REPAIRS 
  1.  Should  an  electrical  component  fail,  consult  the  Factory  Service 
Center to obtain the proper replacement part. 
  2.  If refrigerant gas is lost from the machine, it will be necessary to use 
a  refrigeration  technician  to  correct  the  fault.    Contact  the  Factory 
Service Center prior to initiating this action. 
    Any  competent  refrigeration  technician  will  be  able  to  service  the 
equipment. The following procedure must be used: 
    a.  The source of the leak must be determined and corrected. 
    b.  The  machine  should  be  thoroughly  evacuated  before 
recharging. 
    c.  The  unit  must  be  recharged  with  refrigerant  measured 
accurately by weight. 
    d.  For evacuation and recharging of the machine, use the crimped 
and brazed charging stub attached to the side of the refrigerant 
compressor. 
      The  charging  stub  should  be  crimped  and  rebrazed  after 
servicing.  N
EVER
 allow permanent service valves to be fitted to 
any part of the circuit.  Service valves may leak causing further 
loss of refrigerant gas. 
  3.  The  refrigerant  compressor  fitted  to  the  dehumidifier  is  a  durable 
unit that should give many years of service. Compressor failure can 
result from the machine losing its refrigerant gas.  The compressor 
can be replaced by a competent refrigeration technician. 
    Failure  of  the  compressor  can  be  confirmed  by  the  following 
procedure: 
    a.  Establish  that  power  is  present  at  the  compressor  terminals 
using a voltmeter. 
    b.  With the power disconnected, check the continuity of the internal 
winding  by  using  meter  across  the  compressor  terminals.    An 
open circuit indicates that the compressor should be replaced. 
    c.  Check that the compressor is not grounded by establishing that 
a  circuit  does  not  exist  between  the  compressor  terminals  and 
the shell of the compressor. 