Industrial Electro Boilers Large Specifications Sheet

10/22/2010 BL801
Specifi cations subject to change without notice, all rights reserved.
Electric Supply
Model Volts kW
Amps 3-Phase
Watts
Element
Quantity
Steps
Btu/h
Output
Flow Rate
@20°∆T
Boiler
Weight
Feed #1
Feed #2
Min
GPM
Max
GPM
EB-NB-72-600 600 72 69 - 72,000 6 6 @ 12 245,736 4 21 685
EB-NB-84-600 600 84 81 - 84,000 7 7 @ 12 286,692 4 29 695
EB-NB-108-600 600 108 92 12 108,000 9 9 @ 12 368,604 4 37 700
EB-NB-120-600 600 120 92 23 120,000 10 10 @ 12 409,560 4 41 705
EB-NB-144-600 600 144 92 46 144,000 12 12 @ 12 491,472 4 49 710
EB-NB-160-600 600 160 154 - 160,000 8 8 @ 20 546,080 7 55 695
EB-NB-200-600 600 200 154 38 200,000 10 10 @ 20 682,600 7 68 700
EB-NB-240-600 600 240 154 77 240,000 12 12 @ 20 819,120 7 82 705
EB-NB-300-600 600 300 154 135 300,000 15 15 @ 20 1,023,900 7 102 710
EB-NB-84-480 480 84 101 - 84,000 7 7 @ 12 286,692 4 29 695
EB-NB-108-480 480 108 116 15 108,000 9 9 @ 12 368,604 4 37 700
EB-NB-120-480 480 120 116 29 120,000 10 10 @ 12 409,560 4 41 705
EB-NB-144-480 480 144 116 58 144,000 12 12 @ 12 491,472 4 49 710
EB-NB-160-480 480 160 193 - 160,000 8 8 @ 20 546,080 7 55 695
EB-NB-200-480 480 200 193 48 200,000 10 10 @ 20 682,600 7 68 700
EB-NB-240-480 480 240 193 96 240,000 12 12 @ 20 819,120 7 82 705
EB-NB-300-480 480 300 193 169 300,000 15 15 @ 20 1,023,900 7 102 710
EB-NB-60-208 208 60 167 - 60,000 4 4 @ 15 204,780 5 21 716
EB-NB-75-208 208 75 209 - 75,000 5 5 @ 15 255,975 5 26 721
EB-NB-105-208 208 105 292 - 105,000 7 7 @ 15 358,365 5 36 721
EB-NB-150-208 208 150 292 125 150,000 10 10 @ 15 511,950 5 50 731
EB-NB-180-208 208 180 292 210 180,000 12 12 @ 15 614,340 5 61 737
EB-NB-60-240 240 60 145 - 60,000 4 4 @ 15 204,780 5 20 716
EB-NB-75-240 240 75 181 - 75,000 5 5 @ 15 255,975 5 26 721
EB-NB-105-240 240 105 253 - 105,000 7 7 @ 15 358,365 5 36 721
EB-NB-150-240 240 150 289 73 150,000 10 10 @ 15 511,950 5 51 731
EB-NB-180-240 240 180 289 145 180,000 12 12 @ 15 614,340 5 61 737
Actual calculated amps, not service rating.
Options
EB-N-GFM-KIT - Ground fault monitor kit. Add this kit to your order for installations utilizing a dedicated utility transformer
designed to be used as a 3-wire Delta service, with unbonded neutral.
5600 - Honeywell, T775R, electronic stand-alone operating control.