 26 26 27 28 28 14 14.1 14.2 14.
USV ME400/500/600/650/800 Instruction Manual 1 Presentation In this instruction manual, the abbreviation UPS stands for Uninterruptible Power Supply. The following pictograms are used in this instruction manual: Denotes information which, if disregarded, poses a risk to health, functionality or safety. Warning about the handling of batteries. Warning about dangerous electrical voltage. Denotes additional information and tips. Recycling symbol.
USV ME400/500/600/650/800 Instruction Manual 2 Warranty conditions The delivery receipt is considered to be the initial proof of purchase and should be stored carefully. It is required for all warranty claims. If the product is transferred to another user, then the latter is entitled to claim under the warranty for the remainder of the warranty period. The purchase receipt and this declaration should be transferred to the possession of the new owner.
USV ME400/500/600/650/800 Instruction Manual EFFEKTA GmbH does not give any express or implied warranties in relation to this equipment and its quality, performance, merchantability or suitability for a specific purpose. In some countries, the exclusion of implied warranties is not permitted by law. In this case, the validity of all express and implied warranties is restricted to the warranty period. When this period expires, all warranties cease to be valid.
USV ME400/500/600/650/800 Instruction Manual 3 Safety 3.1 General safety instructions Read and observe the user manual and safety instructions in this chapter before taking any further action (transportation, storage, connection, startup etc.). Since the UPS equipment uses mains voltage and has a suitable energy accumulator (high-capacity batteries) installed either inside or outside the device, the instructions in this chapter are very important for all users and personnel.
USV ME400/500/600/650/800 Instruction Manual Ensure that the vents of the equipment are not blocked and that the circulation of air is not impeded. 3.4 Connection Only connect the UPS to an earthed shock-proof socket. Under no circumstances should the equipment be operated without a protective earth conductor. The house installation socket must be easily accessible and located in the vicinity of the UPS. In the case of a fixed connection, ensure that the shortest possible cable lengths are used.
USV ME400/500/600/650/800 Instruction Manual power supply (switch off the mains input externally or disconnect the UPS from the mains, e.g. by unplugging it). Make sure that no fluids or foreign bodies enter the UPS. 3.6 Handling batteries Warning – danger of electric shocks and burns. Batteries can cause electric shocks and are capable of producing high shortcircuit currents which can also inflict burns. Unauthorised persons must be kept away from batteries.
USV ME400/500/600/650/800 Instruction Manual 4 Introduction This manual is intended to provide basic information about single-phase line interactive UPS equipment, namely the functional principle, use of the various functions and the procedure to follow in the event of faults. In addition, this manual contains information on transportation and storage as well as handling and installation of the UPS equipment.
USV ME400/500/600/650/800 Instruction Manual 5 System description The UPS supplies an uninterrupted, single-phase voltage to users with mission-critical applications. In addition to supplying consumer loads, the equipment also keeps its internal batteries in a fully charged state. In the event of a power failure or power fault (e.g. voltage fluctuation), the UPS continues, without interruption, to deliver a modified sine-wave voltage supply to the UPS output.
USV ME400/500/600/650/800 Instruction Manual 6 Description of equipment – ME series In this chapter, you will be introduced to the various elements of the equipment and will be provided with instructions on its operation as well as all information on equipment connections. 6.1 Display and operator control elements on the front panel Fig. 2: Front view ME series All of the operator control and display elements required for normal operation are positioned on the front of the equipment.
USV ME400/500/600/650/800 Instruction Manual 6.1.1 Warning, indicator and operating elements: All of the indicator elements and the “ON/OFF” button are grouped together on this panel. All information on the device status of the equipment is available at a glance (Fig.3) . In additional, various different audible alarm notifications are presented. 6.1.2 Operator control elements of the UPS Fig.
USV ME400/500/600/650/800 Instruction Manual Battery error LED: The LED lights up in the event of a battery error. The battery should be checked and exchanged if necessary. 6.2 Equipment elements on the rear panel Fig. 4: Rear view ME series Danger! All plug connections on the rear panel (with the exception of the communication interface) are on the mains power potential when connected.
USV ME400/500/600/650/800 Instruction Manual b ) Fuse for mains input: The mains input is enabled when the fuse is inserted. The fuse is triggered in the event of high overcurrents or an equipment defect (e.g. internal shortcircuit) and the device is immediately disconnected from the connected mains power supply. To simulate a mains power failure, simply remove the fuse or disconnect the plug connection for the mains power supply.
USV ME400/500/600/650/800 Instruction Manual 6.3 Audible alarm signals of the UPS Support mode and high battery capacity: The audible warning notification sounds in the following sequence (A) [beep, beep -> long pause (3 s) -> beep, beep -> ..., repeating]. Support mode and low battery capacity: The audible warning notification sounds in the following sequence (B) [beep, beep -> short pause (0.5 s) -> beep, beep -> ..., repeating].
USV ME400/500/600/650/800 Instruction Manual 7 Storage and unpacking 7.1 Storing the UPS If the equipment is not installed immediately, the following should be observed: o The equipment and accessories must always be left in the original packaging and stored. o The recommended ambient storage temperatures are: +5°C...+30°C. o Protect the equipment and its packaging from moisture. o If the storage period is likely to be longer than 4 months, the UPS must be brought into operation for approx.
USV ME400/500/600/650/800 Instruction Manual 8 Installing and connecting the UPS All requirements in the technical data regarding environmental and operating conditions must be observed to ensure trouble-free functioning of the UPS. The following must be observed when setting up / installing the UPS equipment: o Avoid extremes of temperature and atmospheric humidity. A maximum service life, particularly in relation to the batteries, is achieved at an ambient temperature of 15-25°C.
USV ME400/500/600/650/800 Instruction Manual Fig. 5: Connection of UPS and consumers ME series S: 10A 1: 0.75 mm² Warning The UPS equipment contains components with high voltage and amperage. Incorrect handling may therefore result in electrical accidents which may have fatal consequences or cause material damage. The protective earth conductor must always be connected! If not, the consumer loads will also not be earthed. Warning The connection diagram shown in Fig.
USV ME400/500/600/650/800 Instruction Manual 9 Operating and controlling the equipment 9.1 Operating the UPS equipment The operation of this equipment is indicated by various operating modes and signals. 9.1.1 Operating modes and signals The most important operating modes of the UPS are: Charging mode: If the mains power is available and the line-side fuse is switched on, UPS charging mode is enabled. -> The batteries are already charged, but the UPS has not yet been switched on.
USV ME400/500/600/650/800 Instruction Manual A.V.R. mode: Within certain limits, A.V.R. mode compensates for over- or under-voltage in the power supply without drawing current from the batteries. This reduces the transfer voltage range at the UPS output compared to the mains power supply. Display/alarm signal: A.V.R. mode has no special display. The display is the same as on-line mode. No audible alarm signal.
USV ME400/500/600/650/800 Instruction Manual 9.2 Instructions for using the UPS The operator of this UPS equipment must always comply with the instructions in this manual. The operator may only carry out the following and must exercise extreme care when doing so: o Use of the operator control elements: Switching the UPS on and off. o Reading the display elements and interpretation of the audible alarm signals.
USV ME400/500/600/650/800 Instruction Manual 10 Starting up the UPS equipment To guarantee error-free startup, the following actions must be carried out: 1. Check the line-side fuse then connect the equipment to the power supply. 2. Switch the UPS on (switch on the front of the equipment). 3. Wait until the UPS is in on-line mode. 4. Now connect the consumer loads one by one, observing the load indicator.
USV ME400/500/600/650/800 Instruction Manual Problem: Possible cause: Remedy: The UPS cannot be started and no alarm signal is given. Mains power is not available to the UPS or is switched off. Ensure that all connections have been established and verify this by means of appropriate voltage measurements. Check the line-side fuse for the UPS. The batteries are deepRemove batteries from the discharged or defective. UPS and charge externally or replace.
USV ME400/500/600/650/800 Instruction Manual 12 Software The settings and operating statuses of the UPS can be determined and processed further using the communications interface in combination with a suitable software package. The software packages may be obtained from the manufacturer / dealer or via the service hotline (see “Service” chapter) where you can obtain useful information about suitable software packages for your application and UPS.
USV ME400/500/600/650/800 Instruction Manual 13 Maintenance and servicing You can expect a long service life and trouble-free operation from your UPS equipment as long as you ensure that the necessary minimum level of maintenance is carried out. However, the reliability of the UPS is also significantly affected by environmental conditions. The temperature and atmospheric humidity of the surroundings must be kept within the limits.
USV ME400/500/600/650/800 Instruction Manual 13.2 Service log Enter all maintenance and servicing work performed on the UPS equipment into the service log.
USV ME400/500/600/650/800 Instruction Manual 13.3 Service hotline In the unfortunate event that problems occur with the UPS or if you require safety-relevant information, please contact our service hotline on the following phone or fax numbers: Tel. no.: 0049 / (0) 741 –17451-0 Fax no.: 0049 / (0) 741– 17451-29 If it is not possible for you to get in touch by telephone, we have set up an email contact address for you: ups@effekta.
USV ME400/500/600/650/800 Instruction Manual 14 Technical Data 14.1 Equipment specifications Model: Power: Mains power input: ME400 ME500 ME600 ME650 400VA / 225W 500VA / 250W 600VA / 300W 650VA / 325W Phases 1 phase conductor + neutral conductor Input range UPS output: 170-280V AC Rated frequency 50 / 60Hz Synchronous range 45-65Hz Boost (+13%) yes Buck (-13%) yes Rated voltage (support mode) Max. output current Bridging time 230V AC (modified sine +/-15%) 1.7A 2.1A 2.6A 2.
USV ME400/500/600/650/800 Instruction Manual Model: ME800 Power: 800VA / 425W Mains power input: Phases 1 phase conductor + neutral conductor Input range UPS output: 170-280V AC Rated frequency 50 / 60Hz Synchronous range 45-65Hz Boost (+13%) yes Buck (-13%) yes Rated voltage (support mode) Max. output current 230V AC (modified sine +/-10%) 3.5A Bridging time 3 min.
USV ME400/500/600/650/800 Instruction Manual 14.3 List of wearing parts The following components are subject to normal wear and tear and are therefore not covered by the warranty for this UPS: Wearing part: Function: Item number: XXXX XX XX ** ME400, ME500, ME600, ME650 energy accumulator Depending on equipment; see accessories or on request ME800 energy accumulator Depending on equipment; see accessories or on request Battery 12V 7Ah XXXX XX XX ** Battery 12V 9.
USV ME400/500/600/650/800 Instruction Manual 15 Requirements for the declaration of conformity The CE-labelled UPS equipment complies with the following harmonised standards and EC guidelines: EC guideline: 73/23/EEC (for devices operating within a restricted voltage range) 93/&(EEC – supplement to guideline 73/23/EEC 89/336/EEC – guideline on electromagnetic compatibility 92/31/EEC – supplement to EMC guideline 89/336/EEC Standards: EN 50091-1 EN 50091-2 An EC declaration of conformity for CE-labell