EB-NB Spec Sheet
Specification Data Sheet - Industrial Electro-Boiler
TM
Electric Hot Water Boiler Series
STANDARD EQUIPMENT
▪ Pressure vessel built in accordance with the requirements of the ASME Boiler and Pressure Vessel Code
(National Board and CRN registered)
▪ Meets the requirements of ASME CSD-1
▪ ASME pressure relief valve, 30 psi (125 psi optional, must
specify when ordering)
▪ Low water cut-off with manual reset
▪ Auto reset hi-limit control, 210° F
▪ Manual reset hi-limit, 220° F
▪ Pressure/temperature gauge
▪ Circuit breaker or fuse protection on each stage
▪ Integrated ½” air vent
▪ 3” NPT inlet and outlet
▪ 3” inspection opening
▪ Safety door interlock and lockable door latch
▪ Emergency shut-down connection point
▪ Digital temperature control with display
▪ Supply and return water temperature sensing
▪ Outdoor reset, fi eld confi gurable
▪ Stage active indicator lights
▪ 0-10VDC confi gurable for building boiler control
▪ Multi-boiler lead/lag control
▪ SCCR rated at 5 kV
OPTIONS
▪ 125 psi vessel
▪ BACnet or LonWorks interface
▪ Bender fault monitor
▪ T775R controller
All specifi cations subject to ELECTRO INDUSTRIES STANDARD TERMS
AND CONDITIONS, download at www.electromn.com/terms.pdf.
Monticello, Minnesota
800.922.4138
www.electromn.com