PRODUCT SPECIFICATION Open Frame Page 1/12 Document prepared and responsible for M. Mauritz E2OFxW3 60 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I EGSTON Switch Mode Power Supply Product Name: E2OFxW3 60 12V / E2OFxW3 60 24V Input: Output : Type: 100 - 240 V AC 24V / 2,5A 12V / 5A E2OFxW3 60 CONFIDENTIAL This document contains proprietary information originated and/or owned by EGSTON System Electronics Eggenburg GmbH.
PRODUCT SPECIFICATION Open Frame Page 2/12 Document prepared and responsible for M. Mauritz E2OFxW3 60 Approved by Day Month Year S. Schmalhofer 20 01 15 1 Evolution .............................................................................................................. 3 2 Scope .................................................................................................................. 3 3 Technical Specification Sheet ..........................................................
PRODUCT SPECIFICATION Open Frame Page 3/12 Document prepared and responsible for E2OFxW3 60 M. Mauritz 1 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I EVOLUTION Edition A B C Date 01.03.2013 02.07.2013 21.01.2014 Responsible Schmalhofer Schmalhofer Obritzhauser D 16.05.2014 Schmalhofer E 05.06.2014 Mauritz F G H I 03.09.2014 27.10.2014 18.12.2014 20.01.
PRODUCT SPECIFICATION Open Frame Page 4/12 Document prepared and responsible for E2OFxW3 60 M. Mauritz 3.2 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I Safety and Environmental Conditions Parameter Dielectric Strength Key Min 3 3 4 Typ. KVAC KVAC KVAC 100 µA Leakage current Operating Temperature -25 Storage Temperature Humidity -25 Max Unit 70 °C 25 80 °C 95 % Test Cond. Standard Household Medical Secondary to earth At free convection.
PRODUCT SPECIFICATION Open Frame Page 5/12 Document prepared and responsible for E2OFxW3 60 M. Mauritz 3.3 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I Output Specification Parameter Key Output Voltage Output voltage tolerance Output Power Ripple Voltage Typ. Max Unit U2 24* V U2 12* V Test Cond.
PRODUCT SPECIFICATION Open Frame Page 6/12 Document prepared and responsible for E2OFxW3 60 M. Mauritz 3.4.2 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I Mounting PCBA can be fixed onto customer application with screws M3 DIN 931 (max. torque 1Nm) and lock washers DIN 6797 which are positioned on the corners. The PCBA has to be mounted without mechanical stress to protect the PCBA from distortion. 3.4.
PRODUCT SPECIFICATION Open Frame Page 7/12 Document prepared and responsible for M. Mauritz 3.4.4 E2OFxW3 60 Approved by Day Month Year S.
PRODUCT SPECIFICATION Open Frame Page 8/12 Document prepared and responsible for E2OFxW3 60 M. Mauritz 3.4.5 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I Thermal Considerations In order to ensure safe and reliable operation of the open frame power supply in the most adverse conditions permitted in the end-use equipment, the temperature of the components listed in the table below must be not exceeded. See mechanical drawing for component locations.
PRODUCT SPECIFICATION Open Frame Page 9/12 Document prepared and responsible for M. Mauritz 4 4.1 Day Month Year S. Schmalhofer 20 01 15 RELIABILITY MTTF For calculation the following standards were used: MIL-HDBK-217 F MIL-HDBK-217 F, Notice 1 MIL-HDBK-217 F, Notice 2 Siemens norm SN 29500-1 MTTF at 50° ambient temperature, 12V model: 36.47years MTTF at 50° ambient temperature, 24V model: 37.19years 4.2 E2OFxW3 60 Approved by Maintainability The power supply is not to be repaired.
PRODUCT SPECIFICATION Open Frame Page 10/12 Document prepared and responsible for M. Mauritz 5 5.1 E2OFxW3 60 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I SAFETY Dielectric Strength The input isolation test voltage is 3kV AC for standard and household applications 4KV AC for medical application, Sinusoidal waveform, test duration is 2 seconds for 100% test, 1minute for lot-test. 5.2 Over-current Protection The unit is not long time over-current proof.
PRODUCT SPECIFICATION Open Frame Page 11/12 Document prepared and responsible for M. Mauritz 6 6.1 E2OFxW3 60 Approved by Day Month Year S. Schmalhofer 20 01 15 Revision I APPROVALS AND TEST STANDARDS General The device is galvanically isolated with safety extra low voltage (SELV) output. 6.2 Test Standards EN 61000-6-1 EN 61000-6-3 EN 60601-1-2 EN 60950-1 UL 60950-1 EN 60335-1 EN 61558-2-16 UL 60950-1 EN60601-1 (2 MOPP) EN 61558-2-16 UL 60601-1 6.
PRODUCT SPECIFICATION Open Frame Page 12/12 Document prepared and responsible for E2OFxW3 60 M. Mauritz 7 Approved by Day Month Year S.