Operation Manual
Menu: Boiler
Line no.
Operating line
Factory setting
2201
Heat generation lock
Off
2210
Setpoint min
20°C
2212
Setpoint max
See table below
2214
Setpoint manual control
60°C
2440
Fan PWM heating max
See table below
2442
Fan PWM controller delay
See table below
2444
Output min
See table below
2445
Output nominal
See table below
2451
Burner off time min
300 s
2459
Locking time dynamic SD
10 s
2471
Pump overrun time HCs
5 min.
2540
Proportional coefficient Kp DHW
See table below
2543
Proportional coefficient Kp HCs
See table below
Heat generation lock
With this parameter, the heat
generation lock function is released. If
this is the case, the burner and the
boiler pump are turned off when, for
example, due to a programmed input or
a sensor of the clip-in AGU 2514, the
burner is locked from the outside or the
temperature at the sensor of the clip-in
is high enough to supply the
consumers.
Setpoints
The controlled boiler temperature
setpoint can be limited with Setpoint min
and -max. These limitations can be
considered to be a protective function
for the boiler. In normal operation,
minum limitation of the boiler
temperature is the lower limit value for
the controlled boiler temperature
setpoint, depending on the boiler´s
operating mode. In normal operation,
maximum limitation of the boiler
temperature is the upper limit value for
the controlled boiler temperature
setpoint and setpoint for the electronic
limit thermostat (TR).
The adjustment range for the minimum
and maximum setpoints is limited by the
manual mode setpoint.
Setpoint manual control
In manual control, the common flow
temperature setpoint can be set to a
fixed value.
Fan PWM heating max
(cannot be changed).
PWM signal for the maximum capacity
of the unit in heating mode (for values
for the different ratings, see table).
33
Fan PWM controller delay
(cannot be changed).
PWM signal for device output after the
ignition phase and before modulation
release (for values for the different
ratings, see table).
Output min
(cannot be changed).
Minimum device output in kW (for
values for the different ratings, see
table).
Output nominal
(cannot be changed).
Maximum heating output in kW (for
values for the different ratings, see
table).
Burner off time min
After switching off the burner,
reconnection is prevented for this time.
In the case of shorter cycle times the
device clocks more often, for longer
periods less frequently.
Locking time dynamic SD
(cannot be changed).
(Values for different ratings see
table).
Pump overrun time HCs.
Pumps for heating circuits, also
internal device pump, will run for this
time.
Proportional coefficient Kp DHW,
Proportional coefficient Kp HCs
(cannot be changed).
These values determine the heat-up
behaviour of the device (for values
for the different ratings, see table).
Line no.
THISION S
Operating line
9.1
13.1
(Duo)
17.1
(Duo)
17.1
liquid-
gas
25.1
(Duo)
25.1
Combi
35.1
50.1
50.1
Combi
Unity
2212
Setpoint max
85
85
85
85
85
85
78
78
85
2440
Fan PWM heating
max
60
55
58
31
52
52
40
70
40
%
2442
Fan PWM controller
delay
18 18 18 18 18 18 16 16 16 %
2444
Output min
1
2
2
5
5
5
10
10
10
kW
2445
Output nominal
9
13
17
25
25
25
35
50
35
kW
2540
Proportional
coefficient Kp DHW
0,75
0,75
0,75
0,75
0,75
1
0,062
0,062
1
2543
Proportional
coefficient Kp HCs
0.125
0.125
0.125
0.125
0.125
0.125
0.062
0.062
0.062