Operation Manual
Menu: DHW
Setpoints
The DHW setpoint acting on the
control is selected based on the
current operating level which
includes impact of the operating
mode, the release (possibly the
switching program), the DHW push
and the 0 legionella function.
Line no.
Operating line
Factory setting
1610
Nominal setpoint
55°C
1612
Reduced setpoint
40°C
DHWmax DHW nominal setpoint maximum
DHWN DHW nominal setpoint
DHWR DHW reduced setpoint
Release
24h/Day
When this setting is used, DHW heating
is continuously released as long as it is
switched on. The DHW setpoint is
always the nominal setpoint, unless the
legionella function has been activated.
Time programs HCs
When this setting is used, DHW heating
is released during the occupancy times
of the connected heating circuits. If at
least one of the heating circuits is at the
Comfort level, DHW heating will also be
released. If all heating circuits are at
the reduced level or in protective mode,
the DHW level will also be set to
reduced.
Time program 4/DHW
When using this setting, a specific time
program is available for DHW heating.
For every weekday, a time program
with a maximum of three on phases
can be set. During the release time, the
nominal DHW setpoint applies, outside
the release time, the reduced DHW
setpoint.
Line no.
Operating line
Factory setting
1620
Release
24h/day
Time programs HCs
Time program 4/DHW
Time program heating circuits
example
2371Z18
0 6 12 18 24 h
2377Z16
example
24 h
6 12
16 17
31
DHWmax
DHWN
DHWR