Operation Manual
Menu: Solar
General:
The solar function and the solar menu
are only active when a solar Clip-In
AGU 2.530 and collector sensor are
connected to the LMU. In addition, in
the configuration menu, in parameter
5978, the function input SolCl is set to
collector sensor.
Solar
Charging controller (dT)
For charging the storage tank via the
heat exchanger, the temperature
differential between collector and tank
must be sufficient, and the collector
must have reached the minimum
charging temperature.
Line no.
Operating line
Factory setting
3810
Temp diff ON exchanger 1
8 °C
3811
Temp diff OFF exchanger 1
4 °C
3812
Charg temp min exchanger 1
30°C
Min heat transfer temperature:
The solar charging is released when
this temperature is exceeded at the
collector.
Tcol Collector temperature
On / Off Collector pump
SdOn Temperature differential on
SdOff Temperature differential off
TSp Storage tank temperature
TLmin Charging temperature minimum
Line no.
Operating line
Factory setting
3831
Min run time collector pump
60s
3840
Collector frost protection
- - -
3850
Collector overtemp prot
- - -
3860
Evaporation heat carrier
110°C
Evaporation heat carrier
If there is a risk of the heat carrying
medium evaporating due to high
collector temperatures, the collector
pump will be deactivated to prevent it
from reaching excessive temperatures.
This is a protective pump function.
Min run time collector pump
When the collector pump is activated, it
remains on for the minimum running
time
Collector frost protection
When there is risk of frost at the
collector, the collector pump will be
activated to prevent the heat-carrying
medium from freezing.
Collector overtemp protection
If there is a risk of overtemperature at
the collector, storage tank charging is
continued to reduce the amount of
surplus heat. When the storage tank
safety temperature is reached, charging
will be stopped.
35
Tcol
SdOn
SdOff