Service manual

5-16
PERFORMANCE DATA & PRESSURE CURVES
SM DNGDCI 2-E.1 GB
5.4 DNG 80 DCI
5.4.1 Cooling Capacity (kW)
ID COIL ENTERING AIR DB/WB TEMPERATURE [C
0
]
OD COIL
ENTERING AIR DB
TEMPERATURE [C
0
]
DATA 22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 7.25 7.72 8.20 8.67 9.15
SC 6.01 6.13 6.25 6.38 6.50
PI 1.95 1.99 2.02 2.06 2.10
30
TC 6.90 7.37 7.85 8.32 8.80
SC 5.86 5.98 6.10 6.22 6.35
PI 2.18 2.21 2.25 2.29 2.33
35
TC 6.55 7.03 7.50 7.97 8.45
SC 5.70 5.83 5.95 6.07 6.20
PI 2.41 2.44 2.48 2.52 2.55
40
TC 6.20 6.68 7.15 7.63 8.10
SC 5.55 5.68 5.80 5.92 6.04
PI 2.63 2.67 2.71 2.75 2.78
46
TC 5.78 6.26 6.73 7.21 7.68
SC 5.37 5.49 5.62 5.74 5.86
PI 2.91 2.94 2.98 3.02 3.06
LEGEND
TC Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
5.4.2 Capacity Correction Factors (Cooling)
Cooling Capacity Ratio Vs. Outdoor Temperature
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ratio
CONTENT