Submittal Manual

06/16/2009 BL509
STANDARD EQUIPMENT
PROJECT INFORMATION
Submittal Data Sheet - TS Series Midsize Electro-Boiler
TM
Job Name: ________________________________ Part No. Ordered: __________________________
Location: _________________________________ PO Number: ______________________________
_________________________________________
Engineer: _________________________________ Date Submitted: ___________________________
Contractor: ________________________________
Mfg. Rep: _________________________________
Specifi cations subject to change without notice,
all rights reserved.
WATER FLOW REQUIREMENTS (MINIMUM 2 GPM WATER FLOW THROUGH BOILER)
Model
Water Temperature Rise
Flow - 10° F/6° C Head Loss Flow - 20° F/11° C Head Loss Flow - 30° F/16° C Head Loss
gpm lpm ft m gpm lpm ft m gpm lpm ft m
EB-M*-10 6.82 25.82 .01 .003 3.41 12.91 .004 .001 2.27 8.59 .001 .001
EB-M*-15 10.23 38.73 .03 .009 5.11 19.34 .01 .003 3.41 12.91 .004 .001
EB-M*-20 13.65 51.66 .07 .02 6.82 25.01 .02 .006 4.55 17.22 .01 .003
* = S, A, or O
Note: Head Loss based on 110° F return temperature.
ELECTRIC SUPPLY
Model Volts Watts Amps kW Phase Btu/h CB
EB-M*-10 240 10,000 41.66 10 1-60 34,130 60
EB-M*-15 240 15,000 62.50 15 1-60 51,195 60 + 30
EB-M*-20 240 20,000 83.33 20 1-60 68,260 60 + 60
* = S, A, or O
Staging - EB-MS-**
Supply water sensing
Regulates to front panel selected temperature
Staging indicator lights
DC Power Relays
Hi-limits: 1
st
- automatic reset at 190° F
2
nd
- manual reset at 205° F
Circulator switching relay - 10-amp maximum
Thermostat or end switch connection (R and W)
Utility load control provisions
2.2 gl. Steel vessel ASME “H” Stamp (20-year warranty)
Supply temperature/pressure gauge
CLEARANCES
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 12 INCHES 305 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 18 INCHES/457 MM
Safety relief valve (30 PSI)
Optional standby boiler control kit, plug-in
Standby switch and boiler contact
Modulating - EB-MA-**
Same as EB-MS-**
PLUS
Modulates at a tighter temperature control
Standby control package
Modulating - EB-MO-**
Same as EB-MA-**
PLUS
Outdoor sensing with outdoor reset capability. The target supply
temperature ramps up as it is colder outside.