Service manual
5-4
PERFORMANCE DATA
Revision Y06-01
Service Manual - WNG/LEX DCI
5.3 WNG 35/LEX 35 DCI
5.3.1 Cooling Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB
TEMPERATURE
[ºC]
DATA 22/15 24/17 27/19 29/21 32/23
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
-10 - 20
(protection range)
PI
25 - 50 % of nominal
TC 3.38 3.60 3.83 4.05 4.27
SC 2.40 2.45 2.50 2.55 2.60
25
PI 0.78 0.79 0.81 0.82 0.84
TC 3.22 3.44 3.66 3.88 4.11
SC 2.34 2.39 2.44 2.49 2.54
30
PI 0.87 0.88 0.90 0.91 0.93
TC 3.06 3.28
3.50
3.72 3.94
SC 2.28 2.33
2.38
2.43 2.48
35
PI 0.96 0.98
0.99
1.00 1.02
TC 2.89 3.12 3.34 3.56 3.78
SC 2.22 2.27 2.32 2.37 2.42
40
PI 1.05 1.07 1.08 1.10 1.11
TC 2.70 2.92 3.14 3.36 3.58
SC 2.15 2.20 2.25 2.30 2.34
46
PI 1.16 1.18 1.19 1.21 1.22
LEGEND
TC – Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU - Outdoor
5.3.2 Capacity Correction Factors
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
20 25 30 35 40 45
Outdoor Temperature [deg C]
Capacity Ratio
CONTENT
WNG/LEX DCI