Service manual
RATING CONDITIONS
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units)
and EN 14511.
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating Limits
Indoor Outdoor
Upper limit 32
o
C DB 23
o
C WB 46
o
C DB
Cooling
Lower limit 21
o
C DB 15
o
C WB -10
o
C DB
Upper limit 27
o
C DB 24
o
C DB 18
o
C WB
Heating
Lower limit 10
o
C DB -15
o
C DB -16
o
C WB
1PH 198 – 264 V
Voltage
3PH N/A
Service Manual - Trio_Quattro DCI Revision Y05-01 3-1