Service manual

5-11
PERFORMANCE DATA & PRESSURE CURVES
SM KN DCI 2-E.2 GB
5.3 KN80 DCI / DCI 80
5.3.1 Cooling Capacity (kW)
ID COIL ENTERING AIR DB/WB TEMPERATURE [C
0
]
OD COIL
ENTERING AIR DB
TEMPERATURE [C
0
]
DATA
22/15 24/17 27/19 29/21 32/23
-10 - 20
(protection range)
TC 80 - 110 % of nominal
SC 80 - 105 % of nominal
PI 25 - 50 % of nominal
25
TC 7.88 8.34 8.81 9.27 9.74
SC 6.41 6.51 6.60 6.70 6.79
PI 2.00 2.05 2.09 2.14 2.18
30
TC 7.48 7.94 8.40 8.87 9.33
SC 6.16 6.25 6.35 6.45 6.54
PI 2.28 2.33
2.37
2.42 2.46
35
TC 7.07 7.54
8.00
8.46 8.93
SC 5.91 6.00 6.10 6.20 6.29
PI 2.56 2.60
2.65
2.70 2.74
40
TC 6.67 7.13
7.60
8.06 8.52
SC 5.66 5.75 5.85 5.95 6.04
PI 2.84 2.88 2.93 2.97 3.02
46
TC 6.18 6.65 7.11 7.58 8.04
SC 5.36 5.45 5.55 5.64 5.74
PI 3.17 3.22 3.26 3.31 3.35
LEGEND
TC Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
5.3.2 Capacity Correction Factors (Cooling)
Cooling Capacity Ratio Vs. Outdoor Temperature
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
20 25 30 35 40 45
Outdoor Temperature [deg ºC]
Capacity Ration
CONTENT