1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4. INSTALLATION OF THE INDOOR UNIT 5. CONDENSATE HOSE CONNECTION 6. ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT 7. REFRIGERANT TUBING 8.
I N S TA L L AT I O N I N S T R U C T I O N S FOR DCI SPLIT WALL MOUNTED AIR CONDITIONER 1 ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER Shape Name Qty Used for 2 LOCATION OF INDOOR AND OUTDOOR UNIT Select the location considering the following: INDOOR UNIT Mounting plate 1 Remote control with batteries 1 Remote control bracket 1 Screws washer dowels 4 Wall mounting of the indoor unit Operation of unit Wall mounting of the remote control Wall mounting of indoor unit 1.
950mm 1800mm 80 mm min Fig. 3 50 mm min 50 mm min 2300 mm min To remove 2 100 mm min 1 100 mm min 400 mm min To attach Fig. 4 500 mm min 100 mm min NOTE: Distance between indoor and outdoor units should be 30m. Height difference between indoor and outdoor units should be 15m. No additional charge is required. 1 Fig. 5 Fig.5 1.
3 INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) CAUTION New Refrigerant Air Conditioner Installation THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER. R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed.
4 INSTALLATION OF THE INDOOR UNIT INSTALLATION OF THE MOUNTING PLATE 1. Figure 9 shows the location of the mounting plate relative to the unit size. Refer to one of the drawings, according to your unit length (marked in square). REMOVAL AND INSTALLATION OF THE 2. Locate the mounting plate as shown on the wall in a horizontal FRONT PANEL position, using a spirit level. 3. Mark the position of the four mounting holes on the wall and drill four holes to accommodate the dowels. 4.
SUSPENDING AND RELEASING THE UNIT FROM THE MOUNTING PLATE 1. Make sure that the refrigerant tubes, electric cables and condensate water hose are well insulated with closed cell rubber based insulating tubes (6mm thickness), are wrapped together with UV stabilized nonadhesive plastic tape, and are passed through the hole in the wall. 2. Hang the indoor unit on the two hooks that are located near the top edge of the mounting plate as shown in fig. 10 and fig. 11. 3.
6 ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT Power input cable ELECTRICAL REQUIREMENTS Electrical wiring and connections should be made by qualified electricians and in accordance with local electrical codes and regulation. The air conditioner units must be grounded. The air conditioner unit must be connected to an adequate power outlet from a separate branch circuit protected by a time delay circuit breaker, as specified on unit's nameplate.
7 Tightening torques of unions and valve caps: REFRIGERANT TUBING CONNECT THE INDOOR TO THE OUTDOOR UNIT The indoor unit contains a small quantity of nitrogen. Do not unscrew the nuts from the unit until you are ready to connect the tubing. The outdoor unit is supplied with sufficient refrigerant charge (R410A). Refer to outdoor unit nameplate. Fig. 20 NOTE: Use refrigeration R410A type copper tubing only. 2. Use tubing diameter that corresponds to the tubing diameter of the indoor and outdoor units.
),1$/ 7$6.