Drawing : - TPC180 Issue :-4 Date : - 09/12/13 SPP6A DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 SPP6A PACKAGE CONTENTS Item Description Quantity 1139800 Dehumidifier 1 1139805 Indicator box 1 1137500 Dehumidifier stand 1 2137509 Spanner 1 3014338 PVC tube – 12mm I/D 3M 3086101 Jubilee clip 1 TPC180 Manual 1 Page 2 of 16
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 UNPACKING Carefully remove the SPP6A Dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing; it will be useful when transporting the dehumidifier unit in the future. INTRODUCTION Dehumidifiers remove moisture from the air that is circulating through the unit.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 SPECIFICATIONS Model: SPP6A Length: 447mm Width: 340mm Height: 255mm Weight: 28 Kg (Typically) Paint Finish: Light Grey Power Supply: 115v ± 10%, 1 ph / 60Hz Power Rating: 250-300W Airflow: 250 M3/HR Construction: Portability: Welded 1.2m steel chassis and covers Two folding carrying handles.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 WATER EXTRACTION DUTY TEMPERATURE HUMIDITY ºC % WATER EXTRACTION L/24HR 0 70 0.6 10 70 1.8 20 70 3.5 30 70 5.2 40 70 7.0 55 40 7.0 44 95 12.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 INSTALLATION POSITIONING: Position the dehumidifier unit in the center of the room to be conditioned if at all possible. However if a damp patch is particularly apparent the outlet grille should be directed towards it. NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have clear space around them and not be obstructed in anyway. WIRING: Connect the power mains cable/plug of the dehumidifier unit to a 15 Amp power supply.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 OPERATION The operation of the dehumidifier is to remove moisture from the air by having it condense on the cold tubes of the evaporator coil. The air then passes over the hot condenser coil and returns to the conditioned space slightly warmer and dryer than when it entered the dehumidifier unit.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 WARNING: • • Due to the high pressures within the refrigeration circuit, under no circumstances must direct heat be applied to the evaporator coil in an attempt to remove the build up of ice. No attempt should be made to cut open any part of the refrigeration circuit due to high pressures and gas involved.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 SPECIAL FEATURES CONTROL AND WARNING INDICATOR HUMIDISTAT The SPP6A dehumidifier unit is fitted with a control panel fixed to the outside of the dehumidifier cabinet, the panel incorporates two humidity’s, which measure the relative humidity of the air within the room/space. The first humidistat incorporates a pointer and a scale, and is adjustable to a set point.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 AMBER LAMP This indicates that the dehumidifier unit is in stand by mode (the relative humidity within the room/space is below the set point of the Control humidistat) and mains power is applied. GREEN LAMP This indicates that the dehumidifier unit is operating (the relative humidity within the room/space is above the set point of the Control humidistat).
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 ROUTINE MAINTENANCE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTENACE ON ITEMS 1, 2, 3, 4, AND 5. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 TROUBLESHOOTING SYMPTOM CAUSE REMEDY 1. Tighten fan 2. Replace the fan motor 3. See Routine Maintenance Section 4. Check the wiring diagram to find fault and repair 5. Contact the Factory Service Center Little or no airflow 1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils 4. Loose electrical wiring 5. Control humidistat either set too high or malfunctioning Little or no dehumidifying effect 1. Insufficient air movement 2.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 SPP6A SPARE PARTS LIST DESCRIPTION PART NUMBERS 1139800 Compressor 3022143 Compressor OH Protector 3021538 Comp Relay 3021528 Comp Box Cover 3021518 Condenser Coil 3020740 Evaporator Coil 1135707 Filter Dryer 3020937 Fan Motor 3035767 Fan Blade 3040101 Drain Tube 3014338 Worm Drive Clip 3086101 Clip Nut 3080501 Control Humidistat 3031528 Indicator Humidistat 2135727 Male Contacts 3033814 Male insert 3033809 Indicator Box 113
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 Green Neon 3036637 Red Neon 3036636 Mains Cable 3031225 Control Cable 3031227 Bypass Valve 3020811 Solenoid Coil 3030421 Frostat 3031516 Timer 1618200 PCB Mounting Clips 3101413 "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC180 Issue :-4 Date : - 09/12/13 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.