Service manual
CONTROL SYSTEM
Notes:
For the temperature display, when a thermistor is shorted or disconnected it shows FLT
(FLt), when it is disabled it shows DIS (dis).
It’s possible to present a number between 999 and 99,999 by alternating between two
numbers (each number is presented for 1 second). The two numbers format is "xx, yyy".
Pressing select + escap
e together for 5 seconds will reset the counter to 0.
The compressor time is measured in hours.
11.9 Jumper settings
11.9.1 Jumper definitions
0 = open (disconnected)
1 = closed (shorted)
11.9.2 OFAN Jumpers
OFAN use parameters J2 J1
Panasonic- EHD80 0 0
Nidec SIC-71FW-F170-1 0 1
Shinano 1 0
EEPROM 1 1
11.9.3 Compressor Jumpers
Compressor use parameters J3
TNB220FLBM (ROM) 0
EEPROM 1
11.10
11.10.1
Default Value
imit
6
11.10.2
System Parameters
General parameters
Parameter
ODUCodeL
Protection Parameters
Deicer Parameters
Parameter Default
DST
8
DSTF
12
DIF (min)
30
CTMR (min)
15
TimeD (min)
1
DIT (min)
10
DTmin (min)
3
DImin (min)
30
DImax (min)
120
DeicSPChRV
0
EEVDeicerOpen
180
DEICT1 (sec)
50
DEICT2 (sec)
36
DEICT3 (sec)
6
OptimDeicSP
90
11-24
Revision 0