Operating Instructions and Installation Instructions
35
No. Error type Explanation Possible solution
20
Lockout Error gas valve V1, flame ionisation signal detec-
ted longer than 5 seconds after burner stop.
Check closing position of valve V1 within gas combi
valve, replace gas valve.
21
Lockout Error gas valve V2, flame ionisation signal detec-
ted longer than 5 seconds after burner stop.
Check closing position of valve V2 within gas combi
valve, replace gas valve.
22
Lockout APS contact does not close during prepurge. Check setting APS, check if fan is running.
23
Lockout APS contact remains closed when fan is off. Check setting APS
27
Lockout APS contact opens during operation. Check setting APS
30
Lockout CRC error in control system parameters (P11-
P40).
Check parameter settings of P11-P40, change value of
one parameter within P11-P40 (lockout disappears),
change all parameters back to original settings.
31
Lockout CRC error in boiler safety parameters (V1-V16). Check parameter settings of V1-V16, change value of
one parameter within V1-V16 (lockout disappears),
change all parameters back to original settings.
32
Interlock Power supply voltage to boiler controller is too
low.
Check fuse of boiler controller, check power supply to
boiler controller.
40
Lockout Water flow switch has been interrupted when
pump being enabled.
Check pump operation, check water flow through the
boiler, check functionality of water flow switch.
x.y.
Lockout (all lockout codes which are not listed above)
Internal lockout of boiler controller.
Press reset. Change boiler controller when lockout can
not be reset or occurs more frequently.
Lockouts