ROUTINE MAINTENANCE 
To  ensure  continued  full  efficiency  of  the  dehumidifier,  maintenance 
procedures should be performed as follows: 
  1.  Clean the surface of the evaporator and condenser coils by blowing 
the  dirt  out  from  behind  the  fins  with  compressed  air.    Hold  the 
nozzle of the air hose away from the coil to avoid damaging the fins. 
Alternatively, vacuum clean the coils. 
  2.  Check that the fan is firmly secured to the motor shaft and that the 
fan rotates freely.  The fan motor is sealed for life and therefore 
does not need oiling. 
  3.  To  check  the  refrigerant  charge,  run  the  unit  for  15  minutes  and 
briefly remove the top cover.  The evaporator coil should be evenly 
frost  coated  across  its  surface.    At  temperatures  above  80°F,  the 
coil may be covered with droplets of water rather than frost.  Partial 
frosting  accompanied  by  frosting  of  the  thin  capillary  tubes, 
indicates loss of refrigerant gas or low charge. 
  4.  Check all wiring connections. 
  5  To  check  the  operation  of  the  defrost  system,  switch the  machine 
on and leave it running for approximately 55 minutes.  The machine 
will then enter “Hot Gas” defrost mode for approximately 5 minutes 
before returning to normal operation.  If the unit will not defrost, the 
printed  circuit  timer  board  may  be  defective  or  the  by-pass  valve 
may be inoperable. 
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
,
 CONTACT THE 
E
BAC 
S
ERVICE 
C
ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO 
PREVENT PERMANENT DAMAGE
.
WARNING:
ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN 
DISCONNECTED BEFORE CARRYING OUT ROUTINE 
MAINTNEN
ANCE
WARNING:
DO NOT STEAM CLEAN REFRIGERATION COILS 