Operation Manual
Menu: Configuration
Line no.
Operating line
Factory setting
HC1
HC2
5710
Heating circuit 1
On
5715
Heating circuit 2
On
Line no.
Operating line
Factory setting
5732
Pump off change div valve
0s;
with Combi 4s
5733
Delay pump off
0s;
with Combi 2s
5761
System pump Q8
No
Heating circuit 1,2
The HCs can be switched on or off
DHW pump off switch
Duration of the pump shutdown when
reversing the reversing valve between
heating and DHW operation.
If the parameter is set to 0 there is no
pump shutdown. In addition, working
with the delay in parameter 5733 must
be set to 0 seconds.
DHW pump off delay
Duration of delay in the course of the
valves change-over, when interlocking
between heating and DHW operation
(0 = no delay).
System pump Q8
Here you can set whether the system
pump Q8 is to support the heat
requirements of the whole zone or
only of HC1, HC2 or DHW (bits 0-3).
Line no.
Operating line
Factory setting
5920
Relay output K2 LMU basics Bit 0-
7
Default
5921
Default K2 to K1
No
5922
Relay output 1 RelCl
Basic function K2
5923
Relay output 2 RelCl
Status output
5924
Relay output 3 RelCl
Alarm output
5926
Relay output 1 SolCl
collector pump
5927
Relay output 2 SolCl
Status output
5928
Relay output 3 SolCl
Alarm output
The following functions can be set:
0 Default (function as plumbing diagram)
1 Status output
2 Alarm output
3 Status information
4 External transformer switch off
5 Pump 2. Heating circuit
6 Potable water circulating pump
7 Enabled warm air curtain function actuator
8 Pump low loss header (on/off for consumer side pump)
9 System pump (Q8)
10 Basic function K2 (as Default, function as plumbing diagram)
11 Actuator for potable water heating in conjunction with stratified storage tank
12 Analogue signal (on Clip-In function module) above threshold actuator
13 Flue gas damper control
14 Collector pump
15 Fan shutdown
16 Free
17 Potable water mixing pump (Q35) (with Legionella function enabled)
Programmable outputs
On the LMU, the K2 relay output or the
clip-in relay outputs 1-3 can be
programmed with the following
functions, as long as they are already
defined by a particular hydraulic
diagram as a function.
Relay output K2 LMU -
base, default K2 to K1
In some hydraulic diagrams the
programmable output K2 is assigned
to a basic function.
This basic function is set on the K1
output using this parameter.
This means that another
programmable function can be set
on the K2 output.
If the "Default K2 to K1" parameter is
set, the function of output K1 is
overwritten with the basic function of
the output K2.
37