Service manual

CONTROL SYSTEM
11.6 Installation Test Mode
See “A APPENDIX.
11.7 Technician Test Mode
This test is aimed for the technicians to check the system under a preset compressor and
outdoor fan values while the expansion valves will function according to the normal running
mode.
11.7.1 Entering technician mode
o This mode is entered through the outdoor unit using the HMI (refer to user interface
section).
o It can be selected either for cool or heat.
o Technician test is not possible to enter during deicer.
11.7.2 Technician mode procedure
All the connected indoor units will enter technician test at high indoor fan speed.
The outdoor unit will be working normally (according to the run mode control logic) except
the following changes:
o The dry contacts inputs will be ignored.
o Protections will be operative for stop compressor (not to be implemented in the current
version).
o The compressor and the outdoor fan will be working in target preset values according to the
following tab
le:
Technician Test
Unit
Compressor Speed
OFAN speed
Cool Heat
Trio 60 75 High s
peed
Quattro 60 75 High s
peed
11.7.3 Exiting technician mode
Technician mode will be exited either when:
o Escaping by the HMI (exiting the ttC
or ttH menus)
o 60 minutes are passed from entering
Revision 0
11-19