DLF DC Inverter Series Indoor Units Outdoor Units DLF 25 DCI ONG3-25 DCI DLF 35 DCI ONG3-35 DCI DLF 50 DCI DCI 50 DLF 60 DCI DCI 60 DLF 72 DCI DCI 72Z REFRIGERANT R410A SM DLF 1-A.
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ November 2007 Total number of pages in this publication is 145 consisting of the following: Page No. Revision No. # Page No. Revision No.
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The new DLF DC INVERTER concealed split unit range comprises the RC (heat pump) models as follow: ● DLF 25 ● DLF 35 ● DLF 50 ● DLF 60 ● DLF 72 Remote control compatibility The DLF unit is compatible with remote controls RC3, RC4, RCW1, RCW2, and RC7. Unlike standard units (fix RPM) that are selected according to their nominal capacity to overcome the maximum required load; DC Inverter units can be selected to a smaller nominal capacity range unit.
INTRODUCTION 1.3 Indoor Unit The indoor unit can fit easily to many types of residential and commercials applications. It includes: Water-pump drainage build-in. Emergency Water-float to prevent over flow. Horizontal/ Vertical installation build in. 2 options of return air location, on back of the unit or bellow the unit. DC BL motor with maximum fan speed flexibility. High technology plastic fan and fan housing.
INTRODUCTION 1.8 Accessories RCW Wall Mounted Remote Control The RCW remote control is mounted on the wall, and controls the unit either as an infrared remote control or as a wired controller. The wired controller can control up to 10 Indoor units with the same program settings and adjustments. For further details, please refer to the Technical Service Manual. 1.9 Inbox Documentation Each unit includes its own installation and operation manuals. 1.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.2 DLF 35 DCI Model Indoor Unit Model Outdoor Unit Installation method of Pipe Characteristics Capacity (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP (Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds H/ M/ L Air flow (2) H/ M/ L External static pressure Min-Max Sound power level (3) H/ M/ L Sound pressure level (4) H/ M/ L Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET 2.3 DLF 50 DCI Model Indoor Unit Model Outdoor Unit Installation method of Pipe Characteristics Capacity (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP (Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds H/ M/ L Air flow (2) H/ M/ L External static pressure Min-Max Sound power level (3) H/ M/ L Sound pressure level (4) H/ M/ L Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET 2.4 DLF 60 DCI Model Indoor Unit Model Outdoor Unit Installation method of Pipe Characteristics Capacity (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP (Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds H/ M/ L Air flow (2) H/ M/ L External static pressure Min-Max Sound power level (3) H/ M/ L Sound pressure level (4) H/ M/ L Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET 2.5 DLF 72 DCI Model Indoor Unit Model Outdoor Unit Installation method of Pipe Characteristics Capacity (1) OUTDOOR INDOOR Power input (1) EER (Cooling) or COP (Heating) (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds H/ M/ L Air flow (2) H/ M/ L External static pressure Min-Max Sound power level (3) H/ M/ L Sound pressure level (4) H/ M/ L Moisture removal Condensate drain tube I.
RATING CONDITIONS 3. RATING CONDITIONS Standard conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.1 Operating Limits Indoor Cooling Heating Voltage SM DLF 1-A.
OUTLINE DIMENSIONS OUTLINE DIMENSIONS 4.1 Indoor Unit: DLF 25, 35, 50, 60, 72 B C A 59 4. 565 21 160 200 59 Nominal Capacity 2.5 -5.0 kW 6.0-7.2 kW SM DLF 1-A.
OUTLINE DIMENSIONS 4.2 Outdoor Unit: DCI 25, 35, 50 4.3 Outdoor Unit: DCI 60 4-2 CONTENT SM DLF 1-A.
OUTLINE DIMENSIONS 4.4 Outdoor Unit: DCI 72Z SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5. PERFORMANCE DATA & PRESSURE CURVES 5.1 DLF 25 / ONG3-25 DCI 5.1.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C0] OD COIL ENTERING AIR DB TEMPERATURE [CO] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 TC 80 - 110 % of nominal SC 80 - 105 % of nominal PI 25 - 50 % of nominal 32/23 TC 2.42 2.57 2.73 2.89 3.05 SC 2.02 2.06 2.10 2.14 2.18 PI 0.49 0.50 0.51 0.52 0.52 TC 2.30 2.46 2.
PERFORMANCE DATA & PRESSURE CURVES 5.1.3 Heating ID COIL ENTERING AIR DB TEMPERATURE [°C] OD COIL ENTERING AIR DB/WB TEMPERATURE [°C] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 DATA 15 20 25 TC 2.16 2.01 1.86 PI 0.52 0.58 0.63 TC 2.41 2.26 2.11 PI 0.63 0.68 0.74 TC 2.59 2.44 2.29 PI 0.71 0.76 0.82 TC 2.68 2.53 2.38 PI 0.78 0.83 0.88 TC 2.75 2.59 2.44 PI 0.82 0.87 0.92 TC 3.55 3.40 3.25 PI 0.82 0.87 0.92 TC 3.75 3.60 3.44 PI 0.87 0.92 0.
PERFORMANCE DATA & PRESSURE CURVES 5.1.5 Pressure Curves (Cooling – Test Mode) Suction Pressure - Cooling (Technician Mode) 1400 Suction Pressure [KPa(g)] 1300 1200 1100 32/23 29/21 27/19 24/17 22/15 1000 900 800 700 600 500 10 15 20 25 30 35 Outdoor DB Temperature [°C] 40 45 Discharge Pressure - Cooling (Technician Mode) Discharge Pressure [KPa(g)] 4000 3750 3500 3250 3000 32/23 29/21 27/19 24/17 22/15 2750 2500 2250 2000 1750 1500 1250 1000 10 SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.1.6 Pressure Curves (Heating – Test Mode) Suction Pressure - Heating (Technician Mode) 1300 Suction Pressure [KPa(g)] 1200 1100 1000 900 15 20 25 800 700 600 500 400 300 200 -15 -10 -5 0 5 Outdoor WB Temperature [°C] 10 15 Discharge Pressure - Heating (Technician Mode) 4000 Discharge Pressure [KPa(g)] 3750 3500 3250 3000 2750 15 20 25 2500 2250 2000 1750 1500 1250 1000 -15 -10 -5 0 5 10 15 Outdoor WB Temperature [°C] 5-4 CONTENT SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.1.7 Capacity Correction Factor Due to Tubing Length Cooling 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 25 30 25 30 Tubing Lenght [m] Heating 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 Tubing Lenght [m] SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.2 DLF 35 / ONG3-35 DCI 5.2.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C0] OD COIL ENTERING AIR DB TEMPERATURE [C0] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 TC 80 - 110 % of nominal SC 80 - 105 % of nominal PI 25 - 50 % of nominal 32/23 TC 3.38 3.60 3.83 4.05 4.27 SC 2.76 2.81 2.87 2.93 2.98 PI 0.75 0.76 0.78 0.79 0.80 TC 3.22 3.44 3.66 3.88 4.11 SC 2.69 2.74 2.80 2.
PERFORMANCE DATA & PRESSURE CURVES 5.2.3 Heating ID COIL ENTERING AIR DB TEMPERATURE [°C] OD COIL ENTERING AIR DB/WB TEMPERATURE [°C] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 DATA 15 20 25 TC 2.67 2.49 2.30 PI 0.70 0.77 0.84 TC 2.98 2.79 2.60 PI 0.84 0.91 0.98 TC 3.20 3.02 2.83 PI 0.95 1.02 1.09 TC 3.32 3.13 2.94 PI 1.00 1.07 1.14 TC 3.39 3.20 3.02 PI 1.04 1.11 1.18 TC 4.39 4.20 4.01 PI 1.09 1.16 1.23 TC 4.63 4.44 4.26 PI 1.15 1.23 1.
PERFORMANCE DATA & PRESSURE CURVES 5.2.
PERFORMANCE DATA & PRESSURE CURVES 5.2.6 Pressure Curves (Heating – Test Mode) Suction Pressure - Heating (Technician Mode) 1300 Suction Pressure [KPa(g)] 1200 1100 1000 900 15 20 25 800 700 600 500 400 300 200 -15 -10 -5 0 5 Outdoor WB Temperature [°C] 10 15 Discharge Pressure - Heating (Technician Mode) Discharge Pressure [KPa(g)] 4000 3750 3500 3250 3000 2750 15 20 25 2500 2250 2000 1750 1500 1250 1000 -15 -10 -5 0 5 10 15 Outdoor WB Temperature [°C] SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.2.7 Capacity Correction Factor Due to Tubing Length Cooling 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 25 30 25 30 Tubing Lenght [m] Heating 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 Tubing Lenght [m] 5-10 CONTENT SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.3 DLF 50 / ONG3-50 DCI 5.3.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C0] OD COIL ENTERING AIR DB TEMPERATURE [C0] DATA -10 - 20 (protection range) 30 35 40 46 24/17 27/19 29/21 TC 80 - 110 % of nominal SC 80 - 105 % of nominal PI 25 - 50 % of nominal TC 25 22/15 4.83 5.15 5.47 5.78 32/23 6.10 SC 3.74 3.81 3.89 3.96 4.04 PI 1.18 1.20 1.22 1.25 1.27 TC 4.60 4.92 5.23 5.55 5.86 SC 3.64 3.72 3.79 3.
PERFORMANCE DATA & PRESSURE CURVES 5.3.3 Heating ID COIL ENTERING AIR DB TEMPERATURE [°C] OD COIL ENTERING AIR DB/WB TEMPERATURE [°C] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 DATA 15 20 25 TC 3.88 3.61 3.34 PI 1.04 1.14 1.25 TC 4.32 4.05 3.78 PI 1.25 1.36 1.46 TC 4.65 4.38 4.11 PI 1.41 1.52 1.62 TC 4.82 4.54 4.27 PI 1.49 1.60 1.70 TC 4.93 4.65 4.38 PI 1.54 1.65 1.76 TC 6.37 6.00 5.83 PI 1.62 1.73 1.84 TC 6.72 6.45 6.18 PI 1.72 1.83 1.
PERFORMANCE DATA & PRESSURE CURVES 5.3.
PERFORMANCE DATA & PRESSURE CURVES 5.3.6 Pressure Curves (Heating – Test Mode) Suction Pressure - Heating (Technician Mode) 1300 Suction Pressure [KPa(g)] 1200 1100 1000 900 15 20 25 800 700 600 500 400 300 200 -15 -10 -5 0 5 Outdoor WB Temperature [°C] 10 15 Discharge Pressure - Heating (Technician Mode) Discharge Pressure [KPa(g)] 4000 3750 3500 3250 3000 2750 15 20 25 2500 2250 2000 1750 1500 1250 1000 -15 -10 -5 0 5 10 15 Outdoor WB Temperature [°C] 5-14 CONTENT SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.3.7 Capacity Correction Factor Due to Tubing Length Cooling 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 25 30 25 30 Tubing Lenght [m] Heating 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 Tubing Lenght [m] SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.4 DLF 60 / DCI 60 (GC24) 5.4.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C0] OD COIL ENTERING AIR DB TEMPERATURE [C0] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 TC 80 - 110 % of nominal SC 80 - 105 % of nominal PI 25 - 50 % of nominal 32/23 TC 5.80 6.18 6.56 6.94 7.32 SC 4.73 4.82 4.92 5.02 5.11 PI 1.48 1.51 1.53 1.56 1.59 TC 5.52 5.90 6.28 6.66 7.04 SC 4.61 4.70 4.80 4.
PERFORMANCE DATA & PRESSURE CURVES 5.4.3 Heating ID COIL ENTERING AIR DB TEMPERATURE [°C] OD COIL ENTERING AIR DB/WB TEMPERATURE [°C] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 DATA 15 20 25 TC 4.20 3.91 3.61 PI 1.04 1.14 1.26 TC 4.68 4.38 4.09 PI 1.25 1.36 1.46 TC 5.03 4.74 4.45 PI 1.41 1.52 1.62 TC 5.21 4.92 4.62 PI 1.49 1.60 1.70 TC 5.33 5.04 4.74 PI 1.54 1.65 1.76 TC 6.89 6.60 6.31 PI 1.62 1.73 1.84 TC 7.27 6.98 6.69 PI 1.72 1.83 1.
PERFORMANCE DATA & PRESSURE CURVES 5.4.
PERFORMANCE DATA & PRESSURE CURVES 5.4.
PERFORMANCE DATA & PRESSURE CURVES 5.4.7 Capacity Correction Factor Due to Tubing Length Cooling 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 25 30 Tubing Lenght [m] Heating 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 5 10 15 20 25 30 Tubing Lenght [m] 5-20 CONTENT SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.5 DLF 72 / DCI 72Z 5.5.1 Cooling Capacity (kW) ID COIL ENTERING AIR DB/WB TEMPERATURE [C0] OD COIL ENTERING AIR DB TEMPERATURE [C0] DATA -10 - 20 (protection range) 25 30 35 40 46 22/15 24/17 27/19 29/21 TC 80 - 110 % of nominal SC 80 - 105 % of nominal PI 25 - 50 % of nominal 32/23 TC 6.77 7.21 7.65 8.09 8.54 SC 5.51 5.63 5.74 5.85 5.96 PI 1.61 1.64 1.67 1.70 1.73 TC 6.44 6.88 7.33 7.77 8.21 SC 5.37 5.49 5.60 5.71 5.
PERFORMANCE DATA & PRESSURE CURVES 5.5.3 Heating ID COIL ENTERING AIR DB TEMPERATURE [°C] OD COIL ENTERING AIR DB/WB TEMPERATURE [°C] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 DATA 15 20 25 TC 7.74 4.41 4.08 PI 1.21 1.34 1.46 TC 5.28 4.95 4.62 PI 1.46 1.58 1.71 TC 5.68 5.35 5.02 PI 1.65 1.77 1.89 TC 5.88 5.55 5.22 PI 1.74 1.86 1.99 TC 6.02 5.68 5.35 PI 1.80 1.93 2.05 TC 7.78 7.45 7.12 PI 1.90 2.02 2.14 TC 8.21 7.88 7.55 PI 2.01 2.13 2.
PERFORMANCE DATA & PRESSURE CURVES 5.5.
PERFORMANCE DATA & PRESSURE CURVES 5.5.6 Pressure Curves (Heating – Test Mode) Suction Pressure - Heating (Technician Mode) 1300 Suction Pressure [KPa(g)] 1200 1100 1000 900 15 20 25 800 700 600 500 400 300 200 -15 -10 -5 0 5 Outdoor WB Temperature [°C] 10 15 Discharge Pressure - Heating (Technician Mode) Discharge Pressure [KPa(g)] 4000 3750 3500 3250 3000 2750 15 20 25 2500 2250 2000 1750 1500 1250 1000 -15 -10 -5 0 5 10 15 Outdoor WB Temperature [°C] 5-24 CONTENT SM DLF 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.5.7 Capacity Correction Factor Due to Tubing Length Cooling 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 0 10 20 30 40 50 40 50 Tubing Lenght [m] Heating 1.05 Capacity Ratio 1.00 0.95 0.90 0.85 0.80 0.75 0 * Pre-charged to 30m. SM DLF 1-A.
AIRFLOW CURVES 6. AIRFLOW CURVES 6.1 Model: DLF 25 DCI 2.5KW AIR FLOW CHART 48 10PA 44 40 30PA 36 High 32 Med ESP 28 24 Low 20 SHigh 16 12 SMed 8 Slow 4 0 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 M ³ /HR 6.2 Model: DLF 35 DCI 3.5KW AIR FLOW CHART 48 44 10PA 40 30PA 36 32 High ESP 28 Med 24 20 Low 16 SHigh 12 8 SMed 4 Slow 0 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 M³ /HR SM DLF 1-A.
AIRFLOW CURVES 6.3 Model: DLF 50 DCI 5KW AIR FLOW CHART 10PA 48 20Pa 44 40PA 40 36 High 32 Med ESP 28 24 Low 20 SHigh 16 12 SMed 8 4 Slow 0 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 M³ /HR 6.
AIRFLOW CURVES 6.5 Model: DLF 72 DCI 7.2KW AIR FLOW CHART 60 56 52 48 10PA 44 20PA 40 40PA 36 ESP High 32 28 Med 24 Low 20 SHigh 16 12 SMed 8 Slow 4 0 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 M³ /HR 6.6 DLF UNITS RANGE AIR FLOW CORRECTION FACTORS (at nominal rating conditions — Test mode). Cooling Heating TC SC PI PI TC 60% 0.88 0.78 0.95 1.07 0.90 Air Flow Rate [% of nominal] 70% 80% 90% 0.91 0.94 0.97 0.84 0.89 0.
SOUND LEVEL CHARACTERISTICS 7. SOUND LEVEL CHARACTERISTICS 7.1 Sound Pressure Level 2m duct in supply air area 2m duct in return air area static pressure test point (2(AB)1/2 ) Unit 1.4m Mic. Figure 1 7.2 Soud Pressure Level Spectrum (Measured as Figure 1) DLF 35 NC-70 NC-60 NC-50 NC-40 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.
SOUND LEVEL CHARACTERISTICS DLF 60 NC-70 NC-60 NC-50 NC-40 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 NC-10 OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.002 MICRO BAR DLF 50 NC-70 NC-60 NC-50 NC-40 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-20 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.
SOUND LEVEL CHARACTERISTICS 7.3 Outdoor units Unit 1m Mic. Ground Figure 2 7.4 Sound Pressure Level Spectrum (Measured as Figure 2) DCI 25 Cooling DCI 25 Heating DCI 35 Cooling DCI 35 Heating SM DLF 1-A.
SOUND LEVEL CHARACTERISTICS 7-4 DCI 50 Cooling DCI 50 Heating DCI 60 Cooling DCI 60 Heating CONTENT SM DLF 1-A.
SOUND LEVEL CHARACTERISTICS DCI 72Z Cooling SM DLF 1-A.
ELECTRICAL DATA 8. ELECTRICAL DATA 8.1 Single Phase Units MODEL DLF 25-35 DLF 50-60 DLF 72 To Indoor To Indoor or Outdoor To Outdoor 1PH – 230V – 50 Hz 1PH – 230V – 50 Hz 1PH – 230V – 50 Hz Max Current, A 10.5 15 15 Circuit Breaker 16 20 20 3 X 1.5 mm2 3 X 2.5 mm2 3 X 2.5 mm2 4 X 1.5 mm2 4 X 2.5 mm2 4 X 2.5 mm2 Power Supply Power Supply Wiring No. X Cross Section mm2 Interconnecting Cable RC Model No.
WIRING DIAGRAMS 9. WIRING DIAGRAMS 9.1 Indoor Unit: DLF 25, 35, 50, 60, 72 DCI Legend To Outdoor unit EARTH L WP N COM Fresh air Water pump TB RED C/5 Connection to Display Display board RED BLU N/3 BLU BRN L/4 BRN 16 pins display connector IR-S disable jumper 15 Y/G Y/G Power supply (by installer): 1PH~220-230VAC / 50Hz Cable between indoor and outdoor units: 4x2.
WIRING DIAGRAMS 9.2 Outdoor Unit: DCI 50/60 9.2.
WIRING DIAGRAMS Outdoor Unit: DCI 72Z CHOKE COIL REVERSE BASE HEATER U V W P13 P3 P9 P11 VALVE BLUE OFAN (OPTIONAL) 1 2 3 4 5 6 1 2 P4 P14 1 2 P1 1 2 1 2 1 2 1 2 1 2 P19 P20 P2 P8 P5 1 P6 ODU CONTROLLER PCBA P10 L N COM N-COM P7 6 5 4 3 2 1 JP9 1 2 3 4 5 6 P12 EARTH Y/G FERRITE CORE OCT CTT OAT OMT HST EEV AC MAINS EMI FILTER PCBA EARTH EARTH BLACK RED BLUE BROWN SM DLF 1-A.
ELECTRICAL CONNECTIONS 10. ELECTRICAL CONNECTIONS 10.1 DLF 25, 35, 50 1PH 1 1. Indoor Unit 2. Power Supply Cable 3. Outdoor Unit 4. Interconnecting Cable: 2.5-3.5KW (4x1.5mm2) 5.0-6.0KW (4x2.5mm2) 5. Wireless Remote Control 6. Display Unit 7. Display Connector 7 6 N/3 L/4 C/5 5 2 220/240V~50Hz 4 3 10.2 8 DLF 60, 72 1PH 1 1. Indoor Unit 2. Power Supply Cable 3. Power breaker (by installer) 4. Outdoor Unit 5. Interconnecting Cable (4x2.5mm2) 6. Wireless Remote Control 7. Display Unit 8.
REFRIGERATION DIAGRAMS 11. REFRIGERATION DIAGRAMS 11.1 DLF 25 / 35 / 50 / 60 / 72 DCI Cooling Mode EEV Heating Mode EEV SM DLF 1-A.
TUBING CONNECTIONS 12. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 15-18 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8. SM DLF 1-A.
CONTROL SYSTEM 13. CONTROL SYSTEM 13.1 General Functions and Operating RulesThe DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual. 13.1.1 System Operation Concept The control function is divided between indoor and outdoor unit controllers.
CONTROL SYSTEM SW 35V14 and above NLOAD Target Frequency [Hz] 0 0 0 < NLOAD ≤ MinFreq MinFreq > MinFreq MaxFreq MinFreq {min (NLOAD, LoadDeadZone) MinFreq} MinFreq LoadDeadZone MinFreq Differences between Old and New ODU DCI/DCR software Unit DCI Current software 35V12 New software 35V14 Comment: there is no use for 35V13 software. This software is used in the past for Nordic countries. However, currently it’s stopped completely from being used.
CONTROL SYSTEM Target frequency limits as a function of outdoor air temperature (OAT): OAT Range Cooling Mode limits OAT < 6 No limit 6 ≤ OAT < 15 MaxFreqAsOATC 15≤ OAT<28 28≤ OAT 13.1.4 Heating Mode limits MaxFreqAsOAT1H MaxFreqAsOAT2H No limit Frequency Changes Control When the unit is running normally , the compressor frequency change rate is 1 Hz/sec. 13.1.5 13.1.5.1 Compressor Starting Control Compressor starting control for DCI25/35/50/60 Step3 Step2 Step1 1 Minute 13.1.5.
CONTROL SYSTEM 13.1.6 Minimum On and Off Time 3 minutes 13.1.7 Indoor Fan Control 8 Indoor fan speeds are determined for each model. 4 speeds for cool/dry/fan modes and 4speeds for heat mode. When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load. 13.1.7.
CONTROL SYSTEM OFAN State at Cool Mode $ HST 3 Degrees Change To Higher OFAN Cool state (*1) 3 Degrees % 50 & 2$7 45 Change To lower OFAN Cool state Note: Periorities A>B>C (*1) If State C, change to B If State B, change to A When compressor is switched to OFF and the heat sink temperature is above 55 degrees, the outdoor fan will remain ON in low speed for up to 3 minutes. 13.1.8.2 Outdoor Fan Control for DCI72Z OFAN operates between OFMinRPM to OFMaxRPM.
CONTROL SYSTEM 13.1.9 EEV (Electronic Expansion Valve) Control 13.1.9.1 EEV Control for DCI25/35/50/60 EEV opening is defined as EEV = EEVOL + EEVCV EEVOL is the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity. EEVCV is a correction value for the EEV opening that is based on the compressor temperature. During the first 5 minutes of compressor operation EEVCV = 0.
CONTROL SYSTEM 13.1.10 RV(Reversing Valve) Control Reversing valve is on in heat mode. Switching of RV state is done only after compressor is off for over 3 minutes. 13.1.10.1 Ioniser Control Ioniser is on when unit is on ,AND indoor fan is on ,AND Ioniser power switch (on grille) is on. 13.1.10.
CONTROL SYSTEM 13.1.13.2 Indoor Fan Control in Heating Mode Indoor fan speed depends on the indoor coil temperature: 13.1.14 Auto Cool/Heat Mode When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature (.T). Unit will switch from cool to heat when compressor is off for 3 minutes, and .T < -3. Unit will switch from heat to cool when compressor is off for 5 minutes, and .T < -3. 13.1.
CONTROL SYSTEM 13.1.16.2 Indoor Coil Defrost Protection — DLF ICT < -2 [-2, 0) [0, 2) [2, 4) [4, 6) [6, 8] >8 Trend Fast Increasing SC D1 SR SR Norm Norm Increasing SC D1 SR SR Norm Norm No Change SC D2 D1 SR SR Norm Norm Decreasing SC D2 D2 D1 SR SR Fast Decreasing SC D2 D2 D2 D1 SR 13.1.16.3 Indoor Coil Overheating Protection ICT ICT Trend Fast Decreasing >62 [60, 62) [55, 60) [52, 55) [48, 52) [45, 48) I<45 13.1.
CONTROL SYSTEM 13.1.17.2 Compressor Over Current Protection Only For DCI25/35/50/60/72Z CCR Stop-Compresor CCROC4 HzDown2 CCROC3 HzDown1 CCROC2 Stop-Rise CCROC1 Normal 13.1.18 Heat Sink Overheating Protection 13.1.08.1 Heat Sink Overheating Protection For DCI25/35/50/60/72Z HST Trend HST Fast Decreasing ≥ 90 [85, 90) [82, 85) [80, 82) [78 , 80) < 78 13.1.
CONTROL SYSTEM • Deicing Operation Procedure OCT 12 0 T h re s h o ld COMP ON T1 T1 T2 DT m a x. 1 2 m in u te s D e ic e F re q C h R V HEAT RV T3 COOL O FAN T3 ON OFF E E V D e ic e rO p e n EEV Any T1=60 secondes;T2=36 secondes;T3=6 secondes T1=50 secondes;T2=36 secondes;T3=6 secondes 13.1.
CONTROL SYSTEM Overflow when unit is ON Overflow Water Level Overflow when unit is OFF Normal ON OPER LED OFF BLINK ANY NLOAD NLOAD is forced to 0 0 ON PUMP OFF 8 min 13.1.21 8 min 8 min Operating the Unit from Mode Button (On display) Forced operation allows to start, stop and operate in Cooling or Heating, in pre-set temperature according to the following table: Forced operation Mode Cooling Heating 13.1.22 Pre-set Temperature 20ഒ 28ഒ On Unit Controls and Indicators 13.1.22.
CONTROL SYSTEM 13.1.22.2 Outdoor Unit controller Indicatiors Unit has three LED’s. SB LED is ON when power is ON (230 VAC, even when no communication). STATUS LED is ON when COMP is ON, and Blinks according to diagnostics mode definitions when either fault or protection occurs. FAULT LED Blinks according to diagnostics mode definitions when either fault or protection occurs. 13.1.23 DIP switch settings Indoor Unit Controller 13.1.23.1 Power PCB - CK PUMP Wire to Main PCB DC Motor Cable 13.1.23.
CONTROL SYSTEM 13.1.23.3 Main PCB − DLF MCU Flash Port IF Motor ICTE sensor ICT sensor RAT sensor M2L Port DIP Switch WATER level Unit On output ALARM output CLOCK RCW Power RCW 16 Pins Display (not used) To Display Water Pump Fresh Air 13-14 CONTENT SM DLF 1-A.
CONTROL SYSTEM 13.1.24 Self Test Jumper(J1)) ● Jumper for production line only, never install jumper on site! 13.1.25 DIP Switch and Jumper Settings ● CK - Dip switch default setting for each model 1 2 3 4 5 6 7 8 J2 J3 J6 J7 J8 J9 J12 J13 2.5 KW ON OFF OFF OFF OFF OFF ON OFF 3.5 KW ON OFF OFF ON OFF OFF ON OFF 5.0 KW ON ON OFF OFF OFF OFF ON OFF 6.0 KW ON ON OFF ON OFF OFF ON OFF 7.
CONTROL SYSTEM ● Presence Detector/Power Shedding Selection Select the functions of dry contact PD/PS by setting the Dip switch J9 Selection Presence Detector Power Shedding ● J9 OFF ON Installation of height compensation settings (By installer) The compensation settings according to installation height should be set by using the dip switch J12, J13 on the controller PCB Installation Height H0 H1(Factory setting) H2 H3 J12 OFF ON OFF ON J13 OFF OFF ON ON Installation height 2.1-2.7m 2.7-3.3m >3.
CONTROL SYSTEM IDU Diagnostic Table. ● Alarm Output The Alarm Output dry contact will be on (closed), when a predefined set faults occur. The fault set is defined under diagnostics section. The alarm output will be off (open), when the predefined fault is cleared.
CONTROL SYSTEM OUD Diagnostic Table AO - Alarm output No Problem AO 5 4 3 2 1 1 OCT is disconnected Yes 0 0 0 0 1 2 OCT is shorted Yes 0 0 0 1 0 3 CTT is disconnected Yes 0 0 0 1 1 4 CTT is shorted Yes 0 0 1 0 0 5 HST is disconnected (when enabled) Yes 0 0 1 0 1 6 HST is shorted (when enabled) Yes 0 0 1 1 0 7 OAT is disconnected (when enabled) Yes 0 0 1 1 1 8 OAT is shorted (when enabled) Yes 0 1 0 0 0 9 TSUC is disconnected (when enab
CONTROL SYSTEM 13.1.25 Outdoor Unit Controller 13.1.25.1 Outdoor Unit Controller - Jumper setting JP9 Jumper Layout Reserved (PIN 9) ODU3 (PIN 7) ODU2 (PIN 5) ODU1 (PIN 3) ODU0 (PIN 1) GND (PIN 10) GND (PIN 8) GND GND GND 13.1.
CONTROL SYSTEM 13.2.3 Unit Operation in Test Mode In test mode, the unit will operate in fixed settings according to the indoor fan speed setting: Indoor FAN Speed Setting Unit Setting Low Minimum Capacity Setting Turbo Nominal Capacity Setting Auto Maximum Capacity Setting During test mode, protections are disabled, except for stop compressor status. 13.3 Parameters 13.3.
CONTROL SYSTEM 13.3.
CONTROL SYSTEM 13.3.
CONTROL SYSTEM 13.3.4 Outdoor Parameters General Parameters ( for every software): # Name Default Value 1 MinOFFTime 3 2 MinONTime 3 3 OFSPCH 4 4 Down1 3 5 Down2 10 6 DImin 30 7 DImax 120 8 TimeD 1 9 DTmin 2 10 DTmax 12 11 DIT 10 12 CTMRUP 15 13 DIF 30 14 TCT 10 15 HSTOH1 78 17 HSTOH2 80 18 HSTOH3 82 19 HSTOH4 85 20 HSTOH5 90 21 HSTOHDelta1 -1 22 HSTOHDelta2 1 23 EEVCVTConst 30 24 BalanceTime 5 25 EEVInitOpen 300 SM DLF 1-A.
CONTROL SYSTEM 13.3.
CONTROL SYSTEM 13.3.
CONTROL SYSTEM 13.3.7 ODU Model Dependent Parameters ( 36V1-S01 ) Outdoor Model # Parameter 13-26 L Single DCI-72Z 1 MinFreqC 15 2 MaxFreqC 70 3 MinFreqH 15 4 MaxFreqH 90 7 Step1Freq 35 8 Step2Freq 55 9 Step3Freq 90 10 OFMinRPM 8 11 OFMaxRPM 90 12 NightRPM 65 13 OFNNoiseMaxRPM 78 14 CTTOH1 90 15 CTTOH2 95 16 CTTOH3 100 17 CTTOH4 105 18 CCROC1 12.5 19 CCROC2 13.3 20 CCROC3 14.1 21 CCROC4 14.
TROUBLESHOOTING 14. TROUBLESHOOTING WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 3 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock!!! For safe handling of the controller please refer to section 14.6 below. 14.
TROUBLESHOOTING No SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION 8 Compressor is on but outdoor fan does not work Problem with outdoor electronics or outdoor fan Check outdoor fan motor according to the procedure in section 14.5.3 , if not OK replace controller 9 Unit works in wrong mode (cool instead of heat or heat instead of cool) Electronics or power connection to RV Check RV power connections, if OK, Check RV operation with direct 230VAC power supply, if OK, Replace outdoor controller.
TROUBLESHOOTING When system enters diagnostics mode, only one fault code is shown. Order of priority is from the lower to the higher number. Diagnostics is continuously ON as long as power is ON. The current system operation mode will not be changed. If no fault occurred in the system, no fault code will be displayed during normal operation mode. The last fault code will be displayed even if the system has recovered from that fault.
TROUBLESHOOTING No Problem AO 5 4 3 2 1 28 Model A No 1 1 1 0 0 29 Model B No 1 1 1 0 1 30 Model C No 1 1 1 1 0 31 Model D No 1 1 1 1 1 * CN / LSN Units only 14.3.2 Indoor Unit Diagnostics and Corrective Actions No.
TROUBLESHOOTING No Problem AO 5 4 3 2 1 10 OMT is shorted (DCI72 / 72Z / 80) Yes 0 1 0 1 0 11 IPM Fault Yes 0 1 0 1 1 12 Bad EEPROM No 0 1 1 0 0 13 DC under voltage Yes 0 1 1 0 1 14 DC over voltage Yes 0 1 1 1 0 15 AC under voltage Yes 0 1 1 1 1 16 Mismatch IDU & ODU models (*SW 35V14 and above) Yes 1 0 0 0 0 17 No Communication Yes 1 0 0 0 1 18 Reserved No 1 0 0 1 0 20 Heat sink Over Heating No 1 0 1 0 0 21 Deicing N
TROUBLESHOOTING No. Fault 8 Compressor Lock 9 Bad Communication 14.4 Probable Cause Corrective Action Switch unit to STBY and restart If still not ok check compressor (14.5.4) If comp is ok replace OU controller If compressor is not ok replace compressor Communication quality is low reliability Check Indoor to Outdoor wiring and grounding Judgment by MegaTool MegaTool is a special tool to monitor the system states. Using MegaTool requires: • • • A computer with RS232C port.
TROUBLESHOOTING 14.5.4 Checking the Compressor. The compressor is brushless permanence magnetic DC motor. Three coil resistance is same. Check the resistance between three poles. The normal value should be below 0.5 ohm (TBD). 14.5.5 Checking the Reverse Valve (RV). Running in heating mode, check the voltage between two pins of reverse valve connector, normal voltage is 220VAC. 14.5.6 Checking the electrical expansion valve (EEV). The EEV has two parts, drive part and valve.
EXPLODED VIEWS AND SPARE PARTS LISTS EXPLODED VIEWS AND SPARE PARTS LISTS 15.1 Indoor Unit: DLF 25/35/50 G F SM DLF 1-A.1 GB CONTENT E D D D E D E 15.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.2 Indoor Unit: DLF 25 DCI No.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.3 Indoor Unit: DLF 35 DCI No.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.4 Indoor Unit: DLF 50 DCI No.
EXPLODED VIEWS AND SPARE PARTS LISTS E D SM DLF 1-A.1 GB E D D F D G E Indoor Unit: DLF 60 / 72 DCI 15.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.6 Indoor Unit: DLF 60 DCI No.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.7 Indoor Unit: DLF 72 DCI No.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.8 15-8 Outdoor Unit: DCI 50 CONTENT SM DLF 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.9 Outdoor Unit: DCI 50 No. Part No. Description Unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 433218 4526340 433223 4526476 4526475 4526457 4527363 4526459 4526203 4524595 4524176 4526224 4526396 4526223 Front panel A Air inlet ring-420 Painting insulation plate Axial fan OD=401 DC motor for DCI 50 Motor support Base painting Assy. Partition Outdoor DC inverter controller (English) Gas valve (R410A) Liquid valve(R410A) EMI filter board 901-098-00 Chock Assy.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.10 15-10 Outdoor Unit: DCI 60 CONTENT SM DLF 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.11 No.. Outdoor Unit: DCI 60 Item Description 1 4517144 FAN COVER PP+UV 1 2 452795700 PAINTED LEFT CABINET ASSY 1 3 4521642 Painted Right Cabinet and Isolation Assy.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.12 15-12 Outdoor Unit: DCI 72Z CONTENT SM DLF 1-A.
EXPLODED VIEWS AND SPARE PARTS LISTS 15.13 Outdoor Unit: DCI 72Z No. Item Description 1 465100000 Grill/ DCI Trio 2 4523652 PAINTED LEFT CABINET ASSY 1 3 4523758 Nut M8 left 1 4 452960400 Outdoor Fan 1 5 461600023 4-Way Valve Assy.
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► REMOTE CONTROL RC3 ► REMOTE CONTROL RC4 ► REMOTE CONTROL RC7 ► INSTALLATION AND OPERATION MANUAL DLF 25, 35, 50, 60, 72 SM DLF 1-A.
REMOTE CONTROL MANUAL ENGLISH APPENDIX A CONTENT PRECAUTIONS ...................1-2 USING THE REMOTE CONTROL UNIT .....................3 MODE ROOM IFEEL SLEEP TEMP TIMER SET CLEAR HOUR OPERATION ........................4-8 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read this operating instruction carefully and keep it for future reference. 468040071/01 16-2 CONTENT SM DLF 1-A.
APPENDIX A PRECAUTIONS DISPLAY Information are displayed when the remote control unit is switched on. Operation Mode Automatic Heating Cooling Dehumidification (dry) Fan only Displayed when data trasmitted Or remote control unit lock Displayed when the timer is set and activated.
APPENDIX A TRANSMITTER When you press the buttons of the remote control unit, the mark appears on the display to transmit the setting changes to the receiver in the air conditioner. SENSOR Atemperature sensor inside the remote control unit detects the room temperature. FAN SPEED SELECTOR BUTTON Fan speed is automatically selected by the microcomputer. High speed. Medium speed. Low speed. TEMPERATURE SETTING BUTTONS - (cooler) Press this button to decrease the set temperature.
APPENDIX A USING THE REMOTE CONTROL UNIT HOW TO INSTALL BATTERIES OPERATION WITH THE REMOTE CONTROL UNIT Remove the lid in the rear part of the remote control unit. Insert two AAA alkaline batteries of 1,5 V-DC. Make sure the batteries point in the direction marked in the battery compartment. The batteries last about six months. Depending on how much you use the remote control unit. Remove the batteries if you do not use the remote control unit for more than one month.
APPENDIX A OPERATION HOW TO SET THE PRESENT TIME THE DISPLAY SHOWS THE SELECTED TEMPERATURE. 1. Press the SET button for five seconds. The time indication alone flashes. 2. Press the + or - buttons until the present time is displayed. 3. Press the SET button to stop the indication flashing. 4. Press the FAN SPEED button to select the fan speed. 5. Press the FLAP buttons and adjust the air flow direction as desired(see adjustment of air flow). Make sure that the remote control is switched on.
APPENDIX A OPERATION AUTOMATIC OPERATION DEHUMIDIFYING (DRY) 1. Set the MODE selector to AUTO . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.). 1. Set the MODE selector switch to “DRY” . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.).
APPENDIX A OPERATION ADJUSTING THE FAN SPEED SLEEP MODE AUTOMATIC The SLEEP mode enables you to save energy. 1. Set the MODE selector to cool, dry or heat. 2. Press the SLEEP button. 3. The mark appears on the display. Press the SLEEP button again to release the SLEEP function. Simply set the FAN SPEED selector to the position . A microcomputer automatically controls the fan speed when the AUTO mode is selected.
APPENDIX A OPERATION A) HOW TO SET THE ON TIME I FEEL TEMP FUNCTION OPERATION 1. Press the TIMER button to select the desired timer. 2. Press the SET button till the ON sign blinks. 3. Press the + or - (HOUR) button until the desired value is displayed. 4. Press the SET button to activate the timer. Press button IFEEL to activate the IFEEL function. Thermometer sign will appear on the . Select suitable LCD operation display temperature setting.
APPENDIX A OPERATION D) HOW TO CLEAR THE TIMER 1. Press the TIMER button to select the timer. 2. Press the CLEAR button if you want that every timer operation will be cleared. NOTE If the procedure to set the timer is not completed, by pushing the SET button, within 15 seconds the timer operation will be cancelled and the last set-up is restored.
REMOTE CONTROL MANUAL ENGLISH APPENDIX A CONTENT PRECAUTIONS ...................1-2 USING THE REMOTE CONTROL UNIT .....................3 OPERATION ......................4-10 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read this operating instruction carefully and keep it for future reference. 468040125/01 SM DLF 1-A.
APPENDIX A PRECAUTIONS DISPLAY Information are displayed when the remote control unit is switched on.
APPENDIX A FAN SPEED SELECTOR BUTTON TRANSMITTER SENSOR When you press the buttons of the remote control unit, the mark appears on the display to transmit the setting changes to the receiver in the air conditioner. Atemperature sensor inside the remote control unit detects the room temperature. Fan speed is automatically selected by the microcomputer. Low speed. Medium speed. High speed. TEMPERATURE SETTING BUTTONS - (cooler) + (warmer) Press this button to decrease the set temperature.
APPENDIX A USING THE REMOTE CONTROL UNIT HOW TO INSTALL BATTERIES OPERATION WITH THE REMOTE CONTROL UNIT Remove the lid in the rear part of the remote control unit. Insert two AAA alkaline batteries of 1,5 V-DC. Make sure the batteries point in the direction marked in the battery compartment. The batteries last about six months. Depending on how much you use the remote control unit. Remove the batteries if you do not use the remote control unit for more than one month.
APPENDIX A OPERATION HOW TO SET THE PRESENT TIME HEATING 1. Press the SET button for five seconds. The time indication alone flashes. 2. Press the + or - buttons until the present time is displayed. 3. Press the SET button to stop the indication flashing. 1. Set the MODE selector to HEAT . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.).
APPENDIX A OPERATION AUTOMATIC OPERATION DEHUMIDIFYING (DRY) 1. Set the MODE selector to AUTO . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.). 1. Set the MODE selector switch to “DRY” . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.).
APPENDIX A OPERATION ADJUSTING THE FAN SPEED SLEEP MODE AUTOMATIC The SLEEP mode enables you to save energy. 1. Set the MODE selector to cool, dry or heat. 2. Press the SLEEP button. mark appears on the display. Press 3. The the SLEEP button again to release the SLEEP function. Simply set the FAN SPEED selector to the position . A microcomputer automatically controls the fan speed when the AUTO mode is selected.
APPENDIX A OPERATION I FEEL TEMP FUNCTION OPERATION SETTING THE TIMER Press button IFEEL to activate the IFEEL function. Thermometer sign will appear on the . Select suitable LCD operation display temperature setting. Make sure that the remote control unit is aimed at the air conditioner, with the IFEEL sensor in front. Prevent the IFEEL sensor from being affected by heat sources such as lamps, heaters, direct sun, etc. or from being directly affected by the air conditioner air flow.
APPENDIX A OPERATION B) HOW TO SET THE OFF TIME ADJUSTING THE AIR FLOW DIRECTION 1. Press the TIMER button to select the desired timer. 2. Press the SET button till the OFF sign blinks. 3. Press the + or - (HOUR) button until the desired value is displayed. 4. Press the SET button to activate the timer. HORIZONTAL (manual) The horizontal air flow can be adjusted by moving the vertical vanes to the left or right, as indicated in the following figures.
REMOTE CONTROL MANUAL ENGLISH APPENDIX A CONTENT PRECAUTIONS ...................1-2 USING THE REMOTE CONTROL UNIT .....................3 OPERATION ........................4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read this operating instruction carefully and keep it for future reference. 468040197/01 16-20 CONTENT SM DLF 1-A.
APPENDIX A PRECAUTIONS DISPLAY Information are displayed when the remote control unit is switched on.
APPENDIX A TRANSMITTER SENSOR TEMPERATURE SETTING BUTTONS When you press the buttons of the remote control unit, the mark appears on the display to transmit the setting changes to the receiver in the air conditioner. Atemperature sensor inside the remote control unit detects the room temperature. + (warmer) - (cooler) Press this button to decrease the set temperature. Press this button to increase the set temperature.
APPENDIX A USING THE REMOTE CONTROL UNIT HOW TO INSTALL BATTERIES OPERATION WITH THE REMOTE CONTROL UNIT Remove the lid in the rear part of the remote control unit. Insert two AAA alkaline batteries of 1,5 V-DC. Make sure the batteries point in the direction marked in the battery compartment. The batteries last about six months. Depending on how much you use the remote control unit. Remove the batteries if you do not use the remote control unit for more than one month.
APPENDIX A OPERATION 4. Press the FAN SPEED button to select the fan speed. 5. Press the FLAP buttons and adjust the air flow direction as desired(see adjustment of air flow). Make sure that the remote control is switched on. HOW TO SET THE PRESENT TIME 1. Press the SET button for five seconds. The time indication alone flashes. 2. Press the + or - buttons until the present time is displayed. 3. Press the SET button to stop the indication flashing.
APPENDIX A OPERATION AUTOMATIC OPERATION DEHUMIDIFYING (DRY) 1. Set the MODE selector to AUTO . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.). 1. Set the MODE selector switch to “DRY” . 2. Press the ON/OFF button and switch the air condioner ON. 3. Press the TEMP. buttons to set the desired temperature (the temperature range is between 30 °C max. and 16 °C min.).
APPENDIX A OPERATION ADJUSTING THE FAN SPEED SLEEP MODE AUTOMATIC The SLEEP mode enables you to save energy. 1. Set the MODE selector to cool, dry or heat. 2. Press the SLEEP button. 3. The mark appears on the display. Press the SLEEP button again to release the SLEEP function. Simply set the FAN SPEED selector to the position . A microcomputer automatically controls the fan speed when the AUTO mode is selected.
APPENDIX A OPERATION SETTING THE TIMER I FEEL TEMP FUNCTION OPERATION There are four timers that can be selected on the remote control.Two daily timers (designated as T1,T2) ,and two optional weekend timers (designated as WKTI, WKT2) .Each timer can be selected by pressing TIMER button. The daily timers T1 and T2 can be set for ON and OFF separately for two different time periods. Timer setting will not change until new setting is input.
APPENDIX A OPERATION 3. Press the + or - (HOUR) button until the desired value is displayed. 4. Press the SET button to activate the timer. ADJUSTING THE AIR FLOW DIRECTION HORIZONTAL (manual) The horizontal air flow can be adjusted by moving the vertical vanes to the left or right, as indicated in the following figures. VERTICAL (with remote control unit) The remote control gives you the possibility to control the flap in two way: button to start the flap sweep. If 1.
APPENDIX A OPERATION Use the FLAP button on the remote control to adjust the position of the flap. If you move the flap by hand, the factual flap position and the flap position on the remote control may no longer match. If this should happen, shut off the unit, wait for the flap to close, and then turn on the unit again; the flap position will now be normal again. Do not have the flap pointed down during cooling operation. Condensation may begin to form around the air vent and drip down.
APPENDIX A CONCEALED AIR CONDITIONER WITH ELECTRONIC CONTROL SERIES LSN DCI INSTALLATION INSTRUCTIONS 16-30 CONTENT SM DLF 1-A.
APPENDIX A Getting Started… REQUIRED TOOLS LIST 1. Screw driver 2. Electric drill, hole core drill (60 mm) 3. Hexagonal wrench 4. Spanner 5. Pipe cutter 6. Reamer 7. Knife 8. Gas leak detector 9 Measuring tape 10. Thermometer 11. Megameter 12. Multimeter 13. Vacuum pump 14. Gauge manifold (for R-410A) 15. Torque wrench 18 Nm (1.8 kgf.m) 45 Nm (4.5 kgf.m) 65 Nm (6.5 kgf.m) 75 Nm (7.5 kgf.m) 85 Nm (8.5 kgf.m) ATTENTION 1. Selection of the units location.
APPENDIX A SAFETY PRECAUTIONS Read the following "SAFETY PRECAUTIONS" carefully before installation. Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed. The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below.
APPENDIX A Installation/Service Tooling for R410A Changes Gauge manifold As the working pressure is high, it is impossible to measure the working pressure using conventional gauges. In order to prevent any other refrigerant from being charged, the port diameters have been changed. Charge hose In order to increase pressure resisting strength, hose materials and port sizes have been changed (to 1/2 UNF 20 threads per inch). When purchasing a charge hose, be sure to confirm the port size.
APPENDIX A CAUTION R410A Air Conditioner Installation THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER. R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed.
APPENDIX A ATTACHED ACCESSORIES Description Amount Name Technician’s installation 1 manual Instruction manual for 1 remote control Instruction manual for unit 1 display Remote control including 1 batteries 1 Remote control bracket 1 Central control display 4 Rubber mounting pads 4 Tie-Wraps Installation instructions Operation instructions for remote Operation instructions Operating the air-conditioner Hanging the remote control on the wall Operating and main working display Padding of the outdoor u
APPENDIX A GENERAL INFORMATION Indoor Unit The unit can be installed as concealed unit above a false ceiling or as vertical floor mounted. Since the unit is a concealed and not a ducted unit, it is very important that the ducts length will fit the maximum external static pressure allowed in the table in page 9. For vertical installation, refer to the special instructions in drainage and electrical connection chapters. Horizontal Installation 16-36 Vertical Installation CONTENT SM DLF 1-A.
APPENDIX A MAXIMUM PIPES LENGTH & HEIGHT NOMINAL TUBES O.D LENGTH (A) HEIGHT (B) CAPACITY 2.5kW 1/4"-3/8" 20 10 3.5kW 1/4"-3/8" 20 10 5kW 1/4"-1/2" 30 15 6kW 1/4"-1/2" 30 15 7.2kW 3/8"-5/8" 50 25 EXTERNAL STATIC PRESSURE NOMINAL CAPACITY 2.5kW 3.5kW 5kW 6kW 7.2kW NOMINAL MAX 10 10 10 10 10 30 30 40 40 40 SM DLF 1-A.
APPENDIX A GENERAL PRECAUTIONS Always use the support of a large radius cylinder for banding the tubes, using pipe bending tools Do not leave nuts of gas tubes uncovered.
APPENDIX A INDOOR UNIT UNIT LOCATION UNIT DIMENSIONS While selecting a place for the indoor unit: a. Allow max. air flow to the desired space. b. Allow max return air flow. c. Ensure adequate drainage of condensed water. d. Ensure noise reduction near bedrooms. e. Leave a minimum 200 mm free space in the rear side of the unit. f. Allow a free service access to electrical box. h. Allow easy access to the base of the indoor unit while providing enough space from the ceiling. i.
APPENDIX A UNIT INSTALLATION a. Insert 4 M10 or 3/8" threads rods into the ceiling. b. Introduce the rods through the slots of unit suspension brackets. c. Position the shock absorbers, add washers and screw the nuts until the unit is firmly supported. d. In case of a gap between the unit and the ceiling, put a rubber or a neoprene sheet. IMPORTANT The unit must be perfectly leveled HOLES DRILLING LOCATION ON THE CEILLING FOR INDOOR UNIT NOMINAL CAPACITY 2.5-5kW 6.
APPENDIX A DRAINAGE INSTALLATION General For an efficient functioning of the drainage system, please take care of the following: Always balance the unit with 2° downward to the drainage side of the unit. Use 19 mm tube drainage. It is recommended to prepare a drainage point by professional plumber close to the unit. For proper drainage, the passage must be planned with 1° down slope. Prevent any upwards or reverse flow in any part.
APPENDIX A AIR FILTER LOCATION The air filter is located in the rear side of the unit (default from factory) but can be easily relocated in the bottom of the unit if it is required. For vertical installation, it is recommended to relocate the filter in front of the unit. AIR FILTER CLEANING For cleaning the filter remove it by pushing up toward the back of the unit and pull it out as described bellow. AIR FILTER RELOCATION 1. Remove air filter from the unit. 2. Remove panel 4. 3. Remove filter trails 2-3.
APPENDIX A OUTDOOR UNIT UNIT DIMENSIONS NOMINAL A CAPACITY 2.5-5.0kW 610 6kW 690 7.2kW 864 CLEARENS AROUND THE UNIT B C D E F 795 846 950 500 545 527 148 152 212 290 302 340 293 330 378 SEVERAL OUTDOORS INSTALATION When installing several outdoors units please take into account the air flow around the units and follow the minimum distance suggestions as shown in the diagrams bellow. Row Installation Back to Back Front to Front Front to Back SM DLF 1-A.
APPENDIX A DISPOSAL OF OUTDOOR UNIT CONDENSED WATER In case of using a drain elbow, the unit should be placed on a stand at least 3 cm high. Install the hose with a downward to allow smooth flow of draining water. Use 16mm I.D. tube for drainage. PIPES CONNECTIONS CUTTING AND FLARING THE PIPES 1. Please use the pipe cutter for cutting the pipes. 2. Remove all burrs by using reamer. Gas leakage might happen If burrs are not removed ! Turn pipes edge down to avoid metal powder from entering down the pipes.
APPENDIX A PIPE CONECTIONS TO THE UNIT Connecting to the indoor unit 1. Align the center of the pipes and finger tight the flare nut. 2. Use the torque wrench to tighten the nut firmly. Connecting to the outdoor unit 1. Align the center of the pipes to the valves. 2. Use the torque wrench to tighten the valves firmly according to table: Tube (Inch)/ Torque(N.
APPENDIX A ELECTRICAL CONNECTIONS POWER SUPPLY NOMINAL 1PH ELECRICAL SPECIFICATIONS 1PH UNITS VOLTAGE LIMITS 230/50/1 198-264V POWER SUPPLY TO OUTDOOR UNIT NOMINAL CAPACITY CIRCUIT BRAKER POWER SUPPLY CABLE 2.5-3.5kW 5.0-6.0kW 7.2kW NOT APPLICABLE 2 20A 3x2.5mm 20A 3x2.5mm2 POWER SUPPLY TO INDOOR UNIT CIRCUIT BRAKER POWER SUPPLY CABLE 2 16A 3x1.5mm 2 20A 3x2.
APPENDIX A 1PH Units Power supply to indoor (2.5, 3.5, 5.0, 6.0 kW units) 1. 2. 3. 4. Indoor unit Power supply cable Outdoor unit Interconnecting cable 2 (2.5÷3.5 kW : 4x1.5 mm ) 2 (5.0÷6 kW: 4x2.5 mm ) 5. Wireless remote control 6. Display unit 7. Display connector SM DLF 1-A.1 GB 1PH Units Power supply to outdoor (5.0, 6.0, 7.2 kW units) 1. Indoor unit 2. Power supply cable 3. Power breaker (*by installer) 4. Outdoor unit 5. Interconnecting cable (4x2.5mm2) 6. Wireless remote control 7.
APPENDIX A DIPSWITCH SETTING Each model has his dipswitch setting. It is very important verifying the setting according to the table below during installation for avoiding malfunctioning of the unit. 2.5kW 3.5kW 5.0kW 6.0kW 7.
APPENDIX A DISPLAY CONTROL UNIT LOCATION CRITERIA It is recommended to install the Display Control Unit close to a ceiling in a central and neutral zone at typical conditions. In addition, the aesthetic aspect should be considered. The Display Control Unit is connected to the main control board on the air conditioner (the indoor unit) by a communication cable. The cable is connected to the Display Control Unit by a quick-connector.
APPENDIX A Connection of several Displays in parallel units 1. Main Control Board on Indoor Unit 2. Distribution Board, Cat N. 402729 3. Communication cable Cat. N. 402730 4. Display Control Unit Cat. N. 402713 Check list before operation CHECK THE DRAINAGE EVALUATION OF THE PERFORMANCE Pour water into the drain tray-styrofoam. Ensure that water flows out from drain hose of the indoor unit. Operate the unit at cooling mode and high fan speed for fifteen minutes or more.