Operating Instructions For Qualified Persons Controller for THISION S 06/2014 3740530 en
Table of Contents Basics Product description, Features, Functionality .................................................... 3 Basics............................................................................................................... 4 Controls ............................................................................................................ 5 Display / Programming ..................................................................................... 6 Overview of main functions .........
Basics Product description, Features, Functionality Product description The THISION S controller is a weather compensated digital controller that can control one mixed heating zone, one direct heating zone, DHW preparation and burner operation. Additional functions can be activated. The controller calculates the required temperatures for the boiler and the heating zones according to the outside temperature and controls DHWpreparation.
Basics When shipped from the factory, the heating controller is configured as follows: DHW heating active if a DHW sensor is connected Shifting heating circuit 1 4 Further combinations can be configured by setting the appropriate parameters and selecting auxiliary functions in the start-up menu.
Operating instructions Controls M I A L G H B C D E F Operation mode DHW (M) Confirmation (OK) (D) For switching on the DHW operation (indication in display below DHW symbol) Return (ESC) (B) These buttons are used for programming in combination with the Operation mode heating zone(s) (I) rotary knob.
Operating instructions Display / Programming DHW mode selection Heating operation mode selection (Controller Stop mode when pressing > 3 sec.) Display Info button Confirm Manual mode (Deaeration mode when pressing > 3 sec.
Operating instructions Overview of main functions Button Action Procedure Display / Function Comfort setpoint with blinking temperature Blinking temperature in 0,5 °C steps from 10 to 30 °C Set room temperature Zone 1 and zone 2 Actuate rotary knob left/right Turn rotary knob Confirm with OK button or wait 5 sec. or press Zone 2 independent from zone 1 Actuate rotary knob left/right Confirm with OK button Actuate rotary knob left/right Confirm with OK button or wait 5 sec.
Parameters Enduser Main display "Boiler temperature" Press OK Button 1x Turn the rotary knob to select for example menu "DHW" Press OK Button 1x Turn the rotary knob to select for example parameter 1612 "DHW temperature reduced setpoint" in menu "DHW" Press OK Button 1x Turn the rotary knob to change the setting Press OK Button 1x > new setting has been stored Press ESC Button 2x to go back to main display "Boiler temperature" Menu Time of day and date Operator section Time program HC
Parameters Enduser Menu Holidays HC1 Holidays HC2 (when activated) HC1 HC2 (when activated) DHW Boiler Fault Maintenance / special operation 8 Line no.
Parameters professional installer Main display "Boiler temperature" Press OK Button 1x Press Info Button > 3s Turn the rotary knob to select level "Commissioning" or "Engineer" Press OK Button 1x Turn the rotary knob to select for example menu "DHW" Press OK Button 1x Turn the rotary knob to select for example parameter 1612 "DHW temperature reduced setpoint" in menu "DHW" Press OK Button 1x Turn the rotary knob to change the setting Press OK Button 1x > new setting has been stored
Parameters professional installer Menu Holidays HC1 Holidays HC2 (when activated) HC 1 Line no. Operating line Unit Min. Max Factory setting 642 Period Start Day / Month tt.MM 01.01 31.12 643 Periode End Day / Month tt.MM 01.01 31.12 648 Operating level 652 Period Start Day / Month tt.MM 01.01 31.12 --.-- 653 Periode End Day / Month tt.MM 01.01 31.12 --.-- 658 Operating level - 710 Comfort setpoint °C Value from Line no.
Parameters professional installer Menu HC 2 (when activated) Line no. Operating line Unit Min. 1010 Comfort setpoint °C Value from Line no. 1012 1012 Reduced setpoint °C Value from Line no. 1014 Value from Line no. 1010 1014 Frost protection setpoint °C 4 Value from Line no. 1012 1020 - 0.10 4.00 1.50 °C -4.5 4.5 0.
Parameters professional installer Menu Line no. Min.
Parameters professional installer Menu Configuration 14 Line no.
Parameters professional installer Menu Line no.
Parameters professional installer Menu Diagnostics heat generation Diagnostics consumers Line no. 8310 8314 8316 8324 8326 8327 8328 8329 8336 8337 8338 8339 8340 8510 8530 8700 8703 8704 8740 8742 8743 8750 8770 8772 8773 8830 Burner control 16 8832 8836 8950 8980 9502 9504 9510 9512 9520 9522 9524 9527 9550 9560 9563 Operating line Unit Min.
Info menu Manual control Chimney sweeper function Display of information Various data can be displayed by pressing the info button. AUTO Room temperature 0 Possible info Depending on the type of unit, the configuration and operating state, some of the info lines listed below may not appear.
Error messages / Maintenance Error / Maintenance messages In exceptional cases, the basic display shows one of the following symbols. Error messages If this symbol appears, an error in the plant occurred. Press the info button and read further information. Maintenance/special operation If this symbol appears, a maintenance alarm is delivered or the plant has changed to special mode. Press the info button and read further information .
Detailled settings Menu: time of day and date Menu: Operator section Time of day and date The controller has a yearly clock with time of day, weekday and date. To ensure the controller´s functionality, both the time of day and the date must be correctly set.
Menu: Operator interface Units The display can be switched between the SI units (°C, bar) and U.S. units (°F, psi). Heating circuit assignment Line no.
Menu: Time programs Menu: Holiday For the heating circuits and for DHW heating, a number of switching programs are available. They are activated in Automatic operation and control the change of the temperature levels (and the associated setpoints) via the selected switching times. Entering the switching times The switching times can be set in a combined way, that is, either jointly for several days or in the form of se¬parate times for individual days. When preselecting groups of days like for instance Mo..
Menu: Heating circuits For heating circuits, there are various functions available which can be individually set for each heating circuit. Room setpoint Room temperature The room temperature can be shifted according to different setpoints. These setpoints become active depending on the selected operating mode, thus producing different temperature levels in the rooms. The ranges of adjustable setpoints result from the interdependencies, as this is shown in the following diagram. Line no.
Menu: Heating circuits Heating curve slope As the heating curve slope is raised, the flow temperature increases quicker at lower outside temperature. In other words, if the room temperature is not correct at low outside temperatures but correct at higher outside temperatures, the heating curve slope requires readjustment. Increase adjustment: Raises the flow temperature, especially when outside temperatures are low.
Menu: Heating circuits ECO-Function Summer/winter heating limit The summer / winter heating limit is used to switch the heating on and off in the course of the year, depending on temperature conditions. In automatic mode, switching on / off takes place automatically, so there is not need for the user to do this manually. By changing the setting, the respective periods of time will be shortened or extended. Line no.
Menu: Heating circuits Flow temp setpoint min/ max Using this limitation, a temperature range for the flow temperature setpoint can be defined. If the flow temperature setpoint demanded by the heating circuit reaches the relevant limit and the heat request increases or decreases, the flow temperature setpoint will be maintained at the maximum or minimum limit. Line no.
Menu: Heating circuits Room temperature control and limitation With the room temperature limitation function, the heating circuit pump can be disabled if the room temperature exceeds the current room temperature setpoint by more than the preset differential. Line no. HC1 HC2 760 1060 Operating line Factory setting Room temp limitation P SDR t TRw TRx The room temperature limitation does not work in the case of pure weather compensation.
Menu: Heating circuits Optimum start / stop control Line no. HC1 HC2 Operating line Optimum start control max The change from one temperature level to the other is optimized in a way that the comfort setpoint is reached at the relevant switching time.
Menu: Heating circuits Mixing valve control Mixing valve boost To ensure proper mixing valve flow temperature control, the flow temperature must be higher than the demanded setpoint of the mixing valve flow temperature. The value set here is added to the request. The selection of the type of actuator determines the control behavior for the type of mixing valve actuator used. Line no.
Menu: Heating circuits Variable speed pump The pump in the THISION S for heating circuit 1 is speed controlled according to the hydraulic standard. Speed design point Sets the speed level (1-24) of the pump at the design point for achieving the nominal flow rate. If necessary, the fan speed can be reduced (hydraulic adjustment). This corresponds to the analogue speed selector switch on the pump. The "variable speed pump" function is active in hydraulic diagram 3 and 60, in line no. 5701. Line no.
Menu: Heating circuits 100 90 Temperature [°C] 80 TkSNorm (= 70) 70 Required flow temperature at NqmodNenn 60 50 dTkTrNenn (= 20) dTkTrMax (= 3) 20 Required flow temperautre 40 Theoretical returntemperature at NqmodNenn 30 measured temperature at NqmodMin 20 20 15 10 5 0 -5 -10 -15 TiAussenNorm (= -20) -20 Outside temperature [°C] Area within which volumetric flow must be increased from NqmodMin to 100 % Area of reduced volumetric flow (= NqmodMin) den Volumenstrom verstellt Modgrad
Menu: DHW Setpoints The DHW setpoint acting on the control is selected based on the current operating level which includes impact of the operating mode, the release (possibly the switching program), the DHW push and the 0 legionella function. Line no. 1610 1612 Operating line Factory setting Nominal setpoint Reduced setpoint 55°C 40°C DHWN DHWmax DHWR DHWmax DHWN DHWR Release Line no.
Menu: DHW Legionella function Line no. Periodically The legionella function is repeated according to the interval set (operating line 1641). The legionella setpoint is attained via a solar plant, independent of the period of time set, the period of time will be newly started. This means that the heat source is switched on only if the solar plant could not deliver the required “Legionella function setpoint” within the adjusted period of time.
Menu: Boiler Heat generation lock With this parameter, the heat generation lock function is released. If this is the case, the burner and the boiler pump are turned off when, for example, due to a programmed input or a sensor of the clip-in AGU 2514, the burner is locked from the outside or the temperature at the sensor of the clip-in is high enough to supply the consumers. Setpoints The controlled boiler temperature setpoint can be limited with Setpoint min and -max.
Menu: Buffer storage tank General: The buffer storage tank function and menu are only active when in the configuration menu, line no 5973 is set as “Heat generation lock sensor”. Auto generation lock The automatic heat generation lock brings about a temporary hydraulic separation between heat source and buffer storage tank. The heat source is put into operation only when the buffer storage tank is no longer able to cover the current demand for heat.
Menu: Solar Line no. General: The solar function and the solar menu are only active when a solar Clip-In AGU 2.530 and collector sensor are connected to the LMU. In addition, in the configuration menu, in parameter 5978, the function input SolCl is set to collector sensor.
Menu: DHW storage tank Charging Flow setpoint boost The DHW request to the boiler is made up of the current DHW setpoint plus the adjustable charging boost. Recooling collector With solar function activated, excess energy from the drinking water tank when the collector is cold (at night) is routed to the environment via the collector. Line no. 5020 Line no.. 5020 Operating line Flow setpoint boost Operating line 9 - 25 kW 17°C Line no.
Menu: Configuration Heating circuit 1,2 The HCs can be switched on or off DHW pump off switch Duration of the pump shutdown when reversing the reversing valve between heating and DHW operation. If the parameter is set to 0 there is no pump shutdown. In addition, working with the delay in parameter 5733 must be set to 0 seconds. Line no. Operating line HC1 HC2 5710 5715 Heating circuit 1 Heating circuit 2 On On Line no.
Menu: Configuration Programmable relay outputs explanatory notes 0 Default Function as plumbing diagram 1 Status output Control of additional valve in liquid gas applications 2 Alarm output Output set, if a fault is present in the device, which requires manual unlocking. 3 Status information Output set, when burner is operational. 4 External transformer switch off Not possible with LMU 7. 5 Pump 2nd Heating circuit This output supplies the drive signal for the pump of the second LMU7 heating circuit.
Menu: Configuration Line no. Function input H1 (programmable input) On the LMU programmable input the following functions can be selected, that are activated by an external contact. Function input RelCl On the programmable input of the clip-in (not the solar Clip-In), the following functions can be selected, which can be activated by an external contact (function 0,1,2,3,7,8,9,), an analogue signal (function 4,5) or via a sensor (function 6,11).
Menu: Configuration Programmable inputs explanatory notes 0 Default, None The "programmable input" function is not used 1 Modem function active when contact closed The telephone remote switch (modem function) is a central switching off or transfer of the heating system to the operating mode "Standby" or reduced t 2 Modem function active when contact open As 1, but the modem function is activated when the phone switch contact opens.
Menu: Configuration Line no. Config room thermostat 1, 2 5970 5971 Using the parameters, the function of the input can be programmed as follows: 0: 1: 2: 3: 4: Line no. Modulating pump speeds Speed of the modulating pump. Line no. 5975 6089 The above setting is used to adjust the response of the flow temperature setpoint when the outside temperature varies.
Menu: Configuration Frost protection plant Depending on the actual outside temperature the pumps will be switched on, even if there is no heat demand. Device data Line no. 6120 Internal device settings configuration Factory setting Frost protection plant Pump ...-4°C Continuously ON ON -5...1.5°C ON for 10 minutes at 6 hours intervals C ycle 1.5°C... Continuously OFF OFF Line no.. Line no.
Menu: LPB Device address and Segment address The controller LPB address is divided into 2 parts each consisting of two 2-digit numerals. Example: 14 Segment address . 16 Device address When grouping several controllers using LPB - Bus, specifying an address for each component is necessary. The device address must be unique in the segment 43 Line no. Operating line Factory setting 6600 Device address 1 6601 Segment address 6006 LPB – bus config. 0 0 0001.
Menu: Fault, Service/special operation Line no. When a fault is pending, an error message can be displayed on the info level by pressing the Info button. The display describes the cause of the fault. Operating line 6705 SW Diagnostic code 6741 Time before alarm HC2 Factory setting --240 min. SW Diagnostic code An internal software error currently pending in the system is displayed here with diagnostic code indicating where the error occurred.
Menu: Service/special operation Chimney sweep function The burner is started up. To ensure that burner operation will be as continuous as possible, only maximum limitation of the boiler temperature is active to be used as the switch off point. To reach the minimum boiler temperature of 60 °C as quickly as possible, all consumers are locked for that period of time by an absolute locking signal. Line no.
Menu: State, Diagnostics, sensor values State The current operating state of the plant is visualized by means of status displays. Line no. Operating line 8000 State HC 1 8001 State HC 2 8003 State DHW 8005 State Boiler Diagnostics heat generation For diagnostic purposes, the various setpoints, actual values, relay switching states and meter readings can be displayed. Line no. 8310...
Menu: Burner control The burner control guarantees the proper functioning of the boiler including boiler start up, shutdown and flame supervision. The procedure itself is defined by parameters set by the manufacturer. Line no. Operating line The values in the table below are classed to various boiler capacities and they should not be changed by installers. Only in certain cases should they be changed by Elco engineers. THISION S 9.1 THISION S 13.1 13.1 DUO THISION S 17.1 17.1 DUO THISION S 17.1 F 25.
Technical specifications Power supply Rated voltage AC 230 V (10% / -15%) Rated frequency 50 Hz (5%) Maximum power consumption LMU 7, 17 VA Terminal strip wiring (Supply and outputs) Solid or stranded wire (twisted or with conductor end sleeve): 2 2 1 conductor: 0.5 mm ...2.5 mm 2 2 2 conductors 0.5. mm ..1.