Smoke Alarm Product Manual

Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei105R DataSht RevA
Model Ei105R Optical
Important Precaution:
Do not install the actual smoke/heat
alarm itself in new or renovated
buildings until all work is completed
(including floor coverings) and the
building has been fully cleaned.
(Excessive dust and debris from
building work can contaminate the
smoke chamber and cause
problems, and it will also invalidate
the guarantee). If it must be
installed, cover it completely,
particularly around the edges, with
a dust cover (eg. a plastic bag),
until all cleaning is finished..
Technical Specification
Sensor Optical, uses light scatter from
smoke particles
Sensitivity: Complies with BS 5446 1: 2000
Source: Contains no radioactive material
Airspeed: Essentially immune to the effect
of airspeed.
Button Test: Simulates the effect of smoke and
checks chamber, electronics and
horn.
Ambient Light: Chamber housing design
overcomes problems with stray
light.
Supply Voltage: 12V control panel
Alarm: Piezoelectric horn
in unit
Alarm Sound Output: 85dB (minimum) at 3m
Temperature Range: 0 to 40°C
Humidity Range: 0% to 90% Relative Humidity
Fixing: Screw fixings supplied
Plastic material: UL94HB flame retardant
Dimensions: 145 x 120 x 45 mm
Weight: 181 grams
Warranty: 5 year (limited) warranty
Approvals: Kitemarked to BS5446-1:2000, CE
Approved
Specifications are subject to change