Operation Manual

Parameters professional installer
Menu
Line no.
Operating line
Unit
Min.
Max
Factory setting
Configuration
5701
Hydraulic diagram
2
85
3, DUO 60, Combi 7
5710
Heating circuit 1
-
Off
On
On
5715
Heating circuit 2
-
Off
On
On
5732
Pump off change div valve
s 0 10 0, Combi 4
5733
Delay pump off
s 0 10 0, Combi 2
5761
System pump Q8
see description
0000 0000
5920
Relay output K2 LMU basics
Bit 0-7
see description
Default
5921
Default K2 to K1
No
Yes
No
5922
Relay output 1 RelCl
0 Default, no function
1 Status output
2 Alarm output
3 Status information
4 External transformer
5 HC pump 2 (Q2Y2)
6 DHW circulating pump
7 Enabled warm air curtain function actuator
8 Pump pressureless header
9 System pump (Q8)
10 Basic function K2
11 Actuator DHW heating (storage tank)
12 Analogue signal
13 Flue gas damper control
14 Collector pump
15 Fan shutdown
16 Pump Q1
17 DHW mixing pump (Q35)
Basic function K2
5923
Relay output 2 RelCl
Status output
5924
Relay output 3 RelCl
Alarm output
5926
Relay output 1 SolCl
collector pump
5927
Relay output 2 SolCl
Status output
5928
Relay output 3 SolCl
Alarm output
5950
Function input H1
0: None
1: Modem funcition,
2: Modem function inverse
3: Warm air curtain function
7: Checkb sign flue gas damper
8: Heat generation lock,
9: Heat generation lockinvers
Modem function
5957
Modem function
Optg mode change :
All CHs and DHW
All HCs
HC1
HC2
Optg mode change
HCs+DHW
5970
Config room thermostat 1
0: None
1: Room thermostat
2: Time switch room level
3: Time switch heat request
4: Time switch DHW level
Room thermostat
5971
Config room thermostat 2
Room thermostat
5973
Function input RelCl
0: None
1: Modem function
2: Modem function inverse
3: Warm air curtain function
4: Preselected setpoint
5: Preselected output
6: Sensor pressureless header
7: Checkb sign flue gas damper
8: Heat generation lock
9: Heat generation lock inverse
11: Heat generation lock sensor
None
5975
Ext flow temp setpoint max
80
5978
Function input SolCl
0: None
10: Collector Sensor
0000 0000
None
6089
Modulating pump speeds
Indication only
6092
Modulating pump PWM
%
0
70
Indication only
6110
Time constant building
H
0
50
5
6112
Gradient room model
min/C
0
300
60
6120
Frost protection plant
Off
On
On
6220
Software version
Indication only
6221
Development index
Indication only
6225
Device family
Indication only
6226
Device variant
136
6227
Object directory version
0
6240
ConfigContr1
0001 0000
6270
ConfigContr4
0100 0000
6300
ConfigContr7
0000 1101
6310
ConfigContr8
0000 0000
6330
ConfigContr10
0000 0000
14