Menu: DHW storage tank
Charging
Flow setpoint boost
The DHW request to the boiler is made
up of the current DHW setpoint plus the
adjustable charging boost.
Line no.
Operating line
Factory setting
5020
Flow setpoint boost
See table
Line no..
Operating line
5020
9 - 25 kW
25 kW Combi
35 - 50 kW
17°C
8°C
15°
Recooling collector
With solar function activated, excess
energy from the drinking water tank
when the collector is cold (at night) is
routed to the environment via the
collector.
Recooling temp
If activated, the recooling function
remains in operation until the adjusted
recooling temperature in the DHW
storage tank is reached.
Line no.
Operating line
Factory setting
5055
Recooling temp
70°C
Menu: DHW - Direct heat transfer
Line no.
Operating line
Factory setting
5400
Comfort setpoint
40°C
The parameter line no. 5450 - 5487 may not be changed.
This menu is only active on a
THISION S Combi with the hot water
continuous flow principle, via a plate
heat exchanger.
Comfort setpoint
To ensure a high DHW availability the
boiler is constantly kept at this
temperature.
More comfort requires an increase in
the comfort setpoint.
Menu: Configuration
Line no.
Operating line
Factory setting
5701
Hydraulic diagram
3;
60 with DUO boiler;
7 with 50 kW Combi boiler
Hydraulic diagram
With this setting, the hydraulic
diagram is generated. The setting 3
illustrates a circuit with speed-
controlled pump and hot water
loading via a 3-way valve
The factory settings should only be
changed if other settings are
specified in the supplied hydraulic
standard.