Service manual

-
PERFORMANCE DATA
5.8 ECF 18 DCI
5.8.1 Cooling Capacity Factor - Unit D
230[V] : Indoor Fan at High Speed.
ID COIL ENTERING AIR DB/WB TEMPERATURE [ºC]
OD COIL
ENTERING AIR DB DATA
22/15 24/17 27/19 29/21 32/23
TEMPERATURE [ºC]
-10 - 20
(protection range)
TC
SC
PI
80 - 110 % of nominal
80 - 105 % of nominal
25 - 50 % of nominal
TC 0.99 1.04 1.10 1.16 1.22
25 SC 1.05 1.07 1.08 1.10 1.11
PI 0.76 0.77 0.79 0.81 0.82
TC 0.93 0.99 1.05 1.11 1.17
30
SC 1.01 1.03 1.04 1.06 1.07
PI 0.86 0.88
0.90
0.91 0.93
TC 0.88 0.94
1.00
1.06 1.12
35
SC 0.97 0.98 1.00 1.02 1.03
PI 0.97 0.98
1.00
1.02 1.03
TC 0.83 0.89
0.95
1.01 1.07
40
SC 0.93 0.94 0.96 0.97 0.99
PI 1.07 1.09 1.11 1.12 1.14
TC 0.77 0.83 0.89 0.95 1.00
46
SC 0.88 0.89 0.91 0.93 0.94
PI 1.20 1.21 1.23 1.25 1.27
LEGEND
TC Total Cooling Capacity, kW
SC –
Sensible Capacity, kW
PI Power Input, kW
WB Wet Bulb Temp., (
o
C)
DB Dry Bulb Temp., (
o
C)
ID Indoor
OD Outdoor
5.8.2 Capacity Correction Factors
i io
27/19
22/15
24/17
29/21
32/23
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
Capac t y Rat
20 25 30 35 40 45 50
Outdoor Temperature [deg C]
Revision 0 5-15