Operation Manual

Parameters professional installer
Menu
Line no.
Operating line
Unit
Min.
Max
Factory setting
HC 2
(when activated)
1010
Comfort setpoint
°C
Value from Line no. 1012
35
20.0
1012
Reduced setpoint
°C
Value from Line no. 1014
Value from Line no. 1010
16.0
1014
Frost protection setpoint
°C
4
Value from Line no. 1012
4
1020
Heating curve slope
-
0.10
4.00
1.50
1021
Heating curve parallel
displacement
°C
-4.5
4.5
0.0
1026
Heating curve adaption
°C
Off, On
Off
1030
Summer/winter heating limit
°C
---/8
30
20
1032
24-hour heating limit
°C
---/-10
10
-3
1040
Flow temp setpoint min
°C
8
Value from Line no. 1041
8
1041
Flow temp setpoint max
°C
Value from Line no. 1040
80
80
1050
Room influence
%
---/0
100
20
1060
Room temp limitation
°C
---/0.5
4
1
1070
Boost heating
°C
---/0
20
2°C
1080
Quick setback
-
Off, Down to Reduced setpoint,
Down to Frost protection setpoint
Down to Reduced
setpoint
1090
Optimum start control max
min
0
360
0
1091
Optimum Stop control max
min
0
360
0
1100
Reduced setp increase start
°C
---/30
10
---
1101
Reduced setp increase end
°C
-30
Value from Line no. 1100
-15
1130
Mixing valve boost
°C
0
50
6
1134
Actuator running time
s
30
873
120
1135
P-Band (Xp) HC1
°C
1
100
32
1150
Floor curing function
-
Off, Functional heating, Curing heating,
Functional/Curing heating, Manually
Off
1151
Floor curing setpt manually
°C
0
95
25
1155
Floor curing setpt current
°C
-
-
Indication only
Domestic hot
water (DHW)
1610
Nominal setpoint
°C
Value from Line no. 1612
65
55
1612
Reduced setpoint
°C
8
Value from Line no. 1610
40
1620
Release
-
24h/Day, Time programs HCs,
Time program 4/DHWTime programs HCs
Time programs HCs
1640
Legionella function
-
Off, Periodically, Fixed weekday
Off
1641
Legionella function
periodically
-
1
7
3
1642
Legionella funct Day
-
Mo,Tu,We,Th,Fr,
Sa,Su
We, Su
Monday
1644
Legionella funct time
h:m
00:00
23:50
---
1645
Legionella funct setpoint
°C
55
95
65
1646
Legionella funct duration
min
---/10
360
10
1647
Legionella funct circ pump
-
On
Off
On
1660
Circulating pump release
-
Time program 3/HCP, DHW release,
Time program 4/DHW
DHW release
1661
Circulating pump cycling
-
Off, On
On
12