Operation Manual
Parameters professional installer
Menu
Line no.
Operating line
Unit
Min. Max Factory setting
LPB
6600
Device address
-
0
16
1
6601
Segment address
-
0
14
0
6606
LPBConfig0
-
0
1
0001 0000
Fault
6705
SW diagnostic code
6741
Flow temp 2 alarm
min
- - -/10
240
- - -
6800
History 1
h:m
0
255
Indication only
6805
SW diagnostic code 1
-
0
255
Indication only
6810
History 2
h:m
0
255
Indication only
6815
SW diagnostic code 2
-
0
255
Indication only
6820
History 3
h:m
0
255
Indication only
6825
SW diagnostic code 3
-
0
255
Indication only
6830
History 4
h:m
0
255
Indication only
6835
SW diagnostic code 4
-
0
255
Indication only
6840
History 5
h:m
0
255
Indication only
6845
Flow temp 2 alarm
min
0
255
Indication only
Service/Special
operation
7001
Message
Indication only
7007
Display messages
Off
On
Off
7010
Acknowledgement message
No
Yes
No
7011
Repetition time message
Days
0
7012
Reset messages 1-6
-
No
Yes
No
7040
Burner hours interval
h
- - -/10
10000
- - -
7041
Burn hrs since maintenance
h
0
10000
0
7042
Burner start interval
- - -/60
65535
- - -
7043
Burn starts since maint
0
65535
0
7044
Maintenance interval
Months
- - -/1
240
- - -
7045
Time since maintenance
Months
0
240
0
7051
Message ionization current
0
7130
Chimney sweep function
Off
On
Off
7140
Manual control
Off
On
Off
7143
Controller stop function
Off
On
Off
7145
Controller stop setpoint
%
0
100
0
7146
Deaeration function
-
Off
On
Off
State
8000
State heating circuit 1
Different state messages
8001
State heating circuit 2
8003
State DHW
8005
State boiler
8007
State solar
15