EB-NB Installation Manual

12/28/2018 16 BI804
SENSOR CALIBRATION
Use “ENTER” Button to increase value of digit selected.
Use UP and DOWN buttons to move curser up and down
Use LEFT and RIGHT buttons to move curser left and right
OFFSET ST: If there is a need to calibrate the supply temperature sensor, enter in the desired offset.
NOTE: The value entered is the offset, not sensor temperature. Pressing 075° will add 75° to the
existing sensor reading. It will not cause the sensor to now equal 075°.
OFFSET RT: If there is a need to calibrate the return temperature sensor, enter in the desired offset.
NOTE: The value entered is the offset, not sensor temperature. Pressing 075° will add 75° to the
existing sensor reading. It will not cause the sensor to now equal 075°.
OFFSET OT: If there is a need to calibrate the outdoor temperature sensor, enter in the desired offset.
NOTE: The value entered is the offset, not sensor temperature. Pressing 075° will add 75° to the existing
sensor reading. It will not cause the sensor to now equal 075°.