EB-M Spec Sheet
TS COMMERCIAL SERIES
WATER FLOW REQUIREMENTS (MINIMUM 4 GPM WATER FLOW THROUGH BOILER)
Model
Water Temperature Rise
Flow - 20° F/6° C
Head Loss
Flow - 30° F/11° C
Head Loss
Flow - 40° F/16° C
Head Loss
gpm lpm ft m gpm lpm ft m gpm lpm ft m
EB-CX-18-60 6.14 23.24 .002 .0006 4.09 15.48 .001 .0003
3.07
†
11.62
†
.0008 .0002
EB-CX-24-60 8.19 31.00 .002 .0006 5.46 20.66 .001 .0003 4.09 15.48 .0008 .0002
EB-CX-30-60 10.23 38.72 .06 .018 6.82 25.81 .07 .021 5.11 19.34 .07 0.21
EB-CX-36-60 12.28 46.49 .01 .003 8.19 31.00 .004 .001 6.14 23.24 .002 .0006
EB-CX-45-60 15.35 58.10 .02 .006 10.23 38.72 .01 .003 7.67 29.03 .01 .003
EB-CX-54-60 18.43 69.77 .02 .006 12.28 46.49 .01 .003 9.21 34.86 .01 .003
EB-CX-18-48 6.14 23.24 .002 .0006 4.09 15.48 .001 .0003 3.07 11.62 .0008 .0002
EB-CX-24-48 8.18 31.00 .002 .006 5.45 20.66 .002 .006 4.05 15.33 .002 .006
EB-CX-30-48 10.23 38.72 .06 .018 6.82 25.81 .06 .018 5.11 19.34 .06 .018
EB-CX-36-48 12.28 46.49 .01 .003 8.19 31.00 .004 .001 6.14 23.24 .002 .0006
EB-CX-42-48 14.33 54.24 .02 .006 9.55 36.15 .02 .006 7.16 27.1 .02 .006
EB-CX-48-48 16.37 61.97 .02 .006 10.91 41.3 .02 .006 8.18 30.96 .02 .006
EB-CX-54-48 18.43 69.77 .02 .006 12.28 46.49 .01 .003 9.21 34.86 .01 .003
EB-CX-27-20 9.21 34.86 .01 .003 6.14 23.24 .002 .0006 4.60 17.41 .001 .0003
EB-CX-31-20 10.74 40.66 .01 .003 7.16 27.1 .01 .003 5.37 20.33 .01 .003
EB-CX-36-20 12.28 46.48 .01 .003 8.18 30.96 .01 .003 6.14 23.24 .01 .003
EB-CX-40-20 13.82 52.32 .01 .003 9.21 34.86 .01 .003 6.91 26.16 .003 .0009
EB-CX-27-24 9.21 34.86 .01 .003 6.14 23.24 .002 .0006 4.60 17.41 .001 .0003
EB-CX-31-24 10.74 40.66 .01 .003 7.16 27.1 .01 .003 5.37 20.33 .01 .003
EB-CX-36-24 12.28 46.48 .01 .003 8.18 30.96 .01 .003 6.14 23.24 .01 .003
EB-CX-40-24 13.82 52.32 .01 .003 9.21 34.86 .01 .003 6.91 26.16 .003 .0009
EB-CX-31 10.75 40.69 .06 .018 7.16 27.10 .07 .021 5.37 20.33 .07 .021
EB-CX-36 12.28 46.49 .06 .018 8.19 31.00 .06 .018 6.14 23.24 .07 .021
EB-CX-40 13.65 51.67 .01 .003 9.10 34.44 .01 .003 6.82 25.81 .003 .0009
EB-CX-44 15.01 56.82 .02 .006 10.01 37.89 .01 .003 7.50 28.39 .01 .003
†
Result below minimum required fl ow of boiler, make sure system design provides minimum fl ow requirements of boiler.
Note: Head Loss based on 110° F return temperature.
STANDARD EQUIPMENT
Staging - EB-CX-**
▪ Supply water sensing
▪ Regulates to front panel selected temperature
▪ Staging indicator lights
▪ Heavy duty contactors
▪ Hi-limits: 1
st
- automatic reset at 190° F
2
nd
- manual reset at 205° F
▪ Circulator switching relay - 10-amp maximum
▪ Thermostat or end switch connection (R and W)
▪ Utility load control provisions
▪ 13.1 gl. Steel vessel ASME “H” Stamp (20-year
warranty)
▪ Supply temperature/pressure gauge
▪ Safety relief valve (30 PSI)
▪ Standby switch and boiler contact
▪ Outdoor reset capability
).
/54
-/5.44()3
%.$50
MINIMUMCLEARANCE
FROMFLOOR
#/.$5)4
8
.04
.04
#/.$5)4
#/.$5)4
8
IN
DIMENSIONSARE
MM
DRAIN