Service manual

12-3
CONTROL SYSTEM
SM DNGDCI 2-E.1 GB
OAT ODUCodeH ODUCodeC IDU NLOAD
≤ -5 3 3 Refer to sect.1.12..1
≥ -5 3.8 3
12.1.3 Frequency Changes Control
When the unit is running normally , the compressor frequency change rate is 1 Hz/sec.
12.1.4 Compressor Starting Control
12.1.4.1 Compressor starting control for DCI50/60
Frequency
Time
Min 10 Minutes
1
Minute
Step 1
Step 3
1
Minute
Step 2
12.1.4.2 Compressor starting control for DCI72/80
Step 1
Whenever the compressor starts up, after it has been off for more than 45 minutes, the compressor
frequency cannot go below Step1RPS for 3 continuous minutes (this rule comes to ensure oil return
to the compressor).
Step 2
The compressor speed cannot go above Step2RPS once after each compressor start up for 3
continuous minutes (this rule comes to prevent oil exit from the compressor after its start up).
Step 3
The speed cannot go higher than Step3RPS unless it was operating for more than 1 continuous
minutes between Step3RPS – 5 and Step3RPS .
After passing above Step3RPS, this rule is re-applied when passing below Step3RPS-5.
CONTENT