Operation Manual

Menu: Heating circuits
Line no.
Operating line
Factory setting
HC2
1130
Mixing valve boost
5°C; (DUO 0°C)
1134
Actuator running time
135s; (DUO 150s)
Mixing valve control
Mixing valve boost
To ensure proper mixing valve flow
temperature control, the flow
temperature must be higher than the
demanded setpoint of the mixing valve
flow temperature. The value set here
is added to the request.
The selection of the type of actuator
determines the control behavior for
the type of mixing valve actuator
used.
Actuator running time
Setting the running time of the actuator
used with the mixing valve.
Floor curing function
The floor curing function ensures
controlled drying of the floor. It controls
the flow temperature according to a
temperature profile. Drying of the floor
is ensured via the floor heating system
and the mixing or pump heating circuit.
Floor curing function
Off
Function is deactivated.
Functional heating
The first part of the temperature profile
is automatically completed.
Curing heating
The second part of the temperature
profile is traversed automatically.
Functional/curing heating
The entire temperature profile (first and
second part) is passed automatically.
Manually
It is not a temperature profile that is
completed, but the floor setpoint is
controlled manually.
Line no.
Operating line
Factory setting
HC1
HC2
850
1150
Floor curing function
Off
Functional heating (Fh)
Curing heating (Bh)
Functional/curing heating
Manually
Off
851
1151
Floor curing setp manually
25°C
Bh Floor curing heating
Fh Functional heating
X Start day
Observe the relevant standards and
regulations of the floor manufacturer
Proper functioning is ensured only
when the plant is correctly installed
(hydraulic system, electrical installation,
setting)! If not observed, the floor might
get damaged!
The function can be aborted by
choosing Off
Maximum limitation of the flow
temperature remains active
28