Service manual

12-19
CONTROL SYSTEM
SM DNGDCI 2-E.1 GB
12.10 Test Mode
12.10.1 Entering Test Mode
System can enter Test mode in two ways:
Automatically when the following conditions exists for 30 minutes continuously:
Mode = Cool, Set point = 16, Room temperature = 27(+1/−2),
Outdoor temperature = 35(+2/-1)
Or
Mode = Heat, Set point = 30, Room temperature = 20±1,
Outdoor temperature = 7±(+1/-2)
Manually when entering diagnostics with the following settings:
Mode = Cool, Set point = 16
Mode = Heat, Set point = 30
12.10.1.1 Unit Operation in Test Mode
In test mode, the unit will operate in fixed settings according to the indoor fan speed speed :
Indoor FAN Speed Setting Unit Setting
Low Minimum Capacity Setting
Turbo Nominal Capacity Setting
Auto Maximum Capacity Setting
During test mode, protections are disabled, except for stop compressor status.