User and Installation Manual

30
Notes:
1. The height of the installed unit is
recommended to be > 200 cm.
2.
Either the indoor unit or the outdoor
unit can be higher, but the height
difference must comply with a max.
5 metres level difference.
3. Try to avoid bending the pipes as
much as possible so as to avoid
possible negative impacts upon the
performances of the unit.
INSTALLATION OF THE OUTDOOR UNIT
Try to move the product to the installation location in its original packaging
As the gravity center of the unit is not at the installation center, special caution should be taken
when using hoisting cables to lift it up
During transport, the outdoor unit must not be tilted to over 45 degrees (also do not store the unit
horizontally.
Use expansion bolts to fix the mounting supports on the wall;
Use bolts and nuts to fix the outdoor unit firmly on the supports and keep on the same level;
If the unit is installed on the wall or at the rooftop, the supports have to be firmly fixed so as to
resist earthquakes or strong wind.
Dimensions for parallel units installations
300mm(1')min
CONDENSATE DRAINAGE OF THE OUTDOOR UNIT
When operating in heating mode condensate
will collect and drain through the base of the
outdoor unit. The air conditioner is supplied with
an elbow joint which can be connected to the
underside of the outdoor unit for drainage.
1. Connect the elbow joint to the drainage
hole on the underside of the outdoor unit.
2. Connect a drain hose (not supplied) to the
elbow joint and run downhill to your chosen
drainage point.
Please note: The drainage is gravity fed, and so
must run downhill.