Specification Sheet

45
Model
eiQ-SSRFC48K-V4
eiQ-SSRFC60K-V4
Indoor Rated voltage and frequency (Ph-V-Hz)
N/A
N/A
Outdoor Rated voltage and frequency (Ph-V-Hz)
380~415/3/50
380~415/3/50
Indoor Fuse Required
N/A
N/A
Outdoor Fuse Required
20A
20A
Mode
Cooling
Heating
Cooling
Heating
Rated capacity (KW)
14.0 (7.0-15.5)
15.2 (8.0-16.0)
16.0(7.5-17.0)
16.8 (8.5-17.5)
Power input (W)
4950 (1100-5800)
4920 (1200-6000)
5900 (1400-6300)
5460 (1500-6500)
Current input (A)
2.8-14.6
3.0-15.0
3.5-15.8
3.7-16.3
SEER/SCOP(W/W)
6.1 / A++
4.0 / A+
6.1 / A++
4.0 / A+
Nominal load (kW)
14.000
11.500
16.000
12.000
Balance point temperature heating (
o
C)
-
-7
-
-7
Min. outdoor operating temperature (
o
C)
-15
-15
-15
-15
Thermostat-off mode (W)
101
23.9
128
23.6
Standby mode (W)
3
3
Off mode (W)
3
3
Annual consumption (kW)
795
3723
911
4046
Copper Pipe Type length
-
-
Liquid side / Gas side (mm/inch)
Φ9.52/Φ15.88
Φ9.52/Φ15.88
Max. refrigerant pipe length
65
65
Max. elevation
30
30
Interconnecting Cable
4 x 2.5mm
2
4 x 2.5mm
2
Moisture Removal (L/h)
5.08
7.96
Indoor
Air Flow (m
3
/h)
1900
2000
Body Dimensions (L*W*H) (mm)
840x285x840
840x285x840
Panel Dimensions (L*W*H) (mm)
950x50x950
950x50x950
Body Packaging (L*W*H (mm)
920x310x920
920x310x920
Panel Packaging (L*W*H (mm)
1030x100x1030
1030x100x1030
Body Net / Gross weight (Kg)
29/34
29/34
Panel Net / Gross weight (Kg)
6.5/9.5
6.5/9.5
Noise Sound pressure level (dB/A)
45-52
45-52
Noise Sound power level (dB/A)
56-63
56-63
Outdoor
Dimension (L*W*H) (mm)
1014x1430x450
1014x1430x450
Packaging (L*W*H) (mm)
1095x485x1545
1095x485x1545
Net / Gross Weight (Kg)
109/123.6
112/126.6
Noise Sound pressure level (dB/A)
58
58
Noise Sound power level (dB/A)
70
70
Refrigerant type/weight
R32 / 3800g
R32 / 3800g
Defrost mode
Automatic defrosting
Automatic defrosting
Applicable climate types
Cooling (-15
o
C 50
o
C)
Heating(-15
o
C 30
o
C)
Cooling (-15
o
C 50
o
C)
Heating(-15
o
C 30
o
C)
Due to continuous product development process specification may change.
These units contain a gas governed by F-Gas regulations. The gas must be handled by qualified F-Gas engineers.