Drawing : - TPC441 Issue :-2 Date : - 24/11/16 RM85-H INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 INTRODUCTION Designed for a wide range of applications, the RM85H is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 SPECIFICATIONS MODEL: 10560RH-GB HEIGHT: 945 mm WIDTH: 545 mm DEPTH: 492 mm WEIGHT: 45 kg AIRFLOW: 390 M3/Hr POWER SUPPLY: 230V/ 50Hz/ 1 ph FINISH: Rotational Moulded polyethylene OPERATING RANGE: 3°C – 35°C REFRIGERANT: R407c (500g) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 OPERATION The following procedures should be followed to test the RM85 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 13 Amp electrical outlet. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain 2.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 F. When the unit is operated in ambient of less than 15°C, a defrost cycle should occur approximately every hour. The exact time is impossible to predict as the unit is fitted with a temperature sensitive defrost control. During this defrost cycle the fan will switch off. When the unit is defrosting, the % Relative Humidity displayed on the digital controller may increase as a result of the ice / frost melting.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit 2. Mains cable damaged. Little or no airflow 1. Fan motor burnt out 2. Dirty refrigeration coils 3. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 RM85 SPARE PARTS LIST NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 DESCRIPTION Timer Condenser coil Evaporator coil Cable & Tube wrap Drain tray Filter Capillary Solenoid valve Filter dryer Defrost Relay Solenoid coil Humidity Controller On/Off switch Power Relay Run capacitor Pump purge switch Fan Fan inlet ring Wheel Rubber foot Condensate pump Compressor Page 9 of 12 PART NUMBER 1619508 2029322 2029323 2056002 2056003 2056004 3014254 3
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 Page 11 of 12
Drawing : - TPC441 Issue :-2 Date : - 24/11/16 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.