OPERATION 
The  following  procedures  should  be  followed  to  test  the  CS60  for  correct 
operation: 
  1.  After  unpacking, examine  all external features to  confirm damage-
free shipment. Report all defects and damage at once. Connect the 
power cable to a grounded 15 Amp electrical outlet. 
  2.  Check dehumidification process as follows: 
    A.  Place unit on a level surface. 
    B.  Start  up  unit  by  turning  the  humidistat  control  knob  until  the 
unit turns on. 
    C.  Check that the compressor is running. 
    D.  Leave the machine running for 15 minutes. 
E.  Observe  the  evaporator  coils  through  the  rear  upper  grill,  to 
confirm frost operation. 
i.  If the air temperature is below 80° F, an even coating of 
frost should cover the entire evaporator coil 
ii.  If the air temperature is above 80° F, frost and/or droplets 
of  condensed  water  should  cover  the  entire 
evaporator coil. 
F.  After  continuous running time  of approximately 55 minutes, the 
unit  will  enter  “Hot  Gas”  defrost  mode  for  5  minutes  and  then 
automatically return to normal operation. 
If, after carrying out the above procedures, the unit does not appear to 
function properly, refer to the Trouble Shooting section, which follows, 
or contact the Factory Service Center. 
TO ENSURE CONTINUED FULL EFFICIENCY OF THE 
DEHUMIDIFEIR, MAINTENANCE PROCEDURES SHOULD BE 
PERFORMED AS FOLLOWS: 
CAUTION:
ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT 
LEAST FIVE MINUTES BEFORE RESTARTING. 