SX Series R410A Indoor Unit Outdoor Unit SX 9 ONG9 ST/RC SX 12 ONG12 ST/RC SX 15 ONG14 ST/RC SX 18 GC18 ST/RC SX 18 GC18T ST/RC SX 24 OU7-24 ST/RC SX 24 OU7-24T ST/RC SX 30 OU8-30 ST/RC SX 30 OU8-30T ST/RC REFRIGERANT COOLING ONLY R410A HEAT PUMP SM SX Ser1-A.
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ August 2005 Total number of pages in this publication is 149 consisting of the following: Page No. Revision No. # Page No. Revision No.
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The SX split floor and ceiling units range comprise the ST (cooling only) and RC (heat pump) models, as follows: • Cooling Only • Heat Pump 1.2 SX9ST SX12ST SX15ST, SX18ST SX24ST SX30ST SX9RC SX12RC SX15RC, SX18RC SX24RC SX30RC Main Features The SX series benefits from the most advanced technological innovations, namely : 1.3 • R410A • Microprocessor control. • Infrared remote control, and on unit.
INTRODUCTION 1.5 Control The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. The unit is designed with an on unit control board as well. For further details please refer to the Operation Manual, Appendix A. 1.6 Outdoor Unit The SX outdoor units can be installed as floor or wall mounted by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance.
INTRODUCTION 1.10 Matching Table 1.10.1 R410A INDOOR UNITS OUTDOOR UNITS REF’ K9 ONG9 ST MODEL R410A √ K11 K15 K18 WNG9 WNG12 WNG14 WNG18 ONG12 ST R410A ONG14 ST R410A ONG9 RC R410A ONG12 RC R410A ONG14 RC R410A GC18 ST R410A √ √ √ GC18 RC R410A √ √ √ √ SX9 SX12 SX15 √ √ √ √ √ √ SX18 √ √ √ √ √ √ √ √ √* √ √* - the outdoor unit of this combination cannot be matched to other indoor units.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.2 SX 12 / ONG-12 R410A Model Indoor Unit SX-12 Model Outdoor Unit ONG-12 Installation Method of Pipe Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Units Cooling Only Btu/hr 12010 3.52 3.52 3.7 1.155 1.155 1.15 W/W 3.05 3.05 3.22 B B C Rated current A Starting current A Circuit breaker rating A 220-240V/Single/50Hz 5.2 5.
PRODUCT DATA SHEET 2.3 SX 15 / ONG-14 R410A Model Indoor Unit SX-15 Model Outdoor Unit ONG-14 Installation Method of Pipe Flared Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Units Cooling Only Cooling Heating Btu/hr 13990 13990 15350 kW 4.1 4.1 4.5 kW 1.355 1.355 1.380 W/W 3.03 3.03 3.26 B B C Energy efficiency class Power supply V/Ph/Hz Rated current A Starting current A Circuit breaker rating A 220-240V/Single/50Hz 6.4 6.
PRODUCT DATA SHEET 2.4 SX 18 / GC-18 R410A Model Indoor Unit SX-18 Model Outdoor Unit GC-18 Installation Method of Pipe Flared Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Units Cooling Only Cooling Heating Btu/hr 18770 18770 19620 kW 5.5 5.5 5.75 kW 1.82 1.82 1.77 W/W 3.02 3.02 3.25 B B C Energy efficiency class Power supply V/Ph/Hz Rated current A Starting current A Circuit breaker rating A 220-240V/Single/50Hz 8.2 8.
PRODUCT DATA SHEET 2.5 SX 18 / GC-18 3PH R410A Model Indoor Unit SX-18 Model Outdoor Unit GC-18 3PH Installation Method of Pipe Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Flared Cooling Units Cooling Only Btu/hr 18760 18760 19600 kW 5.5 5.5 5.75 kW 1.77 1.77 1.69 W/W 3.12 3.12 3.41 B B B Energy efficiency class Power supply V/Ph/Hz Rated current A Starting current A Circuit breaker rating A 380/3/50Hz 3.1 3.
PRODUCT DATA SHEET 2.6 SX 24 / OU7-24 R410A Model Indoor Unit SX-24 Model Outdoor Unit Installation Method of Pipe Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Units Cooling Only Btu/hr 23300 23300 24000 kW 6.83 6.83 7.03 kW 2.27 2.27 2.13 W/W 3.01 3.01 3.03 B B C Energy efficiency class Power supply V/Ph/Hz Rated current A Starting current A Circuit breaker rating A 9.7 9.
PRODUCT DATA SHEET 2.7 SX 24 / OU7-24Z R410A Model Indoor Unit SX-24 Model Outdoor Unit OU7-24Z R410A Installation Method of Pipe Characteristics Capacity Units Btu/hr kW kW W/W (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET 2.8 SX 24 / OU7-24T R410A Model Indoor Unit SX-24 Model Outdoor Unit OU7-24T Installation Method of Pipe Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Cooling Only Btu/hr 23300 23300 24000 kW 6.83 6.83 7.03 kW 2.27 2.27 2.13 W/W 3.01 3.01 3.
PRODUCT DATA SHEET 2.9 SX 30 / OU8-30 R410A Model Indoor Unit SX 30 Model Outdoor Unit OU8-30 Installation Method of Pipe Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Cooling Only Btu/hr 29,100 29,100 kW 8.52 8.52 8.65 kW 2.99 2.99 2.79 W/W 2.85 2.85 3.10 C D Energy efficiency class C Power supply V/Ph/Hz Rated current A Starting current A Circuit breaker rating A 12.2 12.
PRODUCT DATA SHEET 2.10 SX 30 / OU8-30T R410A Model Indoor Unit SX 30 Model Outdoor Unit OU8-30T Installation Method of Pipe Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Flared Cooling Units Cooling Only Btu/hr 28300 28300 28,300 kW 8.30 8.30 8.30 kW 2.77 2.77 2.63 W/W 3.00 3.00 3.15 C D Energy efficiency class C Power supply V/Ph/Hz Rated current A 400V/3/50 3x5.2 3x5.
RATING CONDITIONS 3. RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.1 Operating Limits R410A Indoor Cooling Heating Voltage SM SX Ser1-A.
OUTLINE DIMENSIONS 4. OUTLINE DIMENSIONS 4.1 Indoor Unit : SX 9, 12, 15 R410A 4.2 Indoor Unit : SX 18, 24, 30 R410A SM SX Ser1-A.
OUTLINE DIMENSIONS 4.3 4.4 4-2 Outdoor Unit : ONG 9, 12, 14 Outdoor Unit : GC 18 CONTENT SM SX Ser1-A.
OUTLINE DIMENSIONS 4.5 Outdoor Unit : OU7-24 / OU7-24Z 4.6 Outdoor Unit : OU8-30 SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5. PERFORMANCE DATA 5.1 SX 9 / ONG9 R410A 5.1.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15(1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 2.80 1.85 0.59 2.71 1.81 0.64 2.57 1.77 0.69 2.40 1.71 0.74 2.22 1.63 0.80 2.02 1.53 0.87 1.75 1.41 0.95 2.90 1.93 0.59 2.86 1.91 0.64 2.77 1.88 0.
PERFORMANCE DATA & PRESSURE CURVES 5.1.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL ( °C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 1.46 1.58 1.67 2.04 2.87 3.12 3.38 3.56 0.69 0.71 0.71 0.75 0.80 0.85 0.89 0.91 1.41 1.52 1.62 1.95 2.79 3.04 3.29 3.47 0.73 0.74 0.76 0.80 0.86 0.91 0.95 0.99 1.35 1.46 1.56 1.87 2.69 2.96 3.21 3.38 0.77 0.78 0.80 0.84 0.91 0.97 1.01 1.
PERFORMANCE DATA & PRESSURE CURVES 5.3 Pressure Curves. 5.3.1 Cooling. Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure VS.
PERFORMANCE DATA & PRESSURE CURVES 5.3.2 Heating. Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) 5-4 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.4 SX 12 / ONG12 R410A 5.4.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15(1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 3.71 2.40 0.82 3.59 2.35 0.89 3.40 2.29 0.96 3.18 2.22 1.04 2.94 2.11 1.12 2.67 1.99 1.21 2.32 1.83 1.32 3.84 2.50 0.82 3.78 2.48 0.90 3.67 2.43 0.97 3.46 2.36 1.06 3.
PERFORMANCE DATA & PRESSURE CURVES 5.4.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 1.94 2.09 2.22 2.70 3.81 4.14 4.48 4.72 0.92 0.94 0.95 1.00 1.08 1.14 1.18 1.22 1.87 2.02 2.15 2.59 3.70 4.03 4.37 4.61 0.98 0.99 1.01 1.06 1.15 1.21 1.28 1.32 1.79 1.94 2.07 2.48 3.57 3.92 4.26 4.48 1.03 1.05 1.07 1.13 1.22 1.30 1.36 1.
PERFORMANCE DATA & PRESSURE CURVES 5.6 Pressure Curves. 5.6.1 Cooling. Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure VS.
PERFORMANCE DATA & PRESSURE CURVES 5.6.2 Heating. Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 5.0 20 DB (ºC) 25 DB (ºC) 4.0 3.0 -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) 5-8 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.7 SX 15 / ONG14 R410A 5.7.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15(1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 4.32 2.74 0.96 4.18 2.69 1.04 3.96 2.62 1.12 3.70 2.54 1.21 3.43 2.41 1.31 3.11 2.27 1.41 2.70 2.09 1.54 4.48 2.86 0.96 4.41 2.83 1.04 4.27 2.78 1.13 4.03 2.70 1.23 3.
PERFORMANCE DATA & PRESSURE CURVES 5.7.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 2.36 2.54 2.70 3.29 4.64 5.04 5.45 5.74 1.10 1.13 1.15 1.20 1.29 1.36 1.42 1.46 2.27 2.45 2.61 3.15 4.50 4.91 5.31 5.60 1.18 1.19 1.21 1.28 1.38 1.46 1.53 1.59 2.18 2.36 2.52 3.02 4.34 4.77 5.18 5.45 1.24 1.26 1.28 1.35 1.47 1.56 1.63 1.
PERFORMANCE DATA & PRESSURE CURVES 5.9 Pressure Curves. 5.9.1 Cooling. Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure VS.
PERFORMANCE DATA & PRESSURE CURVES 5.9.2 Heating. Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) 5-12 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.10 SX 18 / GC18 R410A 5.10.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI (1) 20(1) 25 30 TC SC PI 35 TC SC PI TC SC PI 40 46 15/21 17/24 19/27 21/29 23/32 5.80 3.94 1.29 5.61 3.86 1.40 5.31 3.76 1.51 4.96 3.64 1.63 4.59 3.46 1.76 4.18 3.26 1.90 3.62 3.01 2.08 6.00 4.11 1.29 5.91 4.07 1.41 5.73 3.99 1.52 5.40 3.87 1.
PERFORMANCE DATA & PRESSURE CURVES 5.10.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 3.02 3.25 3.45 4.20 5.92 6.44 6.96 7.33 1.42 1.45 1.47 1.54 1.65 1.75 1.82 1.88 2.90 3.13 3.34 4.03 5.75 6.27 6.79 7.16 1.51 1.53 1.56 1.64 1.77 1.87 1.96 2.04 2.79 3.02 3.22 3.85 5.55 6.10 6.61 6.96 1.58 1.61 1.65 1.73 1.88 2.00 2.09 2.
PERFORMANCE DATA & PRESSURE CURVES 5.12 Pressure Curves. 5.12.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.12.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) 5-16 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.13 SX 18 / GC18 3PH R410A 5.13.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI (1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 5.80 4.09 1.25 5.61 4.01 1.36 5.31 3.91 1.47 4.96 3.79 1.59 4.59 3.60 1.71 4.18 3.39 1.85 3.62 3.13 2.02 6.00 4.27 1.26 5.91 4.23 1.37 5.73 4.15 1.48 5.40 4.
PERFORMANCE DATA & PRESSURE CURVES 5.13.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 3.02 3.25 3.45 4.20 5.92 6.44 6.96 7.33 1.35 1.39 1.40 1.47 1.58 1.67 1.74 1.79 2.90 3.13 3.34 4.03 5.75 6.27 6.79 7.16 1.44 1.46 1.49 1.56 1.69 1.78 1.88 1.94 2.79 3.02 3.22 3.85 5.55 6.10 6.61 6.96 1.51 1.54 1.57 1.66 1.79 1.91 1.99 2.
PERFORMANCE DATA & PRESSURE CURVES 5.15 Pressure Curves. 5.15.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB ºC) ºC) ºC) ºC) ºC) 20 25 11.0 10.0 9.0 8.0 7.0 6.0 5.0 15 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.15.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 5.0 20 DB (ºC) 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) 5-20 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.16 SX 24 / OU7-24, OU7-24Z & OU7-24T R410A 5.16.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI (1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 7.20 5.02 1.61 6.97 4.92 1.75 6.59 4.80 1.89 6.16 4.65 2.04 5.71 4.42 2.20 5.19 4.16 2.37 4.50 3.84 2.59 7.46 5.24 1.61 7.34 5.19 1.75 7.12 5.
PERFORMANCE DATA & PRESSURE CURVES 5.16.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 4.06 4.37 4.64 5.65 7.24 7.87 8.51 8.96 1.70 1.75 1.77 1.85 1.99 2.10 2.19 2.26 3.91 4.21 4.49 5.41 7.03 7.66 8.30 8.75 1.81 1.84 1.87 1.97 2.13 2.25 2.36 2.45 3.75 4.06 4.33 5.18 6.78 7.45 8.08 8.51 6.29 6.41 6.54 6.89 7.47 7.93 8.30 8.
PERFORMANCE DATA & PRESSURE CURVES 5.18 Pressure Curves. 5.18.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.18.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) 5-24 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.19 SX 30 / OU8- 30 R410A 5.19.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI (1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 8.98 5.68 2.12 8.69 5.57 2.30 8.22 5.42 2.49 7.69 5.25 2.68 7.12 5.00 2.89 6.47 4.71 3.12 5.62 4.34 3.41 9.30 5.92 2.12 9.16 5.87 2.31 8.88 5.76 2.50 8.37 5.
PERFORMANCE DATA & PRESSURE CURVES 5.19.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 5.00 5.38 5.71 6.95 8.91 9.69 10.47 11.03 2.23 2.29 2.32 2.43 2.61 2.75 2.87 2.96 4.81 5.19 5.52 6.66 8.65 9.43 10.21 10.77 2.38 2.41 2.46 2.58 2.79 2.94 3.10 3.21 4.61 5.00 5.33 6.38 8.35 9.17 9.95 10.47 2.50 2.54 2.59 2.73 2.96 3.15 3.29 3.
PERFORMANCE DATA & PRESSURE CURVES 5.21 Pressure Curves. 5.21.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.21.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) 5-28 CONTENT SM SX Ser1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.22 SX 30 / OU8- 30T R410A 5.22.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI (1) 20(1) 25 30 35 40 46 15/21 17/24 19/27 21/29 23/32 8.75 5.53 1.96 8.46 5.42 2.13 8.01 5.28 2.30 7.49 5.12 2.49 6.93 4.87 2.68 6.31 4.59 2.89 5.47 4.23 3.16 9.06 5.77 1.97 8.92 5.72 2.14 8.65 5.61 2.32 8.15 5.
PERFORMANCE DATA & PRESSURE CURVES 5.22.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 4.79 5.16 5.48 6.66 8.55 9.30 10.04 10.58 2.10 2.16 2.18 2.29 2.46 2.60 2.71 2.79 4.61 4.98 5.30 6.39 8.30 9.05 9.79 10.33 2.24 2.27 2.31 2.43 2.63 2.77 2.92 3.02 4.43 4.79 5.11 6.12 8.01 8.80 9.55 10.04 2.35 2.40 2.45 2.58 2.79 2.97 3.10 3.
PERFORMANCE DATA & PRESSURE CURVES 5.24 Pressure Curves. 5.24.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.24.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) 5-32 CONTENT SM SX Ser1-A.
ELECTRICAL DATA 6. ELECTRICAL DATA 6.1 Single Phase Units MODEL Power Supply Max Current, A Circuit Breaker Power Supply Wiring No. X Cross Section mm2 SX 9 SX 12 SX 15 SX 18 To indoor 1PH-230V-50Hz 7.1 10 To indoor 1PH-230V-50Hz 7.6 16 To indoor 1PH-230V-50Hz 10.4 16 To Indoor To outdoor 1PH-230V-50Hz 12 16 3x1.5 mm2 3x1.5 mm2 3x1.5 mm2 3x2.5 mm2 Interconnecting Cable RC Model 5x1.5 mm2 +2x0.5 mm2 5x1.5 mm2 +2x0.5 mm2 5x1.5 mm2 +2x0.5 mm2 5x2.5 mm2 +2x0.5 mm2 6x1.5 mm2 +2x0.
WIRING DIAGRAMS 7. WIRING DIAGRAMS 7.1 Indoor Unit: SX 9, 12, 15 7.2 Indoor Unit: SX 18, 24, 30 1PH/3PH SM SX Ser1-A.
WIRING DIAGRAMS 7.3 Outdoor Unit: ONG 9, 12, 15 C R 7.4 S Outdoor Unit: GC 18 LEGEND: OPTIONAL: WIRING DIAGRAM ---Heat Pump Model BK-Black BU-Blue BN-Brown OG-Orange RD-Red WH-White GN/YE-Yellow/Green 1.CONNECTED ONLY FOR ALL SEASON UNIT 2.SP--Pressure Control Electronic ( for all season) 3.PTCH--PTC heater for draining water 4.HPS--High Pressure Switch (Only for GC-30RC) CAP.--Capacitor COMP.--Compressor DEICER TEMP.
WIRING DIAGRAMS 7.5 Outdoor Unit: GC 18 3PH WIRING DIAGRAM OF OUTDOOR UNIT 9 XT3 8 DEICER TEMP.
WIRING DIAGRAMS 7.7 Outdoor Unit: OU7-24Z 7.8 Outdoor Unit: OU8-30 1PH (with soft starter) 7-4 CONTENT SM SX Ser1-A.
WIRING DIAGRAMS 7.9 Outdoor Unit: OU7-24 / OU8-30 3PH SM SX Ser1-A.
ELECTRICAL CONNECTIONS 8. ELECTRICAL CONNECTIONS 8.1 SX 9, 12, 15, 18, 8.2 SX 18, 24,30 (Power Supply to Outdoor) SM SX Ser1-A.
ELECTRICAL CONNECTIONS 8.3 8-2 PX 18, 24, 30 3PH CONTENT SM SX Ser1-A.
REFRIGERATION DIAGRAMS 9. REFRIGERATION DIAGRAMS 9.1 Heat Pump Models 9.1.
REGRIGERATION DIAGRAMS 9.1.2 9-2 SX 24 R410A CONTENT SM SX Ser1-A.
REFRIGERATION DIAGRAMS 9.1.3 SX 24 / OU7-24Z R410A SM SX Ser1-A.
REGRIGERATION DIAGRAMS 9.1.4 9-4 SX 30 R410A CONTENT SM SX Ser1-A.
REFRIGERATION DIAGRAMS 9.2 Cooling Only Models 9.2.1 SX 9, 11, 15, 18 OUTDOOR UNIT INDOOR UNIT Service port Compressor Sensor Sensor Valves Capillary tube Outdoor coil 9.2.2 Flared connection Indoor coil Strainer SX 24, 30 SM SX Ser1-A.
TUBING CONNECTIONS 10. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 11-13 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8.
CONTROL SYSTEM 11. CONTROL SYSTEM 11.1 Electronic Control 11.1.1 Introduction The electronic control information is designed for service applications, and is common to the following groups of air-conditioners: ST/RC group SH group RH group 11.1.2 -Cooling only / cooling and heating by heat pump. -Cooling and heating by heat pump and supplementary heater. -Cooling, heating by heaters only.
CONTROL SYSTEM 11.1.3 Remote Control DIP Switch Settings SETTING SWITCH STATUS DEFINITION SW. NO. 1 OFF ON OFF ON -- SW. NO. 2 OFF OFF ON ON -- SW. NO. 3 ----OFF SW. NO. 4 ------ -- -- ON -- -- -- -- OFF TIMER & CLOCK 12H AM, PM -- -- -- ON TIMER & CLOCK 24H RC3 RC4 RC-ALL MODES OF OPERATION STD-COOL, FAN, DRY, ACTIVE HEAT-COOL, FAN, DRY, ACTIVE AUTO FAN (AF) TEMP. DISPLAY IN C DEGREES TEMP.
CONTROL SYSTEM 11.1.4 Main PCB Controller SM SX Ser1-A.
CONTROL SYSTEM 11.1.5 Display Board :LEXAN 11.1.6 Display Board : Assembly 11.1.7 Legend : A) Heating LED B) Cooling LED C) Fan LED D) Operation LED E) Timer LED F) Filter LED G) Temp’ Set Point Indication H) Fan Speed H,(High) I,(Medium) J,(Low) K,(AUTO) L) Reset M) STB’Y LED 11-4 CONTENT SM SX Ser1-A.
CONTROL SYSTEM 11.2 Control Function 11.2.1 Abbreviations AC - Alternate Current A/C ANY CLOCK COMP CPU CTV HE HPC H/W ICP ICT IF, IFAN IR LEVEL1 LEVEL2/3 LEVEL4 Max Min min NA OCP OCT OF, OFAN OPER Para.
CONTROL SYSTEM 11.3 General Functions 11.3.1 COMP Operation a. For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting, excluding DEICING Mode (see para. 14.12.2). b. The Min operation time of COMP under different operating conditions is: Operation Mode Heat, Cool, HP protection or Auto Modes Fan, Dry, Overflow, Protection Modes, or Mode Change 11.3.2 Min Operation Time of COMP 3 min. Ignored IFAN operation a.
CONTROL SYSTEM 11.3.5 11.3.6 Protections a. High pressure protection is applicable to all operating modes. b. Deicing control is valid in Heat and Auto Heat Modes only. c. Defrosting control is valid in Dry, Cool, and Auto Cool Modes. Thermistors Operation a. Return air Temp. is detected by RAT in normal Mode, or by RCT (R/C sensor) in I-FEEL Mode. b. Indoor Coil Temp. is detected by ICT. c. Outdoor Coil Temp. is detected by OCT. d. Definition of thermistor faults: e.
CONTROL SYSTEM 11.3.7 RV Fault This test is applied only in compressor units where 4.7k resistor is not connected to the OCT. The test is performed every time the unit is switched from OFF/STBY to OPER in Heat mode or changes operation mode from COOL/DRY to HEAT or (this applies also in AUTO COOL/HEAT mode).
CONTROL SYSTEM 11.4 Cooling Mode 11.4.1 Cooling Mode – General a. Mode Definition Mode: COOL, AUTO (at Cooling) Temp: Selected desired temperature. Fan: HIGH, MED, LOW, AUTO. Timer: Any I-FEEL: ON or OFF b. Room Temperature, RT, is detected by: RAT in normal operation, or RCT (R/C sensor) in I-FEEL mode. 11.4.2 c. Indoor Coil Temp is detected by ICT. d. Outdoor Coil Temp is detected by OCT. Control Functions a. COMP Operation COMP ON OFF 0 b.
CONTROL SYSTEM 11.4.3 Sequence Diagrams a. Maintaining room temp at desired level by comparing RT and SPT with user defined IFAN speed. (RT - SPT) [oc] +3 +2 +1 0 -1 -2 ON COMP (WVL) OFF ON OFAN OFF USER FAN SPEED IFAN ON RV 11-10 OFF CONTENT SM SX Ser1-A.
CONTROL SYSTEM b. Maintaining room temp at desired level by comparing RT and SPT with AUTO-IFAN. +4 +3 +2 +1 0 -1 -2 (RT - SPT) [oc] ON COMP (WVL) OFF ON OFAN OFF H IFAN M L ON RV OFF SM SX Ser1-A.
CONTROL SYSTEM 11.5 Heating Mode 11.5.1 Heating Mode - General a. Compensation Procedure When I-FEEL is OFF during HEAT mode: RT= RAT – CTV. When I-FEEL is ON during HEAT mode: RT= RCT. Type of Indoor Wall Mounted Mobiles / Floor Ceiling Square /Window Ducted Cassettes CTV +3 oC +0 oC +2 oC +4 oC +4 oC No compensation will be activated in Forced operation modes b.
CONTROL SYSTEM c. IFAN operation rules for RH group 1) d. In RH group, IFAN starts when HE starts. When HE switches to OFF, IFAN switches to LOW for 30 sec and then stops. Heaters operation rules for RC and SH groups: 1) For both RC and SH groups, Heaters versus T is as follows: ON HE1 OFF ON HE2 OFF 1 2) 2 3 4 T=SP-RT [oc] Operation rules for Heaters in RC group: a) Heaters can be enabled only if IFAN is ON.
CONTROL SYSTEM e. Heaters operation rules for RH groups: 1) In RH group, HE operation is according to the difference between RAT and SPT. ON H E2 O FF ON H E1 O FF -1 f. 0 2 T=SP-R T [ o c] OFAN Operation for RC and SH groups 1) As a general rule for RC and SH groups, excluding protection modes, OFAN starts with the compressor. 2) When OFAN is ON it will operate according to the following conditions: a) OFAN operates together with the compressor.
CONTROL SYSTEM 11.6 Heating, RC or SH Group Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I-FEEL: ON or OFF 11.6.1 Sequence Diagram Maintains room temp. at desired level by comparing RAT or RCT to SPT. (RT - SPT) [oc] +2 +1 0 -1 -2 -3 -4 ON COMP (WVL) OFF ON HE1 OFF ON HE2 OFF ON RV OFF SM SX Ser1-A.
CONTROL SYSTEM 11.7 Heating, RC or SH Group with Autofan Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: AUTO Timer: Any I-FEEL: ON or OFF 11.7.1 Sequence Diagram Maintains room temp at desired level by controlling COMP, IFAN and OFAN. (RT - SPT) [oc] +2 +1 0 -1 -2 -3 -4 ON COMP (WVL) OFF ON HE1 OFF ON HE2 OFF ON RV 11-16 OFF CONTENT SM SX Ser1-A.
CONTROL SYSTEM 11.8 Heating, RH Group Mode: HEAT, AUTO (at Heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I-FEEL: ON or OFF 11.8.1 Sequence Diagram Maintains room temp at desired level by controlling Heating Elements: HE1 or HE2. (RT - SPT) in oc +2 +1 0 -1 -2 -3 ON HE1 OFF ON HE2 OFF H/M/L IFAN L OFF 30 sec SM SX Ser1-A.
CONTROL SYSTEM 11.9 Heating, RH Group, with AUTOFAN Mode: HEAT, AUTO (at Heating) Temp: Selected desired temperature Fan: AUTO Timer: Any I-FEEL: ON or OFF 11.9.1 Sequence Diagram Maintains room temp. at desired level by controlling the 2-Stage Electric Heaters. (RT - SPT) in oc +2 +1 0 -1 -2 -3 ON HE1 OFF ON HE2 OFF H IFAN M L OFF -4 -2 -3 -1 30 sec 11-18 CONTENT SM SX Ser1-A.
CONTROL SYSTEM 11.10 Automatic Cooling or Heating 11.10.1 Automatic Cooling or Heating - General The AUTO Mode is for models with compressor and the WVL-RH only. The WVL-ST, RC and SH units do not work in AUTO Mode. a. Mode Definition Mode: AUTO Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: ON or OFF 3OC. b. Switching-temperature between Cooling and Heating is SPT c.
CONTROL SYSTEM 11.10.2 Sequence Diagrams a. Auto Cooling or Heating, RC or SH Groups Maintains room temp. at desired level by selecting between cooling and heating modes. (RT - SPT) [oc] +3 +2 +1 0 -1 -2 -3 -4 Auto Heat Mode ON COMP & OFAN Auto Cool Mode Auto Heat Mode > 4 min > 3 min (3) (3) OFF ON HE1 OFF ON HE2 OFF H/M/L/OFF USER FAN SPEED H/M/L/OFF IFAN > 3 min ON RV 11-20 > 2 min (4) (4) OFF CONTENT SM SX Ser1-A.
CONTROL SYSTEM b. Auto Cooling or Heating RH Group Maintains room temp. at desired level by selecting between Cooling or Heating Modes. (RT - SPT) [oc] +3 +2 +1 0 -1 -2 -3 Auto Heat Mode Auto Cool Mode Auto Heat Mode ON COMP & OFAN OFF ON HE1 > 3 min > 3 min (2) (2) OFF ON HE2 OFF H/M/L IFAN L OFF 30 sec (1) RV OFF 11.11 Dry Mode 11.11.
CONTROL SYSTEM (RT - SPT) [ oc] +2 +1 0 10 20 40 30 50 Time [min] -1 -2 DRY-ON DRY DRY-OFF LOW IFAN OFF 5 minutes COMP ON time ON COMP OFAN OFF Max 15 minutes ON HE1 & HE2 3.5 min Note1 Max 15 minutes 6 min Note 2 OFF ON RV OFF NOTES 1. When DRY is ON, the COMP is forced OFF for 3.5 min (longer than the 3 min Min COMP- OFF time) after every 15 min of continuous COMP operation. 2.
CONTROL SYSTEM 11.11.2 DRY, SH or RH group Mode: DRY Temp: Selected desired temperature Fan: LOW (automatically selected by software) Timer: Any I-FEEL: Any Control function Reduces room humidity with minimum temp. fluctuations by operating in Cool Mode with LOW speed IFAN and HE. (RT - SPT) [ oc] +2 +1 0 10 20 30 40 50 Time [min] -1 -2 LOW IFAN OFF ON COMP & OFAN OFF ON HE1 OFF ON HE2 OFF ON RV OFF SM SX Ser1-A.
CONTROL SYSTEM 11.12 Protection 11.12.1 Cooling Mode Protections a. Indoor Coil Defrost Mode: COOLING, DRY, AUTO Temp: Selected desired temp. Fan: Any Timer: Any I-FEEL: ON or OFF Control Function Protects the indoor coil from ice formation at low ambient temperatures. ICT [oc] +14 +5 +2 +1 0 -1 t1 t2 t3 t1 ON OFAN OFF ON COMP OFF ON IFAN OFF t1 = 5 min minimum for each COMP starting. t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum.
CONTROL SYSTEM b. High Pressure Protection Mode: (AUTO) COOLING or DRY Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: ON or OFF Control Function To protect the COMP from the high pressure build-up in the outdoor coil during normal cooling operation, by switching OFF the IFAN and COMP.
CONTROL SYSTEM 11.12.2 Heating Mode Protections a. Outdoor Coil Deicing (excluding RH Group) Mode: HEATING, AUTO (at heating) Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: Any Control function To protect the outdoor coil from ice formation by controlling COMP & RV operation.
CONTROL SYSTEM 2) Deicing procedure OCT [oc] 12 DOC 0 DST (DDT) 3 min 3 min 36s max 12 min. 36s ON COMP OFF DI (note 1) DI (note 2) ON OFAN OFF 30s 30s ON RV OFF DT RC or WAX units all SH units except WAX ANY IFAN L IFAN is forced to Low Speed ON HE ANY HEs are forced ON ANY IFAN OFF Note 3 ANY HE OFF HEs are forced OFF ON OPER LED BLINK NOTES 1. In the following Deicing cycles, the time interval between two Deicing cycles activation is between 30 to 80 min. 2.
CONTROL SYSTEM b. High Pressure Protection (excluding RH Group) Mode: (AUTO) HEATING Fan: Any Timer: Any I-FEEL: ON or OFF Control Function Protects the compressor from high pressure by switching OFF the OFAN and COMP. ICT [oc] For all models except WAX For WAX model 67 66 61 55 52 Any COMP Off COMP is forced OFF COMP is forced OFF Any OFAN Off OFAN is force Off ON OPER LED 11-28 BLINK CONTENT SM SX Ser1-A.
CONTROL SYSTEM 11.12.3 Condensation Pump (ECC/K model) Mode: Cool, Dry, Auto Temp: Selected desired temperature Fan: Any Timer: Any I FEEL: Any Control function: Prevent Condensed water from Overflowing. Overflow when unit is ON Overflow Water Level Overflow when unit is OFF Normal ON OPER LED OFF BLINK ON COMP (WVL) COMP/WVL is forced OFF OFF ON PUMP OFF 8 min 8 min 1 min Notes: 1.
CONTROL SYSTEM 11.13 Forced Operation (Excluding PRX & PXD Models) a. Forced operation allows units to start, stop and operate in cooling or heating in preset temp. according to the following table: Forced Operation Mode Cooling Heating Pre-set Temp for : MBX, P2000, PX Models 20 ºC 25 ºC Pre-set Temp for : FCD, RWK ,ELD, ECC, WAX, WNX, WMN Models 22 ºC 28 ºC NOTES 1. While under the forced operation, the temperature compensation schedule is disabled. 2.
CONTROL SYSTEM 11.14 SPT Adjustment in Sleep Mode In COOL, AUTO COOL or DRY modes, the SPT adjustment is positive (from 0 to +3oC). In HEAT or AUTO HEAT modes, the SPT adjustment is negative (from 0 to -3oC). In other modes, there is no SPT adjustment. The SPT adjustment is cancelled when the Sleep mode is cancelled.
CONTROL SYSTEM 11.14.1 Time Adjustment in SLEEP Mode In 10V4, the user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below. Case 1 is the Standard Sleep Mode, which is the only sleep mode in the previous version of MCU. The A/C unit simply works for 7 hours, then goes to SB. Case 2 is the new Extended Sleep Mode.
CONTROL SYSTEM 11.15 Controller Self-Test Procedure 11.15.
CONTROL SYSTEM 11.15.2 By Remote Control Settings: a. STEP 1: TURNING ON THE POWER. Turn ON the power, make sure that the unit is in operation. b. STEP 2 : ENABLE SELF-TEST MODE c. 1) Use the remote control to send the first settings to display / indoor unit HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed. 2) Cover the IR transmitter components in the remote control so that it will not transmit the signals to the indoor unit display.
CONTROL SYSTEM d. STEP 3: AUTO LED WALK TEST. 1) All the LEDS will turn OFF. 2) All the LEDS will turn ON for 1 second one by one in the following sequence: STAND-BY Ö OPERATE Ö TIMER Ö FILTER Ö COOL Ö HEAT. 3) e. In PRX all the LEDS will turn ON for 1 second one by one in the following sequence : 18 °c Ö 20 °c Ö 22 °c Ö 24 °c Ö 26 °c Ö 28 °c Ö 30 °c Ö High IFAN Ö Auto IFAN Ö Med IFAN Ö Low IFAN Ö STAND-BYÖ TIMER Ö FILTER ÖCOOLÖ HEAT.
CONTROL SYSTEM Fail condition: 0 sec - STAND-BY is turned ON 3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON When the timing reset test is completed, the next test will start automatically. i. STEP 8: MEMORY TEST (EEPROM) The test purpose is to check if the memory is functioning correctly. The test result is reported by using the STAND-BY and FILTER LEDS: LED Indicator STAND-BY LED FILTER LED Condition for LED to be ON Test passed Test failed AT THIS POINT THE SELF-TEST IS COMPLETED.
CONTROL SYSTEM 11.16 System Diagnostics Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate the DIAGNOSTICS mode, acknowledged by 3 short beeps and lighting of COOL and HEAT LEDs. In DIAGNOSTICS mode, system failures will be indicated by the blinking of HEAT & COOL LEDs. The coding method is as follows: HEAT LED blinks 5 times in 5 seconds, and then turns off for the next 5 seconds. COOL LED blinks during the same 5 seconds according to the following table: No.
TROUBLESHOOTING 12. No. TROUBLESHOOTING SYMPTOM PROBABLE CAUSE 1 Power supply indicator (Red LED) does not light up. No power supply. 2 Unit does not respond to remote control command. Remote control command did not reach the indoor unit. 3 Unit responds to remote control command but operate indicator (Green LED) does not light up. Indoor fan does not start (louvers are opened and Green LED lights up). Problem with display PCB. 4 Change to COOL MODE and check. Problem with PCB or capacitor.
TROUBLESHOOTING No. SYMPTOM 11 One of the protections is activated and compressor is stopped with no apparent reason. Compressor motor is noisy and no suction is present. Control problem or refrigeration system problem. Perform diagnostics to detect active protection, and take action accordingly. Wrong phase order to compressor. Check compressor phase order. Water leakage from indoor unit. Freezing of outdoor unit in HEAT Mode and outdoor unit base is blocked with ice.
EXPLODED VIEWS & SPARE PARTS LISTS 13. EXPLODED VIEWS & SPARE PARTS LISTS 13.1 Indoor Unit: SX 9, 12, 15, 18 SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.2 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.3 No. 25 22 1 14 6 19 21 17 4 9 16 9 27 28 23 24 2 20 15 5 None None 29 3 29 8 12 21 30 18 13 7 10 11 Indoor Unit: SX 12 Item Code 234213 263034 307979 307981 323425 370281 372339 373244 373247 4520929 4520429 4520158 438413 438082 436665 391508 382334 375209-16 484001 455000600 452837700R 452837700 452837700 452791200 4524613 4520933 373245 372338 311036 371257 221555 293321 4521029 372341 SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.4 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.5 Indoor Unit: SX 18, 24, 30 SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.6 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.7 No. 14 25 22 8 1 15 30 7 19 18 21 21 12 17 13 4 20 2 24 23 28 27 9 11 9 6 10 29 29 None None 3 5 16 Indoor Unit: SX 24 Item Code 221554 234213 263034 293322 307980 307982 311036 323422 370280 371257 372336 372337 372340 373244 373245 373246 375209-16 382333 391508 436665 438082 438413 4520159 4520429 4520931 4520934 4521029 4524613 452837700 452837700 452837700R 452907300 455000602 484002 SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.8 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.9 Outdoor Unit: ONG 9, 12 ST SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.12 13-12 Outdoor Unit: ONG 9, 12 RC CONTENT SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.15 Outdoor Unit: ONG 14 ST SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.17 Outdoor Unit: ONG 14 RC SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.18 Outdoor Unit: ONG 14 RC No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.19 Outdoor Unit: GC 18 ST SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.20 Indoor Unit: GC 18 ST NO. Part No. Description Quantity 1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 452989200 Base welding plate assy.
EXPLODED VIEWS & SPARE PARTS LISTS 13.21 Outdoor Unit: GC 18 RC SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.22 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 13-22 Outdoor Unit: GC 18 RC Part No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.23 Outdoor Unit: OU7-24 RC 1PH SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.24 Outdoor Unit: OU7-24 RC 1PH No. SP No. Part No. 1 13 190443 2 22 402283 3 17 402495 4 7 433285 5 15 433288 6 16 433291 7 14 433293 8 6 433294 9 44 433816 10 9 434062 11 19 434716 12 3 436357 13 11 436358 14 1 437045 15 5 437091 16 24 437229 17 21 437274 18 4 439329 19 12 439342 20 18 442007 21 20 442016 22 33 442466 23 8 4529604 13-24 Description HEATER CRANKCASE MITSUBISHI CO SUCTION ACCUMULATOR 3"x5/8" 3.
EXPLODED VIEWS & SPARE PARTS LISTS 13.25 Outdoor Unit: OU7-24 ST 1PH *Optional SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.26 Outdoor Unit: OU7-24 ST 1PH No. SP No. Part No. 1 13 190443 2 22 402283 3 17 402495 4 14 433293 5 6 433705 6 44 433816 7 16 433817 8 15 433845 9 7 433846 10 45 433847 11 9 434062 12 19 434716 13 3 436357 14 11 436358 15 1 437045 16 5 437091 17 24 437229 18 21 437274 19 4 439329 20 12 439342 21 18 442007 22 20 442016 23 8 4529604 13-26 Description HEATER CRANKCASE MITSUBISHI CO SUCTION ACCUMULATOR 3"x5/8" 3.
EXPLODED VIEWS & SPARE PARTS LISTS 13.27 Outdoor Unit: OU7-24Z RC 1PH RSWLRQDO 20 18 44 17 24 19a SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.28 Outdoor Unit: OU7-24Z RC 1PH SP No. Part No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.29 Outdoor Unit: OU7-24 RC 3PH SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.30 Outdoor Unit: OU7-24 RC 3PH No. SP No. Part No. 1 13 190443 2 22 402283 3 17 402494 4 7 433285 5 15 433288 6 16 433291 7 6 433294 8 14 433753 9 44 433816 10 9 434062 11 19 434716 12 3 436357 13 11 436358 14 1 437045 15 5 437091 16 24 437229 17 21 437278 18 4 439329 19 12 439342 20 25 439795 21 18 442007 22 33 442466 23 8 4529604 13-30 Description HEATER CRANKCASE MITSUBISHI CO SUCTION ACCUMULATOR 3"x5/8" 3.
EXPLODED VIEWS & SPARE PARTS LISTS 13.31 Outdoor Unit: OU7-24 ST 3PH *Optional SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.32 No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 13-32 Outdoor Unit: OU7-24 ST 3PH SP No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 21 22 24 25 44 45 Part No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.33 Outdoor Unit: OU8-30 RC 1PH SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.36 13-36 Outdoor Unit: OU8-30 ST 1PH CONTENT SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.39 Outdoor Unit: OOU8-30 RC 3PH SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.41 Outdoor Unit: OU8-30 ST 3PH SM SX Ser1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
OPTIONAL ACCESSORIES 14. OPTIONAL ACCESSORIES 14.1 RCW Wall Mounted Remote Control 14.1.1 The RCW wall mounted remote control can be fitted to a large range and models, It can be used as IR (wirless mode) or wired controler.the RCW can control up to15 indoor units using the same settings (on its wired aplication), The max wiring length between the controller to the last indoor unit is 300m. for application on WNG LED indoor units an additional interface PCB is needed.
OPTIONAL ACCESSORIES 14.2 RCW2 Wall Mounted Remote Cntrol 14.2.1 The RCW2 wall mounted remote controler is a wired controler that can provide affective controling management up to 15 different settings and temp’ zones. The RCW2 can be connected up to a max’ of 32 units,allowing a max wiring length of 1000m. for application on WNG LED indoor units an additional interface PCB is needed. Ordering code no’: RCW2 – SP000000081 WNG add’ PCB - SP000000290 1 2 3 1 4 2 3 4 14-2 CONTENT Display screen.
OPTIONAL ACCESSORIES 14.3 RCW/RCW2 Wiring Connections as Shown on Kit SM SX Ser1-A.
OPTIONAL ACCESSORIES All Season Kit Installation Instruction(for ST units only) Switch off power supply to the unit A Fig.1 ● Remove: – Cover A; – Power panel handle B; – Side cover C (if it exist). B C Fig.1 Fig.2 ● Mount the Fan speed controller on the partition of the compressor compartment in the holes provided, using four supplied screws . Note: ● In outdoor models OU8, the Fan Speed Controller should be mounted on the partition toward the outdoor fan motor side. OU7 OU10 OU8 Fig.
OPTIONAL ACCESSORIES Fig.4 Flare nut D E ● Connect capillary E to T-valve. Use Copper sealing gasket between the flare nut and the connection to T-valve. Note: ● Installing the Copper sealing gasket is mandatory in order to avoid refrigerant leak. T-valve Cooper sealing gasket Fig.4 Fig.5 TB2 Electrical connections for 1PH units: ● Disconnect the wire from point “6” on main terminal outdoor PCB Typhoon and isolate it with isolation tape.
OPTIONAL ACCESSORIES Fig.7 ● Verify the wiring to electrical diagram. 1PH Unit 3PH Unit Capillary loop Fig.8 ● Arrange the wires and capillary tube together with plastic ties, don’t fold or break the capillary tube,keep a large loop for extra length of capillary tube. ● Check for refrigerant leaks. Plastic tie Fig.8 ● Re-assemble the previously removed elements. 3 14-6 CONTENT SM SX Ser1-A.
SM SX Ser1-A.3 GB CONTENT Disconnect the wires between the PXD and the top: • Display cable (clear insulated cable). • Vertical louver motor wires (red and blue with connectors). • Horizontal louver motor wires (black). Take care to separate the wire to help re-instalation.
14-8 CONTENT Blue wire to N'1 Violet wire to HE2 Black wire to HE1 wiring - Connect the wires with 6.
- Connect the wires with 6.35 connectors directly to the control board as shown MODELS SXSP 9 - 12 - 15 - 18 - 24 - 30 SM SX Ser1-A.
14-10 bloc mousse wiring - On the unit top : • Using flat pliers break the plastic A (for the heater cable) • Place the foam insulation in the groove (to prevent air by-pass) KIT INSTALLATION : (Fig.3) Fig.3 A OPTIONAL ACCESSORIES CONTENT SM SX Ser1-A.
SM SX Ser1-A.3 GB 24 3213 Heatpump with heaters PXD- SH PXD- RC CONTENT - A label "DO NOT COVER" is supplied with the kit. Place it on the rear of the discharge frame as shown below. THE DISCHARGE PORT OF THE APPLIANCE MUST NEVER BE COVERED OR OBSTRUCTED BY A CURTAIN, CLOTH, ETC...
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL SM SX Ser1-A.