© January 2013 Aqua-Hot
®
600-D01 Series Hydronic Heating System Service Manual - Rev. A
SECTION 9: DIESEL-BURNER COMPONENTS
Be sure to remove the jumper wire that was used to make the
connection from the C-1 location to the C-7 location. Failure
to do so will result in an overheating condition during normal
operation.
Replacement Procedure:
1.
Remove both the B-plug and the C-plug from the
diesel-burner controller. Gently pry away each side
of the diesel-burner controller bracket from the die-
sel-burner controller’s locking posts with a flat-head
screw driver. Once the locking posts have been
released, pull on the diesel-burner controller to re-
move it from the diesel-burner head.
2.
Slide the new diesel-burner controller into the diesel
-burner controller bracket. Push down on the diesel
-burner controller until the locking posts snap into
the bracket slots.
3.
Reconnect the B-plug and the C-plug.
NOTE:
Be sure to install the diesel-burner controller
with it’s C-plug and B-plug ports facing downward. Failure
to do so, will result in moisture collecting in the ports and
potential damage to the diesel-burner controller’s internal
circuitry.
Figure 62
Figure 63
NOTE: If the Control Box is replaced and the Ignition
Coils still will not operate, it is possible the Electronic Con-
troller is defective.