Operation Manual

Parameters professional installer
Menu
Line no.
Operating line
Unit
Min.
Max
Factory setting
Holidays HC1
642
Period Start Day / Month
tt.MM
01.01
31.12
--.--
--.--
643
Periode End Day / Month
tt.MM
01.01
31.12
--.--
648
Operating level
-
Frost protection, Reduced
Frost protection
Holidays HC2
(when activated)
652
Period Start Day / Month
tt.MM
01.01
31.12
--.--
653
Periode End Day / Month
tt.MM
01.01
31.12
--.--
658
Operating level
-
Frost protection, Reduced
Frost protection
HC 1
710
Comfort setpoint
°C
Value from Line no. 712
35
20.0
712
Reduced setpoint
°C
Value from Line no. 714
Value from Line no. 710
16.0
714
Frost protection setpoint
°C
4
Value from Line no. 712
4
720
Heating curve slope
-
0.10
4.00
1.50
721
Heating curve parallel
displacement
°C
-4.5
4.5
0.0
726
Heating curve adaption
°C
Off, On
Off
730
Summer/winter heating limit
°C
---/8
30
20
732
24-hour heating limit
°C
---/-10
10
-3
740
Flow temp setpoint min
°C
8
Value from Line no. 741
8
741
Flow temp setpoint max
°C
Value from Line no. 740
80
80
750
Room influence
%
---/0
100
20
760
Room temp limitation
°C
---/0.5
4
1
770
Boost heating
°C
---/0
20
2°C
780
Quick setback
-
Off, Down to Reduced setpoint,
Down to Frost protection setpoint
Down to Reduced
setpoint
790
Optimum start control max
min
0
360
0
791
Optimum Stop control max
min
0
360
0
800
Reduced setp increase start
°C
---/30
10
---
801
Reduced setp increase end
°C
-30
Value from Line no. 800
-15
850
Floor curing function
-
Off, Functional heating, Curing heating,
Functional/Curing heating, Manually
Off
851
Floor curing setp manually
°C
0
95
25
884
Speed design point
-
1
50
9-13 kW = 16
17-25 kW =
19
35-50 kW =
24
885
Pump PWM min
%
10
100
40 %
886
Standard outside temp
°C
-50
+20
- 15°C
887
Flow temp setp standard OT
°C
20
90
75 °C
888
Curve readj at 50% speed
%
0
100
40
894
dT differential standard OT
°C
2.5
20
20
895
dT differential max
°C
2.5
35
20
11