Technical Manual Multi Split Trio Quattro DCI Indoor Units WNG 9 DCI INV WNG 12 DCI INV WNG 18 DCI INV ECF 9 DCI INV ECF 12 DCI INV ECF 18 DCI INV PXD 9 DCI INV PXD 12 DCI INV PXD 18 DCI INV LS 35 DCI INV REFRIGERANT R410A TM TQDCI E 0 GB Outdoor Units TRIO DCI QUATTRO DCI HEAT PUMP 08-2005
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ August 2005 Total number of pages in this publication is 88 consisting of the following: Page No. Revision No. # Title ......................
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The Trio/Quattro DCI Multi series is a full line multi-tubing system with 3 to 4 connected indoor units. The multi-split inverter is a high level technology product for residential and commercial application offering comfort, low noise operation and energy saving. 1.2 Main Features 1.2.1 High Technology • • • • • • 1.2.2 • • • • • • • • • • • • • • • 1.3 Sine wave form in both OFAN and Compressor drives. DC-BL-SL (Sensor less) Inverter Compressor drive.
INTRODUCTION 1.5 Matching Table R410A DCI INDOOR UNITS OUTDOOR UNITS REFRIGER. WNG 9/12/18 ECF 9/12/18 PXD 9/12/18 LS 35 Trio DCI R410A √ √ √ √ Quattro DCI DCI R410A √ √ √ √ MODEL 1.6 Indoor Unit combinations Trio Unit A 9 9 9 9 12 9 12 Unit B 9 9 9 12 12 12 12 Unit D 9 12 18 12 12 18 18 Quattro Code Sum 3 3.5 4 4 4.5 4.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.1 Outdoor TRIO DCI Specifications. Model TRIO DCI R410A Operation Mode Cooling Capacity (1), (2) Heating Kcal/hr 6,190 (1,120~7,740) 7,740 (820~9,460) Btu/hr 24,570 (4,440~30,710) 30,710 (3,240~37,530) W 7,200 (1,300~9,000) 9,000 (950~11,000) W 2,240 (500~3,000) 2,370 (500~3,000) W/W 3.21 3.80 Running Current (3) A 9.7 Starting Current A Total Input E.E.R (Cooling) / C.O.P (Heating) 9.8 10 Inrush Current A <35.
PRODUCT DATA SHEET 2.2 Outdoor QUATTRO DCI Specifications. Model QUATTRO DCI R410A Operation Mode Capacity (1), (2) Total Input E.E.R (Cooling) / C.O.P (Heating) Running Current (3) Cooling Heating Kcal/hr 6,880 (1,200~7,910) 8,170 (820~9,460) Btu/hr 27,300 (4,780~31,390) 32,410 (3,240~37,530) W 8,000 (1,400~9,200) 9,500 (950~11,000) W 2,490 (500~3,000) 2,380 (400~3,000) W/W 3.21 4.00 A 10.8 10.3 Starting Current A 11 Inrush Current A <35.
PRODUCT DATA SHEET 2.3 Indoor Units Data 2.3.1 WNG 9 DCI Specifications WNG 9 DCI / Wall Mounted Model Indoor Unit / Type Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 Fan Type & Quantity INDOOR Airflow(2) Cooling / Heating Sound Power Level(3) Cooling / Heating Sound Pressure Level (4) Cooling / Heating Crossflow *1 H/M/L m3/hr 530/570 430/460 330/350 L-H dB (A) 39-50 / 39-51 L-H dB (A) 26-38 / 26-39 mm 16 Condensate Drain Tube I.D.
PRODUCT DATA SHEET WNG 18 DCI Specifications 2.3.3 WNG 18 DCI / Wall Mounted Model Indoor Unit / Type Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 Fan Type & Quantity Crossflow *1 INDOOR Airflow(2) Cooling / Heating Sound Power Level(3) Sound Pressure Level (4) H/M/L m3/hr L-H dB (A) 47 - 55 L-H dB (A) 34 -43 W/H/D mm Condensate Drain Tube I.D.
PRODUCT DATA SHEET ECF 12 DCI Specifications 2.3.5 ECF 12 DCI / Cassette Model Indoor Unit / Type Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 INDOOR Fan Type & Quantity Centifugal *1 Airflow(2) Cooling / Heating H/M/L m3/hr Sound Power Level(3) Cooling / Heating L-H dB (A) 42-49 / 42-48 Sound Pressure Level (4) Cooling / Heating L-H dB (A) 32-38 / 32-38 W/H/D mm Condensate Drain Tube I.D.
PRODUCT DATA SHEET PXD 9 DCI Specifications 2.3.7 PXD 9 DCI Floor/ceiling Model Indoor Unit / Type Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 INDOOR Fan Type & Quantity Centifugal *2 Airflow(2) Cooling / Heating H/M/L m3/hr Sound Power Level(3) Cooling / Heating L-H dB (A) 47-50 Sound Pressure Level (4) Cooling / Heating L-H dB (A) 39-35 Condensate Drain Tube I.D.
PRODUCT DATA SHEET PXD 18 DCI Specifications 2.3.9 PXD 18 DCI Floor/ceiling Model Indoor Unit / Type Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 INDOOR Fan Type & Quantity Centifugal *2 Airflow(2) Cooling / Heating H/M/L m3/hr Sound Power Level(3) Cooling / Heating L-H dB (A) 56 - 65 Sound Pressure Level (4) Cooling / Heating L-H dB (A) 45 - 51 mm 16 Condensate Drain Tube I.D.
RATING CONDITIONS 3. RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.
OUTLINE DIMENSIONS 4. OUTLINE DIMENSIONS 4.1 Indoor Unit: WNG 9/12 DCI 4.
OUTLINE DIMENSIONS 4.3 Indoor Unit: ECF 9, 12, 18 DCI 4.
OUTLINE DIMENSIONS 4.5 Indoor Unit: LS 35 DCI 4.
PERFORMANCE DATA 5. PERFORMANCE DATA 5.1 Outdoor Unit Trio DCI Combinations (Based on WNG) 5.1.1 Cooling Cooling Capacity [KW] Power Consumption [W] Model COP Nom. Energy Efficiency Class A B C Nom. Min. Max. Nom. Min. Max. 925 - - 2.50 2.50 1.30 3.70 685 500 1,025 3.65 A 12 35 - - 3.50 3.50 1.30 4.40 968 500 1,223 3.62 A 18 50 - - 5.00 5.00 1.49 5.93 1,393 566 1,656 3.59 A 9+9 25+25 - 2.54 2.54 5.08 1.86 6.56 1,498 683 1,856 3.
PERFORMANCE DATA 5.1.2 Heating Power Consumption [W] Heating Capacity [KW] Model COP Nom. Energy Efficiency Class A B C Nom. Min. Max. Nom. Min. Max. 925 - - 3.40 3.40 0.95 4.00 685 500 897 4.96 A 12 35 - - 4.30 4.30 0.95 5.20 1,003 485 1,320 4.29 A 18 50 - - 6.20 6.20 1.11 7.50 1,673 549 2,131 3.71 A 9+9 25+25 - 3.60 3.60 7.20 1.43 9.10 1,883 649 2,636 3.82 A 25+35 9+12 - 3.26 4.34 7.60 1.43 9.50 2,009 649 2,711 3.
PERFORMANCE DATA 5.2 Outdoor Unit Quattro DCI Combinations (Based on WNG) 5.2.1 Cooling Power Consumption [W] Cooling Capacity [KW] Model A B C D Nom. Min. Max. Nom. Min. Max. COP Nom. Energy Efficiency Class 9 25 - - - 2.50 2.50 1.40 3.70 685 500 1,025 3.65 A 12 35 - - - 3.50 3.50 1.40 4.40 968 500 1,223 3.62 A 18 50 - - - 5.00 5.00 1.60 5.60 1,393 570 1,563 3.59 A 9+925+25 - - 2.54 2.54 5.08 2.00 6.20 1,453 689 1,742 3.
PERFORMANCE DATA 5.2.2 Heating Power Consumption [W] Heating Capacity [KW] Model A B C D Nom. Min. Max. Nom. Min. Max. COP Nom. Energy Efficiency Class 9 25 - - - 3.40 3.40 0.95 4.00 685 400 859 4.96 A 12 35 - - - 4.30 4.30 0.95 5.20 946 388 1,207 4.54 A 18 50 - - - 6.20 6.20 1.11 7.50 1,497 455 1,875 4.14 A 9+925+25 - - 3.64 3.64 7.28 1.43 8.63 1,707 539 2,172 4.26 A 9+12 25+35 - - 3.29 4.39 7.68 1.43 9.01 1,838 539 2,235 4.
PERFORMANCE DATA 5.3 WNG-9-DCI 5.3.1 Cooling Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.16 1.03 1.
PERFORMANCE DATA 5.5.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.72 PI 0.89 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 TC PI TC PI TC PI TC PI 1.04 0.94 1.10 1.00 1.16 1.
PERFORMANCE DATA 5.4 WNG-12 DCI 5.4.1 Cooling Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.16 1.03 1.
PERFORMANCE DATA 5.4.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) DATA 15 20 25 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 1.00 1.00 1.06 1.06 1.12 1.
PERFORMANCE DATA 5.5 WNG-18 DCI 5.5.1 Cooling Capacity Factors - Unit D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.08 1.10 0.
PERFORMANCE DATA 5.5.3 Heating Capacity Factors - Unit D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) DATA 15 20 25 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 1.00 1.00 1.06 1.02 1.11 1.
PERFORMANCE DATA 5.6 ECF-9 DCI 5.6.1 Cooling Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.16 1.03 1.
PERFORMANCE DATA 5.6.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) DATA 15 20 25 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.72 1.
PERFORMANCE DATA 5.7 ECF-12 DCI 5.7.1 Cooling Capacity Factors - Run Mode (Unit A,B,C or D) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.
PERFORMANCE DATA 5.7.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/ WB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 1.00 1.00 1.06 1.06 1.12 1.11 85 - 105 % of nominal 80 - 120 % of nominal 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.
PERFORMANCE DATA 5.8 ECF-18 DCI 5.8.1 Cooling Capacity Factor - Unit D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.08 1.10 0.
PERFORMANCE DATA 5.8.3 Heating Capacity Factor - Unit D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] -15/-16 -10/-12 -7/-8 -1/-2 2/1 7/6 10/9 15/12 15-24 (Protection Range) DATA 15 20 25 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.92 1.07 0.95 1.12 0.97 1.18 0.99 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 0.32 0.80 0.47 0.89 0.58 0.96 0.63 0.99 0.67 1.02 1.
PERFORMANCE DATA 5.9 PXD-9 DCI 5.9.1 Cooling Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.09 1.16 1.03 1.
PERFORMANCE DATA 5.9.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/ WB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.89 1.04 0.94 1.10 1.00 1.16 1.05 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 1.00 1.00 1.06 1.06 1.12 1.11 85 - 105 % of nominal 80 - 120 % of nominal 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.
PERFORMANCE DATA 5.10 PXD-12 DCI 5.10.1 Cooling Capacity Factors - Run Mode (Unit A,B,C or D) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.
PERFORMANCE DATA 5.10.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/ WB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.72 PI 0.89 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 TC PI TC PI TC PI TC PI 1.04 0.94 1.10 1.00 1.16 1.05 1.00 1.00 0.96 1.06 1.01 1.12 1.07 1.
PERFORMANCE DATA 5.11 PXD-18 DCI 5.11.1 Cooling Capacity Factor - Unit D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.99 1.05 0.76 0.93 1.01 0.86 0.88 0.97 0.97 0.83 0.93 1.07 0.77 0.88 1.20 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.04 1.10 1.16 1.07 1.08 1.
PERFORMANCE DATA 5.11.3 Heating Capacity Factor - Unit D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/ WB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.46 0.70 0.60 0.79 0.71 0.86 0.76 0.89 0.80 0.32 0.80 0.47 0.89 0.58 0.96 0.63 0.99 0.67 PI 0.92 0.39 0.75 0.54 0.84 0.64 0.91 0.70 0.94 0.74 0.97 TC PI TC PI TC PI TC PI 1.07 0.95 1.12 0.97 1.18 0.99 1.00 1.00 0.93 1.05 0.99 1.07 1.04 1.
PERFORMANCE DATA 5.12 LS 35 DCI 5.12.1 Cooling Capacity Factors - Run Mode (Unit A,B,C or D) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC] OD COIL ENTERING AIR DB TEMPERATURE [ºC] -10 - 20 (protection range) 25 30 35 40 46 DATA TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 22/15 24/17 27/19 29/21 32/23 0.97 1.01 0.79 0.92 0.98 0.88 0.87 0.96 0.97 0.83 0.93 1.06 0.77 0.90 1.17 80 - 110 % of nominal 80 - 105 % of nominal 25 - 50 % of nominal 1.03 1.
PERFORMANCE DATA 5.12.3 Heating Capacity Factors - Unit A,B,C or D 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ºC] OD COIL ENTERING AIR DB/WB TEMPERATURE [ºC] DATA 15 20 25 TC PI TC PI TC PI TC PI TC 0.64 0.60 0.71 0.72 0.76 0.82 0.79 0.86 0.81 0.55 0.72 0.62 0.85 0.67 0.94 0.70 0.98 0.72 PI 0.89 0.59 0.66 0.66 0.78 0.72 0.88 0.75 0.92 0.76 0.95 TC PI TC PI TC PI TC PI 1.04 0.94 1.10 1.00 1.16 1.05 1.00 1.00 0.96 1.06 1.01 1.12 1.07 1.
PERFORMANCE DATA 5.13 Tubing Length Capacity Correction Factor (FT) - one way 5.13.1 Cooling Tubing Length Capacity Ratio - Cooling (1 Unit) 1.06 Capacity Ratio 1.01 0.96 0.91 0.86 0.81 0.76 0 5.13.2 5 10 15 Tubing Length [m] 20 25 30 25 30 Heating Tubing Length Capacity Ratio - Heating (1 Unit) 1.06 Capacity Ratio 1.01 0.96 0.91 0.86 0.81 0.
PERFORMANCE DATA 5.14 Model Correction Factors (FM) Model Capacity Power input Cooling Heating Cooling Heating WNG DCI 1.00 1.00 1.00 1.00 K DCI ECF DCI 1.03 1.07 1.01 1.10 PXD DCI TBD TBD TBD TBD LSDCI DCI LS TBD TBD TBD TBD 15.
PRESSURE CURVES 6. PRESSURE CURVES 6.1 Model: TRIO DCI 6.1.1 Cooling – Technician Mode Bar(g) Discharge Pressure - Cooling (Technician Mode) (WNG25+25+25 ; 5m each) 40.0 35.0 32/23 30.0 29/21 27/19 24/17 25.0 22/15 20.0 15.0 10 Bar(g) 15 20 25 30 Outdoor DB Temperature [ºC] 35 40 45 40 45 Suction Pressure - Cooling (Technician Mode) (WNG25+25+25 ; 5m each) 12.00 11.00 10.00 32/23 29/21 27/19 9.00 24/17 22/15 8.00 7.00 6.
PRESSURE CURVES 6.1.2 Heating – Technician Mode Discharge Pressure - Heating (Technician Mode) (WNG25+25+25 ; 5m each) Bar(g) 34.00 32.00 30.00 28.00 26.00 25 20 15 24.00 22.00 20.00 18.00 16.00 14.00 12.00 10.00 -15 -10 -5 0 5 10 15 20 Outdoor DB Temperature [ºC] Bar(g) Suction Pressure - Heating (Technician Mode) (WNG25+25+25 ; 5m each) 12.00 11.00 10.00 9.00 25 20 8.00 15 7.00 6.00 5.00 4.
PRESSURE CURVES 6.1.3 Tubing Length correction Factor Tubing Length Pressure Ratio - Cooling 1.02 1.01 1.01 Cooling Pd Cooling Ps 1.00 1.00 0.99 0.99 0.98 Discharge Pressure Ratio Suction Pressure Ratio 1.02 0.98 0 10 20 30 Total Tubing Lengtht [m] 40 50 1.02 1.01 1.01 1.00 1.00 Heating Ps 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.96 0.95 Discharge Pressure Ratio Suction Pressure Ratio Tubing Length Pressure Ratio - Heating 1.02 0.95 Heating Pd 0.94 0.94 0 6.1.
PRESSURE CURVES 6.2 Model: QUATTRO DCI 6.2.1 Cooling – Technician Mode Bar(g) Discharge Pressure - Cooling (Technician Mode) (WNG25+25+25+25 ; 5m each) 40.0 35.0 32/23 30.0 29/21 27/19 24/17 25.0 22/15 20.0 15.0 10 Bar(g) 15 20 25 30 Outdoor DB Temperature[ºC] 35 40 45 40 45 Suction Pressure - Cooling (Technician Mode) (WNG25+25+25+25 ; 5m each) 13.0 12.0 11.0 32/23 29/21 10.0 27/19 24/17 9.0 22/15 8.0 7.0 6.
PRESSURE CURVES 6.2.2 Heating – Technician Mode Bar(g) Discharge Pressure - Heating (Technician Mode) (WNG25+25+25+25 ; 5m each) 30.00 28.00 26.00 24.00 22.00 25 20 15 20.00 18.00 16.00 14.00 12.00 10.00 -15 Bar(g) -10 -5 0 5 Outdoor WB Temperature [ºC] 10 15 20 15 20 Suction Pressure - Heating (Technician Mode) (WNG25+25+25+25 ; 5m each) 12.00 11.00 10.00 9.00 25 20 8.00 15 7.00 6.00 5.00 4.
PRESSURE CURVES Tubing Length correction Factor (FT) Tubing Length Pressure Ratio - Cooling 1.02 1.01 1.01 Cooling Pd Cooling Ps 1.00 1.00 0.99 0.99 0.98 0.98 0 10 20 30 40 50 Total Tubing Lengtht [m] 60 70 Tubing Length Pressure Ratio - Heating 1.02 1.02 Suction Pressure Ratio 1.01 1.01 1.00 1.00 Heating Ps 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.96 0.95 0.95 Heating Pd 0.94 0.94 0 6-6 Discharge Pressure Ratio Suction Pressure Ratio 1.
PRESSURE CURVES 6.2.4 Outdoor Unit Code correction Factor (FC) Cooling Suction Discharge Pressure Pressure 1.00 1.00 1.02 1.01 1.04 1.01 1.05 1.02 1.07 1.02 ODU Code 4 4.5 5 5.5 6 6.3 Heating Suction Discharge Pressure Pressure 1.00 1.00 1.00 0.99 0.99 0.98 0.99 0.97 0.98 0.
ELECTRICAL DATA 7. ELECTRICAL DATA Power Supply Connected to Maximum Current Inrush Current 1 PH, 220-240 VAC, 50Hz Outdoor 16 A 35 A Starting Current Circuit breaker Power supply wiring - No. x cross section Interconnecting cable - No. x cross section 11 A 20 A 3 X 2.5 mm2 4 X 1.5 X 1.5 mm2 (For each IDU) Note: • Inrush current is the current when power is up. (charging the DC capacitors at outdoor PCB). • Starting current is the current at comp; start up.
WIRING DIAGRAMS 8. WIRING DIAGRAMS 8.
REFRIGERATION DIAGRAMS 9. REFRIGERATION DIAGRAMS 9.
TUBING CONNECTIONS 10. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 11-13 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8.
CONTROL SYSTEM 11. 11.
CONTROL SYSTEM 3URGXFW 2YHUYLHZ %ORFN 'LDJUDP Dry Cont acts 1ph/ 230V/ 50Hz Control Power 230V ac PFC Low voltage Power supply 380V dc 5V 3.
CONTROL SYSTEM 11.2.7 Dry Contacts Dry contacts are used to interface the system with an external building management system (BMS). Night input. Switches the system to night mode when closed. During night mode, the outdoor unit speed will be reduced in order to reduce the system noise level. SB input. System will be turned to Stand-by when the contact is closed. Power Shedding input. Limits the maximum power consumption when closed. Forced Mode input.
CONTROL SYSTEM 11.3 General Operating Rules 11.3.1 Initialization Initialization process is the first operation done each time power is up. The targets of the initialization are: Addressing of IDU’s Identification of connected IDU’s IDU Matching Check EEV’s homing (reset position) Restoring Parameters from EEPROM/Jumpers/Dipswitches 11.3.1.1 IDU’s Initialization 11.3.1.1.
CONTROL SYSTEM 11.3.2 Communication with Indoor Units 11.3.2.1 Communication Failures Definition Two types of communication failures are diagnosed. The communication failures are checked separately for each IDU channel. 11.3.2.1.1 ‘Bad Communication’ fault The system keeps a balance of a good/bad communication packet ratio for each active communication channel. When the ratio getting high , system enters ‘Bad Communication’ fault. 11.3.2.1.
CONTROL SYSTEM 11.4 11.4.1 Indoor Unit Control Indoor Fan Control 10 Indoor fan speeds are determined for each model. 5 speeds for each mode cool/dry/fan or heat. When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly at set speed. When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set according to the cool/heat load. 11.4.1.
CONTROL SYSTEM 11.4.3.2 Indoor Fan Control in Heat Mode Indoor fan speed depends on the indoor coil temperature: ICTST 11.4.4 ICTVL ICTL ICTH ICTT Auto Cool/Heat Mode When in auto cool heat mode unit will automatically select between cool and heat mode according to the difference between actual room temperature and user set point temperature (ΔT). Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3.
CONTROL SYSTEM 11.4.10 Indoor Unit Dry Contact Indoor unit Dry contact has two alternative functions that are selected by J8. Status J8 = Open J8 = Short 11.4.
CONTROL SYSTEM (Low) (Med) STBY OFF Cool SPT Heat SPT Auto SPT Fan SPT Dry SPT OFF OFF OFF ON OFF ON OFF ON OFF ON OFF ON OFF OFF User setting IFAN speed User setting IFAN speed User setting IFAN speed User setting IFAN speed User setting IFAN speed OFF ON ON OFF ON ON ON ON OFF ON OFF (High) OFF (Turbo) OFF (Auto) Backlight(red) Backlight(green) OFF OFF 11.4.12.
CONTROL SYSTEM 11.5 Run Mode Run mode is the default operation mode of the system. This is the standard operation mode that is active in field application (at customer site). System can go from run mode to other operation modes through keyboard or serial ports. 11.5.1 Mode Setting Mode defines the ODU operation mode. There are three possible operation modes: 1. STBY – standby mode 2. COOL - the unit operating at cooling cycle 3.
CONTROL SYSTEM 11.5.2 Compressor Speed Control 11.5.2.1 Compressor Min On/Off time Compressor minimum OFF time is MinOFFTime minutes except during Deicing protection. Compressor minimum ON time is MinOnTime minutes, minimum ON time is ignored during protections, and when unit is turned to STBY. 11.5.2.
CONTROL SYSTEM 11.5.2.5 Speed Step Limitations 11.5.2.5.1 Step 1 and step 2 The compressor speed cannot go below Step1RPS or above Step2RPS during 3 continuous minutes once after the compressor starts up when the ODU unit changes from STBY 11.5.2.5.2 Step 3 limit The speed cannot go higher than Step3RPS unless it was operating for more than 1 continuous minute between Step3RPS – 5 and Step3RPS. 11.5.3 EEV Control 11.5.3.
CONTROL SYSTEM EEV Opening 60 200 Change to Idle 11.5.3.4 EEV is initialized by current EEV opening + 20 and defined as 0. EEV Opening Determination The target EEV value is the sum of open loop value (OL) and a result of the accumulative correction values (CV). EEVi EEVOLi EEVCVi EEVi is the EEV opening for each ‘i’ IDU. 11.5.3.
CONTROL SYSTEM 11.5.4 Outdoor Fan Speed Control 11.5.4.1 General Rules o OFAN operates between OFMinRPM to OFMaxRPM. o Min time for speed change of OFAN OFMinTimeReduce (60 seconds). There are 4 defined speeds – High, Med, Low, and Very Low. The actual OFAN speeds are defined according to the following table: Speed High Med Low VLow COOL 700 600 450 300 HEAT 700 600 450 250 The fan speed is also related to compressor speed, outdoor temperature and to protections. 11.5.4.
CONTROL SYSTEM Base Heater OFF ON 0 OAT 2 When OAT is faulty the base heater will be “ON” continuously in HEAT mode. 11.5.7 Thermodynamic Protections 11.5.7.1 Protection level definition Five protection levels are defined: Normal – No protection status is ON. Stop-Rise (SR) – System is in protection, first level D1 - System is in protection, second level D2 - System is in protection third level Stop-Compressor (SC) – System is in protection fourth level 11.5.7.
CONTROL SYSTEM 11.5.7.3.2 Indoor Coil over Heating Protection ICT Trend ICT ICT > 55 53 < ICT ≤ 55 49 < ICT ≤ 53 47 < ICT ≤ 49 45 < ICT ≤ 47 43 < ICT ≤ 45 ICT ≤ 43 11.5.7.
CONTROL SYSTEM OAT – Outdoor Air Temperature TLD – Time from Last Deicing DI – Deicing Interval (Time Interval between Two Deicing) DST – Deicing static threshold (Temperature) Deicing interval time when compressor is first started in heat mode, is 10 minutes if OCT < -2, and is 40 minutes in other cases. Deicing interval time is changed (increased/ decreased in 10 minutes steps) as a function of deicing time. If deicing time is shorter then former deicing time, the deicing interval time will be increased.
CONTROL SYSTEM 0 1 L4 Water Level LEVEL4 LEVEL2&3 LEVEL1 ON Pump OFF ANY NLOAD 0 BLINK OPER LED NORMAL 11.5.9.
CONTROL SYSTEM 11.6 Installation Test Mode See “A APPENDIX”. 11.7 Technician Test Mode This test is aimed for the technicians to check the system under a preset compressor and outdoor fan values while the expansion valves will function according to the normal running mode. 11.7.1 o Entering technician mode This mode is entered through the outdoor unit using the HMI (refer to user interface section). o It can be selected either for cool or heat.
CONTROL SYSTEM 11.8 11.8.1 User Interface User interface description o The user interface uses three 7 segments, and 4 keys. o Keys, The 4 keys are: - Scroll - used to scroll between options (up and down) Up - Select - use to select an option - Escape - Will go up one level in the menu o The user interface concept is Tree menus. Esc o Active selection or status will be indicated by a dot at the Select Down right side of the third digit. 11.8.
CONTROL SYSTEM 11.8.3 Menus 11.8.3.
CONTROL SYSTEM o Technician Test mode is exited after 60 minutes from entry. o All the menus, except technician menus- Parameter changing, Status, Technician Test and their sub menus, are automatically exited to the main menu after 1 continuous minute out of any press. o When Technician test cool or heat menu is selected, it will blink constantly until this menu is escaped.
CONTROL SYSTEM 11.8.3.
CONTROL SYSTEM Notes: For the temperature display, when a thermistor is shorted or disconnected it shows FLT (FLt), when it is disabled it shows DIS (dis). It’s possible to present a number between 999 and 99,999 by alternating between two numbers (each number is presented for 1 second). The two numbers format is "xx, yyy". Pressing select + escape together for 5 seconds will reset the counter to 0. The compressor time is measured in hours. 11.9 11.9.
CONTROL SYSTEM 11.10.3 Compressor Parameters Compressor Parameters MinOFFTime MinOnTime MaxSpeedC MaxSpeedH Step1RPS Step2RPS Step3RPS 11.10.4 Value 3 3 75 95 40 60 75 OFAN parameters EEV Parameters OFMinRPM OFMaxRPM NightRPM OFMinTimeReduce (Sec) OFLowSpC OFMedSpC OFLowSpH OFMedSpH 11.10.5 Value 150 1000 650 60 35 50 40 65 Indoor Units SW Parameters 11.10.5.
CONTROL SYSTEM 11.10.5.
TROUBLESHOOTING 12. TROUBLESHOOTING WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 1 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock!!! For safe handling of the controller please refer to section 12.5 below. 12.
TROUBLESHOOTING No SYMPTOM PROBABLE CAUSE Indoor coil block Outdoor coil block 11. Compressor is over heated and unit does not generate capacity EEV problem Refrigerant leakage Indoor coil block Outdoor coil block 12. Compressor stops during operation 13. Not all units are operating 14. Compressor does not start 15. Unit works in wrong mode (cool instead of heat or heat instead of cool) 16. 17. 18. 19. 20. 21. 22.
TROUBLESHOOTING No Fault Name Fault Description Corrective Action 10 OFAN- Vospd exceeded Exceeds speed high limit Check motor type matches motor jumpers in controller Make necessary arrengments in unit installation location to avoid back wind Avoid EMC problems (12.4.10.1) 11 Compressor- IPM Fault Over current / Over temperature of compressor IPM Check no obstruction to controller air opening Check Compressor (12.4.5) 12 Compressor Lock Compressor does not rotate Check Compressor (12.4.
TROUBLESHOOTING 12.3.2 Fault Code for Indoor unit Pressing Mode button for long will activate diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LED’s. When Indoor diagnostics is displayed, all four LED’s (STBY, Operate, Filter, TMR) are on. Entering diagnostics in STBY mode allows only viewing of status (fault-display). In diagnostic mode, system problems / information will be indicated by blinking of Heat & Cool LED’s.
TROUBLESHOOTING 12.3.3 No. Indoor unit diagnostics and corrective actions Probable Cause Fault 1-4 Sensor failures 7 Communication mismatch 8 No Communication 9 No Encoder Indoor electronics or motor 11 17-21 Outdoor Unit Fault Protections Outdoor controller problem Indication 24 EEPROM Not Updated System is using ROM parameters and not EEPROM parameters 25 Bad EEPROM 26 Bad Communication 27 28-31 Using EEPROM data IDU model 12.4 12.4.
TROUBLESHOOTING The normal value should be between 10 to 20 . Change to Stand-by or Power OFF and re-start - If the fault is still active - replace controller. 12.4.5 Checking the Compressor Check Compressor connections - Repair if needed. Use a current probe (“Clamp”) to assure that there is an AC current on each phase – no more than 15A. In case there is no current, check the resistance between the three poles. Assure the three coil resistances are almost the same (between 0.8 to 1.5 ).
TROUBLESHOOTING (insulate for noise or distance from the noise source): 1. Use shielded wires. 2. Move unit away from the noise source. 12.4.10.2 EMC troubles to near by home appliances Locations most susceptible to noise : 1. A television or radio is located near the A/C and A/C wiring. 2. The antenna cable for a television or radio is located close to the A/C and A/C wiring. 3. Locations where television and radio signals are weak. Trouble : 1.