PXD Series R410A Indoor Unit Outdoor Unit PXD9 ONG9 ST/RC PXD12 ONG12 ST/RC PXD15 ONG14 ST/RC PXD18 GC18 ST/RC PXD18 GC18 ST/RC 3PH PXD24 OU7-24 ST/RC PXD24 OU7-24T ST/RC PXD30 OU8-30 ST/RC PXD30 OU8-30T ST/RC REFRIGERANT R410A COOLING ONLY HEAT PUMP SEPTEMBER - 2005 CONTENT
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ August 2005 Total number of pages in this publication is 149 consisting of the following: Page No. Revision No. # Page No. Revision No.
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The PXD split floor and ceiling units range comprise the ST (cooling only) and RC (heat pump) models, as follows: • Cooling Only PXD9ST, PXD12ST, PXD15ST, PXD18ST, PXD24ST, PXD30ST • Heat Pump PXD9RC,PXD12RC,PXD15RC, PXD18RC, PXD24RC, PXD30RC 1.2 Main Features The PXD series benefits from the most advanced technological innovations, namely : 1.3 • R410A • Microprocessor control. • Infrared remote control, and on unit.
INTRODUCTION 1.5 Control The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming. The unit is designed with an on unit control board as well. For further details please refer to the Operation Manual, Appendix A. 1.6 Outdoor Unit The PXD outdoor units can be installed as floor or wall mounted by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance.
INTRODUCTION 1.10 Matching Table 1.10.1 R410A INDOOR UNITS OUTDOOR UNITS REF’ K9 ONG9 ST MODEL R410A √ K11 K15 K18 WNG9 WNG12 WNG14 WNG18 PXD9 PXD12 PXD15 PXD18 ONG12 ST R410A ONG14 ST R410A ONG9 RC R410A ONG12 RC R410A ONG14 RC R410A GC18 ST R410A √ √ √ GC18 RC R410A √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √ √* √ √* - the outdoor unit of this combination cannot be matched to other indoor units.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.1 R410A Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Capacity Units Btu/hr kW kW W/W (1) Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Units Btu/hr kW kW W/W Capacity (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Units Btu/hr kW kW W/W Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET Model Indoor Unit PXD-18 Model Outdoor Unit GC-18 Installation Method of Pipe Flared Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Units Cooling Only Cooling Heating Btu/hr 18770 18770 19620 kW 5.5 5.5 5.75 kW 1.82 1.82 1.77 W/W 3.02 3.02 3.25 B C Energy efficiency class B Power supply V/Ph/Hz Rated current A Starting current A Circuit breaker rating A 220-240V/Single/50Hz 8.
PRODUCT DATA SHEET Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Units Btu/hr kW kW W/W Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics INDOOR OUTDOOR Sound pressure level(4) Moisture removal Condensate drain tube I.D Dimensions Weight Package dimensions Packaged weight Units per pallet Stacking height H/M/L H/M/L Min-Max RPM m3/hr Pa H/M/L H/M/L dB(A) dB(A) l/hr mm mm kg mm kg units units 64/62/59 53/51/48 2.
PRODUCT DATA SHEET Model Indoor Unit PXD-24 Model Outdoor Unit OU7-24T Installation Method of Pipe Flared Characteristics Capacity (1) Power input (1) EER (Cooling) or COP(Heating) (1) Units Cooling Only Cooling Heating Btu/hr 23300 23300 24000 kW 6.83 6.83 7.03 kW 2.27 2.27 2.13 W/W 3.01 3.01 3.
PRODUCT DATA SHEET Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Capacity Units Btu/hr kW kW W/W (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET Model Indoor Unit Model Outdoor Unit Installation Method of Pipe Characteristics Capacity Units Btu/hr kW kW W/W (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP(Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds Air flow (2) External static pressure Sound power level (3) Sound pressure level(4) Moisture removal Condensate drain tube I.
RATING CONDITIONS 3. RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.
OUTLINE DIMENSIONS 4. OUTLINE DIMENSIONS 4.1 Indoor Unit : PXD 9, 12, 15 R410A 4.
OUTLINE DIMENSIONS 4.3 4.
OUTLINE DIMENSIONS 4.5 Outdoor Unit : OU7-24 4.
PERFORMANCE DATA & PRESSURE CURVES 5. PERFORMANCE DATA 5.1 PXD9 ONG9 R410A 5.1.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15(1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 2.80 1.85 0.59 2.71 1.81 0.64 2.57 1.77 0.69 2.40 1.71 0.74 2.22 1.63 0.80 2.02 1.53 0.87 1.75 1.41 0.95 2.90 1.93 0.59 2.86 1.91 0.64 2.77 1.88 0.70 2.
PERFORMANCE DATA & PRESSURE CURVES 5.1.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL ( °C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 1.46 1.58 1.67 2.04 2.87 3.12 3.38 3.56 0.69 0.71 0.71 0.75 0.80 0.85 0.89 0.91 1.41 1.52 1.62 1.95 2.79 3.04 3.29 3.47 0.73 0.74 0.76 0.80 0.86 0.91 0.95 0.99 1.35 1.46 1.56 1.87 2.69 2.96 3.21 3.38 0.77 0.78 0.80 0.84 0.91 0.97 1.01 1.
PERFORMANCE DATA & PRESSURE CURVES 5.3 Pressure Curves. 5.3.1 Cooling. Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure VS.
PERFORMANCE DATA & PRESSURE CURVES 5.3.2 Heating. Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.4 PXD12 ONG12 R410A 5.4.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15(1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 3.71 2.40 0.82 3.59 2.35 0.89 3.40 2.29 0.96 3.18 2.22 1.04 2.94 2.11 1.12 2.67 1.99 1.21 2.32 1.83 1.32 3.84 2.50 0.82 3.78 2.48 0.90 3.67 2.43 0.97 3.46 2.36 1.06 3.
PERFORMANCE DATA & PRESSURE CURVES 5.4.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 1.94 2.09 2.22 2.70 3.81 4.14 4.48 4.72 0.92 0.94 0.95 1.00 1.08 1.14 1.18 1.22 1.87 2.02 2.15 2.59 3.70 4.03 4.37 4.61 0.98 0.99 1.01 1.06 1.15 1.21 1.28 1.32 1.79 1.94 2.07 2.48 3.57 3.92 4.26 4.48 1.03 1.05 1.07 1.13 1.22 1.30 1.36 1.
PERFORMANCE DATA & PRESSURE CURVES 5.6 Pressure Curves. 5.6.1 Cooling. Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure VS.
PERFORMANCE DATA & PRESSURE CURVES 5.6.2 Heating. Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 5.0 20 DB (ºC) 25 DB (ºC) 4.0 3.0 -10 -5 0 5 o 10 15 20 Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.7 PXD15 ONG14 R410A 5.7.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15(1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 4.32 2.74 0.96 4.18 2.69 1.04 3.96 2.62 1.12 3.70 2.54 1.21 3.43 2.41 1.31 3.11 2.27 1.41 2.70 2.09 1.54 4.48 2.86 0.96 4.41 2.83 1.04 4.27 2.78 1.13 4.03 2.70 1.23 3.
PERFORMANCE DATA & PRESSURE CURVES 5.7.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 2.36 2.54 2.70 3.29 4.64 5.04 5.45 5.74 1.10 1.13 1.15 1.20 1.29 1.36 1.42 1.46 2.27 2.45 2.61 3.15 4.50 4.91 5.31 5.60 1.18 1.19 1.21 1.28 1.38 1.46 1.53 1.59 2.18 2.36 2.52 3.02 4.34 4.77 5.18 5.45 1.24 1.26 1.28 1.35 1.47 1.56 1.63 1.
PERFORMANCE DATA & PRESSURE CURVES 5.9 Pressure Curves. 5.9.1 Cooling. Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure VS.
PERFORMANCE DATA & PRESSURE CURVES 5.9.2 Heating. Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.10 PXD18 GC18 R410A 5.10.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 (1) 20(1) 25 30 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 35 TC SC PI TC SC PI 40 46 15/21 17/24 19/27 21/29 23/32 5.80 3.94 1.29 5.61 3.86 1.40 5.31 3.76 1.51 4.96 3.64 1.63 4.59 3.46 1.76 4.18 3.26 1.90 3.62 3.01 2.08 6.00 4.11 1.29 5.91 4.07 1.41 5.73 3.99 1.52 5.40 3.87 1.
PERFORMANCE DATA & PRESSURE CURVES 5.10.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 3.02 3.25 3.45 4.20 5.92 6.44 6.96 7.33 1.42 1.45 1.47 1.54 1.65 1.75 1.82 1.88 2.90 3.13 3.34 4.03 5.75 6.27 6.79 7.16 1.51 1.53 1.56 1.64 1.77 1.87 1.96 2.04 2.79 3.02 3.22 3.85 5.55 6.10 6.61 6.96 1.58 1.61 1.65 1.73 1.88 2.00 2.09 2.
PERFORMANCE DATA & PRESSURE CURVES 5.12 Pressure Curves. 5.12.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.12.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.13 PXD18 GC18 3PH R410A 5.13.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 (1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 5.80 4.09 1.25 5.61 4.01 1.36 5.31 3.91 1.47 4.96 3.79 1.59 4.59 3.60 1.71 4.18 3.39 1.85 3.62 3.13 2.02 6.00 4.27 1.26 5.91 4.23 1.37 5.73 4.15 1.48 5.40 4.02 1.
PERFORMANCE DATA & PRESSURE CURVES 5.13.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 3.02 3.25 3.45 4.20 5.92 6.44 6.96 7.33 1.35 1.39 1.40 1.47 1.58 1.67 1.74 1.79 2.90 3.13 3.34 4.03 5.75 6.27 6.79 7.16 1.44 1.46 1.49 1.56 1.69 1.78 1.88 1.94 2.79 3.02 3.22 3.85 5.55 6.10 6.61 6.96 1.51 1.54 1.57 1.66 1.79 1.91 1.99 2.
PERFORMANCE DATA & PRESSURE CURVES 5.15 Pressure Curves. 5.15.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB ºC) ºC) ºC) ºC) ºC) 20 25 11.0 10.0 9.0 8.0 7.0 6.0 5.0 15 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.15.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 5.0 20 DB (ºC) 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.16 PXD24 OU7-24 & 24T R410A 5.16.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 (1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 7.20 5.02 1.61 6.97 4.92 1.75 6.59 4.80 1.89 6.16 4.65 2.04 5.71 4.42 2.20 5.19 4.16 2.37 4.50 3.84 2.59 7.46 5.24 1.61 7.34 5.19 1.75 7.12 5.09 1.90 6.71 4.
PERFORMANCE DATA & PRESSURE CURVES 5.16.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 20 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 25 TH PI TH PI TH PI 4.06 4.37 4.64 5.65 7.24 7.87 8.51 8.96 1.70 1.75 1.77 1.85 1.99 2.10 2.19 2.26 3.91 4.21 4.49 5.41 7.03 7.66 8.30 8.75 1.81 1.84 1.87 1.97 2.13 2.25 2.36 2.45 3.75 4.06 4.33 5.18 6.78 7.45 8.08 8.51 6.29 6.41 6.54 6.89 7.47 7.93 8.30 8.
PERFORMANCE DATA & PRESSURE CURVES 5.18 Pressure Curves. 5.18.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.18.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 o 10 15 20 Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.19 PXD30 OU8- 30 R410A 5.19.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 (1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 8.98 5.68 2.12 8.69 5.57 2.30 8.22 5.42 2.49 7.69 5.25 2.68 7.12 5.00 2.89 6.47 4.71 3.12 5.62 4.34 3.41 9.30 5.92 2.12 9.16 5.87 2.31 8.88 5.76 2.50 8.37 5.58 2.
PERFORMANCE DATA & PRESSURE CURVES 5.19.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 5.00 5.38 5.71 6.95 8.91 9.69 10.47 11.03 2.23 2.29 2.32 2.43 2.61 2.75 2.87 2.96 4.81 5.19 5.52 6.66 8.65 9.43 10.21 10.77 2.38 2.41 2.46 2.58 2.79 2.94 3.10 3.21 4.61 5.00 5.33 6.38 8.35 9.17 9.95 10.47 2.50 2.54 2.59 2.73 2.96 3.15 3.29 3.
PERFORMANCE DATA & PRESSURE CURVES 5.21 Pressure Curves. 5.21.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.21.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 15 DB (ºC) 6.0 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.
PERFORMANCE DATA & PRESSURE CURVES 5.22 PXD30 OU8- 30T R410A 5.22.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OU COIL (°C) 15 (1) 20(1) 25 30 35 40 46 ENTERING AIR WB/DB ID COIL ( °C) DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 15/21 17/24 19/27 21/29 23/32 8.75 5.53 1.96 8.46 5.42 2.13 8.01 5.28 2.30 7.49 5.12 2.49 6.93 4.87 2.68 6.31 4.59 2.89 5.47 4.23 3.16 9.06 5.77 1.97 8.92 5.72 2.14 8.65 5.61 2.32 8.15 5.44 2.
PERFORMANCE DATA & PRESSURE CURVES 5.22.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) 15 ENTERING AIR WB OU COIL (°C) -10 -7 -2 2 6 10 15 20 20 25 TH PI TH PI TH PI 4.79 5.16 5.48 6.66 8.55 9.30 10.04 10.58 2.10 2.16 2.18 2.29 2.46 2.60 2.71 2.79 4.61 4.98 5.30 6.39 8.30 9.05 9.79 10.33 2.24 2.27 2.31 2.43 2.63 2.77 2.92 3.02 4.43 4.79 5.11 6.12 8.01 8.80 9.55 10.04 2.35 2.40 2.45 2.58 2.79 2.97 3.10 3.
PERFORMANCE DATA & PRESSURE CURVES 5.24 Pressure Curves. 5.24.1 Cooling. Suction Pressure Vs.Outdoor Temp Suction Pressure (Bar[g]) 12.0 15/21(WB/DB 17/24(WB/DB 19/27(WB/DB 21/29(WB/DB 23/32(WB/DB 11.0 10.0 ºC) ºC) ºC) ºC) ºC) 9.0 8.0 7.0 6.0 5.0 15 20 25 30 35 40 46 40 46 o Outdoor Temp.(DB C ) Discharge Pressure (Bar[g]) Discharge Pressure Vs.
PERFORMANCE DATA & PRESSURE CURVES 5.24.2 Heating. Suction Pressure Vs.Outdoor Temp Suction Pressure(Bar[g]) 12.0 11.0 10.0 9.0 8.0 7.0 6.0 15 DB (ºC) 20 DB (ºC) 5.0 25 DB (ºC) 4.0 3.0 -10 -5 0 5 10 15 20 o Outdoor Temp.( WB C ) Discharge Pressure(Bar[g]) Discharge Pressure Vs.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) -10 -5 0 5 10 15 20 o Outdoor Temp.
ELECTRICAL DATA 6. ELECTRICAL DATA 6.1 Single Phase Units MODEL Power Supply Max Current, A Circuit Breaker Power Supply Wiring No. X Cross Section mm2 PXD 9 PXD 12 PXD 15 PXD 18 To indoor 1PH-230V-50Hz 7.1 10 To indoor 1PH-230V-50Hz 7.6 10 To indoor 1PH-230V-50Hz 10.4 15 To Indoor To outdoor 1PH-230V-50Hz 12 15 3x1.5 mm2 3x1.5 mm2 3x1.5 mm2 2 2 2 3x2.5 mm2 2 Interconnecting Cable RC Model 5x1.5 mm2 +2x0.5 mm2 5x1.5 mm +2x0.5 mm 5x1.5 mm +2x0.5 mm 5x2.5 mm2 +2x0.5 mm2 6x1.5 mm2 +2x0.
WIRING DIAGRAMS 7. WIRING DIAGRAMS 7.1 Indoor Unit: PXD 9, 12, 15 7.
WIRING DIAGRAMS 7.3 Outdoor Unit: ONG 9, 12, 15 C R 7.4 S Outdoor Unit: GC 18 LEGEND: OPTIONAL: WIRING DIAGRAM ---Heat Pump Model BK-Black BU-Blue BN-Brown OG-Orange RD-Red WH-White GN/YE-Yellow/Green 1.CONNECTED ONLY FOR ALL SEASON UNIT 2.SP--Pressure Control Electronic ( for all season) 3.PTCH--PTC heater for draining water 4.HPS--High Pressure Switch (Only for GC-30RC) CAP.--Capacitor COMP.--Compressor DEICER TEMP.
WIRING DIAGRAMS 7.5 Outdoor Unit: GC 18 3PH WIRING DIAGRAM OF OUTDOOR UNIT 9 XT3 8 DEICER TEMP. SENSOR RT3 ANTI-PHASE PROTECTOR U RD V 6 BN WH BU BN A W BN N BU BU RD RD BK L1 P OG TERMINAL BK TERMINAL OG L1 L2 B B BK L2 L3 BU BN L3 3PH BK BK BN BN BU BN WH RD BK BN BK WH L N BU WH RD BU BU BU 4-W VALVE BK WH RD PTCH N BU 380~400V 50Hz N BN 4 BK 5 INDICATOR LIGHT BK 3 A1 BU 5 21 CAP OG TERMINAL A2 BN-GC18RC BK-GC24RC RD 6 22 VT COMP.
WIRING DIAGRAMS 7.7 Outdoor Unit: OU8-30 1PH (with soft starter) 7.
ELECTRICAL CONNECTIONS 8. ELECTRICAL CONNECTIONS 8.1 PXD 9, 12, 15, 18, 24 8.
ELECTRICAL CONNECTIONS 8.
REFRIGERATION DIAGRAMS 9. REFRIGERATION DIAGRAMS 9.1 Heat Pump Models 9.1.
REGRIGERATION DIAGRAMS 9.1.
REFRIGERATION DIAGRAMS 9.1.
REGRIGERATION DIAGRAMS 9.2 Cooling Only Models 9.2.1 PXD 9, 11, 15, 18 OUTDOOR UNIT INDOOR UNIT Service port Sensor Compressor Sensor Valves Capillary tube Outdoor coil 9.2.
TUBING CONNECTIONS 10. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 11-13 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8.
CONTROL SYSTEM 11. CONTROL SYSTEM 11.1 Electronic Control 11.1.1 Introduction The electronic control information is designed for service applications, and is common to the following groups of air-conditioners: ST/RC group SH group RH group 11.1.2 -Cooling only / cooling and heating by heat pump. -Cooling and heating by heat pump and supplementary heater. -Cooling, heating by heaters only.
CONTROL SYSTEM 11.1.3 Remote Control DIP Switch Settings SETTING SWITCH STATUS DEFINITION SW. NO. 1 OFF ON OFF ON -- SW. NO. 2 OFF OFF ON ON -- SW. NO. 3 ----OFF SW. NO. 4 ------ -- -- ON -- -- -- -- OFF TIMER & CLOCK 12H AM, PM -- -- -- ON TIMER & CLOCK 24H RC3 RC4 RC-ALL MODES OF OPERATION STD-COOL, FAN, DRY, ACTIVE HEAT-COOL, FAN, DRY, ACTIVE AUTO FAN (AF) TEMP. DISPLAY IN C DEGREES TEMP.
CONTROL SYSTEM 11.1.
CONTROL SYSTEM 11.1.5 Display Board :LEXAN 11.1.6 Display Board : Assembly 11.1.
CONTROL SYSTEM 11.2 Control Function 11.2.1 Abbreviations AC - Alternate Current A/C ANY CLOCK COMP CPU CTV HE HPC H/W ICP ICT IF, IFAN IR LEVEL1 LEVEL2/3 LEVEL4 Max Min min NA OCP OCT OF, OFAN OPER Para.
CONTROL SYSTEM 11.3 General Functions 11.3.1 COMP Operation a. For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting, excluding DEICING Mode (see para. 14.12.2). b. The Min operation time of COMP under different operating conditions is: Operation Mode Heat, Cool, HP protection or Auto Modes Fan, Dry, Overflow, Protection Modes, or Mode Change 11.3.2 Min Operation Time of COMP 3 min. Ignored IFAN operation a.
CONTROL SYSTEM 11.3.5 11.3.6 Protections a. High pressure protection is applicable to all operating modes. b. Deicing control is valid in Heat and Auto Heat Modes only. c. Defrosting control is valid in Dry, Cool, and Auto Cool Modes. Thermistors Operation a. Return air Temp. is detected by RAT in normal Mode, or by RCT (R/C sensor) in I-FEEL Mode. b. Indoor Coil Temp. is detected by ICT. c. Outdoor Coil Temp. is detected by OCT. d. Definition of thermistor faults: e.
CONTROL SYSTEM 11.3.7 RV Fault This test is applied only in compressor units where 4.7k resistor is not connected to the OCT. The test is performed every time the unit is switched from OFF/STBY to OPER in Heat mode or changes operation mode from COOL/DRY to HEAT or (this applies also in AUTO COOL/HEAT mode).
CONTROL SYSTEM 11.4 Cooling Mode 11.4.1 Cooling Mode – General a. Mode Definition Mode: COOL, AUTO (at Cooling) Temp: Selected desired temperature. Fan: HIGH, MED, LOW, AUTO. Timer: Any I-FEEL: ON or OFF b. Room Temperature, RT, is detected by: RAT in normal operation, or RCT (R/C sensor) in I-FEEL mode. 11.4.2 c. Indoor Coil Temp is detected by ICT. d. Outdoor Coil Temp is detected by OCT. Control Functions a. COMP Operation COMP ON OFF 0 b.
CONTROL SYSTEM 11.4.3 Sequence Diagrams a. Maintaining room temp at desired level by comparing RT and SPT with user defined IFAN speed.
CONTROL SYSTEM b. Maintaining room temp at desired level by comparing RT and SPT with AUTO-IFAN.
CONTROL SYSTEM 11.5 Heating Mode 11.5.1 Heating Mode - General a. Compensation Procedure When I-FEEL is OFF during HEAT mode: RT= RAT – CTV. When I-FEEL is ON during HEAT mode: RT= RCT. Type of Indoor Wall Mounted Mobiles / Floor Ceiling Square /Window Ducted Cassettes CTV +3 oC +0 oC +2 oC +4 oC +4 oC No compensation will be activated in Forced operation modes b.
CONTROL SYSTEM c. IFAN operation rules for RH group 1) d. In RH group, IFAN starts when HE starts. When HE switches to OFF, IFAN switches to LOW for 30 sec and then stops. Heaters operation rules for RC and SH groups: 1) For both RC and SH groups, Heaters versus T is as follows: ON HE1 OFF ON HE2 OFF 1 2) 2 3 4 T=SP-RT [oc] Operation rules for Heaters in RC group: a) Heaters can be enabled only if IFAN is ON.
CONTROL SYSTEM e. Heaters operation rules for RH groups: 1) In RH group, HE operation is according to the difference between RAT and SPT. ON H E2 O FF ON H E1 O FF -1 f. 0 2 T=SP-R T [ o c] OFAN Operation for RC and SH groups 1) As a general rule for RC and SH groups, excluding protection modes, OFAN starts with the compressor. 2) When OFAN is ON it will operate according to the following conditions: a) OFAN operates together with the compressor.
CONTROL SYSTEM 11.6 Heating, RC or SH Group Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I-FEEL: ON or OFF 11.6.1 Sequence Diagram Maintains room temp. at desired level by comparing RAT or RCT to SPT.
CONTROL SYSTEM 11.7 Heating, RC or SH Group with Autofan Mode: HEAT, AUTO (at heating) Temp: Selected desired temperature Fan: AUTO Timer: Any I-FEEL: ON or OFF 11.7.1 Sequence Diagram Maintains room temp at desired level by controlling COMP, IFAN and OFAN.
CONTROL SYSTEM 11.8 Heating, RH Group Mode: HEAT, AUTO (at Heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I-FEEL: ON or OFF 11.8.1 Sequence Diagram Maintains room temp at desired level by controlling Heating Elements: HE1 or HE2.
CONTROL SYSTEM 11.9 Heating, RH Group, with AUTOFAN Mode: HEAT, AUTO (at Heating) Temp: Selected desired temperature Fan: AUTO Timer: Any I-FEEL: ON or OFF 11.9.1 Sequence Diagram Maintains room temp. at desired level by controlling the 2-Stage Electric Heaters.
CONTROL SYSTEM 11.10 Automatic Cooling or Heating 11.10.1 Automatic Cooling or Heating - General The AUTO Mode is for models with compressor and the WVL-RH only. The WVL-ST, RC and SH units do not work in AUTO Mode. a. Mode Definition Mode: AUTO Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: ON or OFF b. Switching-temperature between Cooling and Heating is SPT 3OC. c.
CONTROL SYSTEM 11.10.2 Sequence Diagrams a. Auto Cooling or Heating, RC or SH Groups Maintains room temp. at desired level by selecting between cooling and heating modes.
CONTROL SYSTEM b. Auto Cooling or Heating RH Group Maintains room temp. at desired level by selecting between Cooling or Heating Modes. (RT - SPT) [oc] +3 +2 +1 0 -1 -2 -3 Auto Heat Mode Auto Cool Mode Auto Heat Mode ON COMP & OFAN OFF > 3 min > 3 min (2) (2) ON HE1 OFF ON HE2 OFF H/M/L IFAN L OFF 30 sec (1) RV OFF 11.11 Dry Mode 11.11.
CONTROL SYSTEM (RT - SPT) [ oc] +2 +1 0 10 20 40 30 50 Time [min] -1 -2 DRY-ON DRY DRY-OFF LOW IFAN OFF 5 minutes COMP ON time ON COMP OFAN OFF Max 15 minutes ON HE1 & HE2 3.5 min Note1 Max 15 minutes 6 min Note 2 OFF ON RV OFF NOTES 1. When DRY is ON, the COMP is forced OFF for 3.5 min (longer than the 3 min Min COMP- OFF time) after every 15 min of continuous COMP operation. 2.
CONTROL SYSTEM 11.11.2 DRY, SH or RH group Mode: DRY Temp: Selected desired temperature Fan: LOW (automatically selected by software) Timer: Any I-FEEL: Any Control function Reduces room humidity with minimum temp. fluctuations by operating in Cool Mode with LOW speed IFAN and HE.
CONTROL SYSTEM 11.12 Protection 11.12.1 Cooling Mode Protections a. Indoor Coil Defrost Mode: COOLING, DRY, AUTO Temp: Selected desired temp. Fan: Any Timer: Any I-FEEL: ON or OFF Control Function Protects the indoor coil from ice formation at low ambient temperatures. ICT [oc] +14 +5 +2 +1 0 -1 t1 t2 t3 t1 ON OFAN OFF ON COMP OFF ON IFAN OFF t1 = 5 min minimum for each COMP starting. t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum.
CONTROL SYSTEM b. High Pressure Protection Mode: (AUTO) COOLING or DRY Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: ON or OFF Control Function To protect the COMP from the high pressure build-up in the outdoor coil during normal cooling operation, by switching OFF the IFAN and COMP.
CONTROL SYSTEM 11.12.2 Heating Mode Protections a. Outdoor Coil Deicing (excluding RH Group) Mode: HEATING, AUTO (at heating) Temp: Selected desired temperature Fan: Any Timer: Any I-FEEL: Any Control function To protect the outdoor coil from ice formation by controlling COMP & RV operation.
CONTROL SYSTEM 2) Deicing procedure OCT [oc] 12 DOC 0 DST (DDT) 3 min 3 min 36s max 12 min. 36s ON COMP OFF DI (note 1) DI (note 2) ON OFAN OFF 30s 30s ON RV OFF DT RC or WAX units all SH units except WAX ANY IFAN L IFAN is forced to Low Speed ON HE ANY HEs are forced ON ANY IFAN OFF Note 3 ANY HE OFF HEs are forced OFF ON OPER LED BLINK NOTES 1. In the following Deicing cycles, the time interval between two Deicing cycles activation is between 30 to 80 min. 2.
CONTROL SYSTEM b. High Pressure Protection (excluding RH Group) Mode: (AUTO) HEATING Fan: Any Timer: Any I-FEEL: ON or OFF Control Function Protects the compressor from high pressure by switching OFF the OFAN and COMP.
CONTROL SYSTEM 11.12.3 Condensation Pump (ECC/K model) Mode: Cool, Dry, Auto Temp: Selected desired temperature Fan: Any Timer: Any I FEEL: Any Control function: Prevent Condensed water from Overflowing. Overflow when unit is ON Overflow Water Level Overflow when unit is OFF Normal ON OPER LED OFF BLINK ON COMP (WVL) COMP/WVL is forced OFF OFF ON PUMP OFF 8 min 8 min 1 min Notes: 1.
CONTROL SYSTEM 11.13 Forced Operation (Excluding PRX & PXD Models) a. Forced operation allows units to start, stop and operate in cooling or heating in preset temp. according to the following table: Forced Operation Mode Cooling Heating Pre-set Temp for : MBX, P2000, PX Models 20 ºC 25 ºC Pre-set Temp for : FCD, RWK ,ELD, ECC, WAX, WNX, WMN Models 22 ºC 28 ºC NOTES 1. While under the forced operation, the temperature compensation schedule is disabled. 2.
CONTROL SYSTEM 11.14 SPT Adjustment in Sleep Mode In COOL, AUTO COOL or DRY modes, the SPT adjustment is positive (from 0 to +3oC). In HEAT or AUTO HEAT modes, the SPT adjustment is negative (from 0 to -3oC). In other modes, there is no SPT adjustment. The SPT adjustment is cancelled when the Sleep mode is cancelled.
CONTROL SYSTEM 11.14.1 Time Adjustment in SLEEP Mode In 10V4, the user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below. Case 1 is the Standard Sleep Mode, which is the only sleep mode in the previous version of MCU. The A/C unit simply works for 7 hours, then goes to SB. Case 2 is the new Extended Sleep Mode.
CONTROL SYSTEM 11.15 Controller Self-Test Procedure 11.15.
CONTROL SYSTEM 11.15.2 By Remote Control Settings: a. STEP 1: TURNING ON THE POWER. Turn ON the power, make sure that the unit is in operation. b. STEP 2 : ENABLE SELF-TEST MODE c. 1) Use the remote control to send the first settings to display / indoor unit HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed. 2) Cover the IR transmitter components in the remote control so that it will not transmit the signals to the indoor unit display.
CONTROL SYSTEM d. STEP 3: AUTO LED WALK TEST. 1) All the LEDS will turn OFF. 2) All the LEDS will turn ON for 1 second one by one in the following sequence: STAND-BY Ö OPERATE Ö TIMER Ö FILTER Ö COOL Ö HEAT. 3) e. In PRX all the LEDS will turn ON for 1 second one by one in the following sequence : 18 °c Ö 20 °c Ö 22 °c Ö 24 °c Ö 26 °c Ö 28 °c Ö 30 °c Ö High IFAN Ö Auto IFAN Ö Med IFAN Ö Low IFAN Ö STAND-BYÖ TIMER Ö FILTER ÖCOOLÖ HEAT.
CONTROL SYSTEM Fail condition: 0 sec - STAND-BY is turned ON 3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON When the timing reset test is completed, the next test will start automatically. i. STEP 8: MEMORY TEST (EEPROM) The test purpose is to check if the memory is functioning correctly. The test result is reported by using the STAND-BY and FILTER LEDS: LED Indicator STAND-BY LED FILTER LED Condition for LED to be ON Test passed Test failed AT THIS POINT THE SELF-TEST IS COMPLETED.
CONTROL SYSTEM 11.16 System Diagnostics Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate the DIAGNOSTICS mode, acknowledged by 3 short beeps and lighting of COOL and HEAT LEDs. In DIAGNOSTICS mode, system failures will be indicated by the blinking of HEAT & COOL LEDs. The coding method is as follows: HEAT LED blinks 5 times in 5 seconds, and then turns off for the next 5 seconds. COOL LED blinks during the same 5 seconds according to the following table: No.
TROUBLESHOOTING 12. No. TROUBLESHOOTING SYMPTOM PROBABLE CAUSE 1 Power supply indicator (Red LED) does not light up. No power supply. 2 Unit does not respond to remote control command. Remote control command did not reach the indoor unit. 3 Unit responds to remote control command but operate indicator (Green LED) does not light up. Indoor fan does not start (louvers are opened and Green LED lights up). Problem with display PCB. 4 5 Change to COOL MODE and check.
TROUBLESHOOTING No. SYMPTOM 11 One of the protections is activated and compressor is stopped with no apparent reason. Compressor motor is noisy and no suction is present. Control problem or refrigeration system problem. Perform diagnostics to detect active protection, and take action accordingly. Wrong phase order to compressor. Check compressor phase order. Water leakage from indoor unit. Freezing of outdoor unit in HEAT Mode and outdoor unit base is blocked with ice.
EXPLODED VIEWS & SPARE PARTS LISTS 13. EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.2 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.3 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.4 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.6 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.7 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.8 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.18 Outdoor Unit: ONG 14 RC No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.20 Indoor Unit: GC 18 ST NO. Part No. Description Quantity 1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 452989200 Base welding plate assy.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.22 NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 13-22 Outdoor Unit: GC 18 RC Part No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.24 Outdoor Unit: OU7-24 RC 1PH No. SP No. Part No. 1 13 190443 2 22 402283 3 17 402495 4 7 433285 5 15 433288 6 16 433291 7 14 433293 8 6 433294 9 44 433816 10 9 434062 11 19 434716 12 3 436357 13 11 436358 14 1 437045 15 5 437091 16 24 437229 17 21 437274 18 4 439329 19 12 439342 20 18 442007 21 20 442016 22 33 442466 23 8 4529604 13-24 Description HEATER CRANKCASE MITSUBISHI CO SUCTION ACCUMULATOR 3"x5/8" 3.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.26 Outdoor Unit: OU7-24 ST 1PH No. SP No. Part No. 1 13 190443 2 22 402283 3 17 402495 4 14 433293 5 6 433705 6 44 433816 7 16 433817 8 15 433845 9 7 433846 10 45 433847 11 9 434062 12 19 434716 13 3 436357 14 11 436358 15 1 437045 16 5 437091 17 24 437229 18 21 437274 19 4 439329 20 12 439342 21 18 442007 22 20 442016 23 8 4529604 13-26 Description HEATER CRANKCASE MITSUBISHI CO SUCTION ACCUMULATOR 3"x5/8" 3.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.28 Outdoor Unit: OU7-24 RC 3PH No. SP No. Part No. 1 13 190443 2 22 402283 3 17 402494 4 7 433285 5 15 433288 6 16 433291 7 6 433294 8 14 433753 9 44 433816 10 9 434062 11 19 434716 12 3 436357 13 11 436358 14 1 437045 15 5 437091 16 24 437229 17 21 437278 18 4 439329 19 12 439342 20 25 439795 21 18 442007 22 33 442466 23 8 4529604 13-28 Description HEATER CRANKCASE MITSUBISHI CO SUCTION ACCUMULATOR 3"x5/8" 3.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.30 No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 13-30 Outdoor Unit: OU7-24 ST 3PH SP No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 21 22 24 25 44 45 Part No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
EXPLODED VIEWS & SPARE PARTS LISTS 13.
OPTIONAL ACCESSORIES 14. OPTIONAL ACCESSORIES 14.1 RCW Wall Mounted Remote Control 14.1.1 The RCW wall mounted remote control can be fitted to a large range and models, It can be used as IR (wirless mode) or wired controler.the RCW can control up to15 indoor units using the same settings (on its wired aplication), The max wiring length between the controller to the last indoor unit is 300m. for application on WNG LED indoor units an additional interface PCB is needed.
OPTIONAL ACCESSORIES 14.2 RCW2 Wall Mounted Remote Cntrol 14.2.1 The RCW2 wall mounted remote controler is a wired controler that can provide affective controling management up to 15 different settings and temp’ zones. The RCW2 can be connected up to a max’ of 32 units,allowing a max wiring length of 1000m. for application on WNG LED indoor units an additional interface PCB is needed.
OPTIONAL ACCESSORIES 14.
OPTIONAL ACCESSORIES All Season Kit Installation Instruction Switch off power supply to the unit A Fig.1 ● Remove: – Cover A; – Power panel handle B; – Side cover C (if it exist). B C Fig.1 Fig.2 ● Mount the Fan speed controller on the partition of the compressor compartment in the holes provided, using four supplied screws . Note: ● In outdoor models OU8, the Fan Speed Controller should be mounted on the partition toward the outdoor fan motor side. OU7 OU10 OU8 Fig.2 Service valve cap Fig.
OPTIONAL ACCESSORIES Fig.4 Flare nut D E ● Connect capillary E to T-valve. Use Copper sealing gasket between the flare nut and the connection to T-valve. Note: ● Installing the Copper sealing gasket is mandatory in order to avoid refrigerant leak. T-valve Cooper sealing gasket Fig.4 Fig.5 TB2 Electrical connections for 1PH units: ● Disconnect the wire from point “6” on main terminal outdoor PCB Typhoon and isolate it with isolation tape.
OPTIONAL ACCESSORIES Fig.7 ● Verify the wiring to electrical diagram. 1PH Unit 3PH Unit Capillary loop Fig.8 ● Arrange the wires and capillary tube together with plastic ties, don’t fold or break the capillary tube,keep a large loop for extra length of capillary tube. ● Check for refrigerant leaks. Plastic tie Fig.8 ● Re-assemble the previously removed elements.
Service Manual - PXD Series CONTENT Revision Y05-01 Disconnect the wires between the PXD and the top: • Display cable (clear insulated cable). • Vertical louver motor wires (red and blue with connectors). • Horizontal louver motor wires (black). Take care to separate the wire to help re-instalation.
14-8 Revision Y05-01 CONTENT Blue wire to N'1 Violet wire to HE2 Black wire to HE1 wiring - Connect the wires with 6.
- Connect the wires with 6.
14-10 bloc mousse wiring - On the unit top : • Using flat pliers break the plastic A (for the heater cable) • Place the foam insulation in the groove (to prevent air by-pass) KIT INSTALLATION : (Fig.3) Fig.
24 3213 Heatpump with heaters Service Manual - PXD Series PXD- SH PXD- RC CONTENT - A label "DO NOT COVER" is supplied with the kit. Place it on the rear of the discharge frame as shown below. THE DISCHARGE PORT OF THE APPLIANCE MUST NEVER BE COVERED OR OBSTRUCTED BY A CURTAIN, CLOTH, ETC...
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL Service Manual - PXD Series Revision Y05-01 CONTENT 15-1
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
CONTENT
Øœ 17/2/00 18:42 Page 1 C M Y CM MY CY CMY K REMOTE CONTROL PROGRAMMING AND OPERATING MANUAL CONTENT ENGLISH ı
RC4 433066 ITAL/0 18/2/00 9:37 Page 1 C M Y CM MY CY CMY K INDICE TELECOMANDO 1 USO DEL TELECOMANDO 2 MODO DI FUNZIONAMENTO E CARATTERISTICHE 3 ISTRUZIONI PER L'USO 5 Accensione del condizionatore 5 Ventilazione 5 Raffreddamento 5 Raffreddamento con ventilazione automatica 5 Riscaldamento 5 Riscaldamento con ventilazione automatica 5 Raffreddamento/riscaldamento automatici 6 Deumidificazione 6 Selezione della temperatura 6 Funzionamento a sensore individuale 6 Funzione no
pg1 RC4 433066 ENG 17/2/00 18:31 Page 1 C M Y CM MY CY CMY K REMOTE CONTROL 1 START/STOP button 2 Operation mode selection button COOLING HEATING AUTO COOL / HEAT DRY FAN I FEEL temperature 3 sensing mode button 4 FAN SPEED and AUTO FAN button 5 Room temperature UP button 6 Room temperature DOWN Button 7 SLEEP button Airflow direction 8 MANUAL positioning control button 9 Airflow direction AUTOCONTROL button 10 TIMER button 11 TIMER UP button 12 TIMER DOWN button 13 LCD operation display 1
pg2 RC4 433066 ENG 17/2/00 18:32 Page 1 C M Y CM MY CY CMY K USE OF WIRELESS REMOTE CONTROL PRIOR TO OPERATION Prior to operating your air conditioner, make sure that: ● The red tab protecting the remote control battery has been removed. ● For WIRELESS REMOTE CONTROL PUTS ALL FUNCTIONS AT YOUR FINGERTIPS REMOTE CONTROL HOLDER ● ● ● Aim at the infrared signal receiver on the room air conditioner when operating. The remote control signal can be received at a distance of up to about 8 m.
pg3 RC4 433066 ENG 17/2/00 18:33 Page 1 C M Y CM MY CY CMY K MODES OF OPERATION, FUNCTIONS AND FEATURES COOL Cools, dehumidifies and filters the room air. Maintains desired room temperature. HEAT Heats and filters the room air. Maintains desired room temperature. AUTO Automatically switches from COOLING to HEATING or from HEATING to COOLING, maintaining the desired temperature according to the room conditions.
pg4 RC4 433066 ENG 17/2/00 18:34 Page 1 C %RH HUMIDITY MEASUREMENT (OPTIONAL) AUTO LOUVRE VERTICAL AIR SWING M Y CM MY CY CMY K Measures and displayes relative humidity between 30% and 90% at a temperature range of 15ºC to 45º C. The air louvre is automatically positioned for the most suitable blow-out angle, when COOL, HEAT, DRY or FAN modes are selected. When the air conditioner is turned off, the flap will close automatically for an aesthetic appearance.
pg5 RC4 433066 ENG 17/2/00 18:34 Page 1 C M Y CM MY CY CMY K OPERATION PROCEDURE TURNING ON THE AIR CONDITIONER Press START/STOP button (1) to turn the air conditioner on. The operation indicator on the air conditioner will light up, indicating that the unit is in operation. Note that the LCD operation display (13) will always show the last mode of operation and previous function used.
pg6 RC4 433066 ENG 17/2/00 18:35 Page 1 C M Y CM MY CY CMY K AUTO COOLING / HEATING OPERATION Select the AUTO mode by pressing MODE button (2). Switch to the desired FAN SPEED or to AUTO FAN by pressing button (4). Select suitable temperature setting. The air flap will automatically move to either horizontal air delivery for cooling or to vertical air delivery for heating. At start, the air conditioner will select its mode of operation according to the room temperature and the temperature setting.
p7 RC4 433066 ENG 17/2/00 18:36 Page 1 C M Y CM MY CY CMY K TIMER OPERATION There are four timers that can be selected on the remote control.Two daily timers (designated as T1,T2) ,and two optional weekend timers (designated as WKTI, WKT2) .Each timer can be selected by pressing TIMER button (10). To set each timer use time adjust up and down buttons Hour+ (11) and Hour- (12) respectively. SET button (17) to enable the timer and/or CLEAR button (18) to disable the timer.
p8 RC4 433066 ENG 17/2/00 18:36 Page 1 C M Y CM MY CY CMY K TIMER OPERATING MODES SETTING THE ON TIMER Undertake the following steps after selecting a timer - T1,T2 or WKT1, WKT2, to set a timer for the start time of operation. Press the SET. EXAMPLE: Turning the air button. conditioner ON at 10:30. 1 Set the hours and minutes. 2 The ON icon & ON time digits will blink Press the SET button 4 3 1.Set the ON time at 10:30 . 2.
p9 RC4 433066 ENG 17/2/00 18:37 Page 1 C M Y CM MY CY CMY K SETTING THE ON AND OFF TIMERS Undertake the following steps after selecting a timer - T1,T2 or WKT1, WKT2, to set a timer for the start and stop time of operation. EXAMPLE: Turning the air conditioner ON at 10:30 and OFF at 18:30. Press the SET button Set the hours and minutes. 2 1 The ON icon & ON time digits will blink. Press the SET button Set the hours and minutes. Press the SET. button. 3 4 5 1. Set the ON time at 10:30. 2.
TO CANCEL THE TIMER SETTING FOR A PARTICULAR TIMER To cancel the ON time while keeping the OFF time setting. Press TIMER button to select a timer. 1 Press SET button . 2 The selected timer icon blinks & the correspending previous timer ON, OFF settings light. Press CLEAR button 4 3 ON icon & ON time digits blink. Press SET button ON time is cleared, OFF icon & OFF time digits blink. Confirm the new setting. TO CANCEL THE ON & OFF TIME SETTINGS Press TIMER button to select a timer.
pg11 RC4 433066 ENG 17/2/00 18:39 Page 1 C M Y CM MY CY CMY K AIR DIRECTION OPERATION 1. Automatic Vertical Air Swing Press button (9) to activate the auto air swing. Press button (9) again to deactivate this function 2. Air Direction Positioning (See Option 1 on page 2) Press button (8) to position the air flap to any desired angle. 3. Horizontal air flow control (See Opion 2 on page 2) A.