Operation Manual

Menu: Heating circuits
For heating circuits, there are various
functions available which can be
individually set for each heating circuit.
Room setpoint
Room temperature
The room temperature can be shifted
according to different setpoints. These
setpoints become active depending on
the selected operating mode, thus
producing different temperature levels
in the rooms. The ranges of adjustable
setpoints result from the
interdependencies, as this is shown in
the following diagram.
Frost protection
In protection mode, the room
temperature is prevented from falling
below a certain level. This means that
the frost protection setpoint of the
room temperature will be maintained.
Heating curve
The heating curve is used to
generate the flow temperature
setpoint, shich is used to maintain a
certain flow temperature level
depending on the prevailing weather
conditions. The heating curve can
be adjusted with a number of
settings, thus matching heat output
and room temperature to individual
needs.
Line no.
Operating line
Factory setting
HC1
HC2
710
1010
Comfort setpoint
20°C
712
1012
Reduced setpoint
16°C
714
1014
Frost protection
4°C
TRF
TRKmax Comfort setpoint maximum
TRK Comfort setpoint
TRR Reduced setpoint
TRF Frost protection setpoints
Line no.
Operating line
Factory setting
HC1
HC2
720
-
Heating curve slope
1,5
-
1020
Heating curve slope
0,8
721
1021
Heating curve displacement
0
726
1026
Heating curve adaption
Off
22