Spec Sheet
02/09/2016 BL506
STANDARD EQUIPMENT
Specification Data Sheet - TS Standard Electro-Boiler
TM
Specifi cations subject to change without notice,
all rights reserved.
* 20-year warranty does not apply to 3-phase models.
WATER FLOW REQUIREMENTS (MINIMUM 2 GPM WATER FLOW THROUGH BOILER)
Model
Water Temperature Rise
Flow - 10° F/6° C Head Loss Flow - 20° F/11° C Head Loss Flow - 30° F/16° C Head Loss
gpm lpm ft m gpm lpm ft m gpm lpm ft m
EB-**-13 9.21 34.86 .03 .009 4.60 17.41 .01 .003 3.07 11.62 .004 .001
EB-**-18 12.28 46.49 .06 .018 6.14 23.24 .02 .006 4.09 15.48 .01 .003
EB-**-23 15.35 58.11 .09 .027 7.67 29.03 .02 .006 5.11 19.34 .01 .003
EB-**-27 18.43 69.77 .13 .039 9.21 34.86 .03 .009 6.14 23.24 .02 .006
EB-WX-13-2 9.21 34.86 .03 .009 4.60 17.41 .01 .003 3.07 11.62 .004 .001
EB-WX-27-2 18.43 69.77 .13 .039 9.21 34.86 .03 .009 6.14 23.24 .02 .006
** = S or WX
Note: Head Loss based on 110° F return temperature.
ELECTRIC SUPPLY
Model Volts Watts Amps kW Phase Btu/h
CB
†
EB-**-13 240 13,500 56 13.5 1-60 46,075 60 + 30
EB-**-18 240 18,000 75 18 1-60 61,434 60 + 60
EB-**-23 240 22,500 94 22.5 1-60 76,792 60 + 60 + 30
EB-**-27 240 27,000 113 27 1-60 92,151 60 + 60 + 60
EB-WX-13-2 208 13,500 37.5 13.5 3-60 46,075 50
EB-WX-27-2 208 27,000 75 27 3-60 92,151 100
** = S or WX
†
Canadian models include single feed bus option where applicable.
SHIPPING WEIGHT
Model Weight (lbs)
EB-**-13 150
EB-**-18 152
EB-**-23 153
EB-**-27 155
EB-WX-13-2 150
EB-WX-27-2 155
Staging - EB-S-**
▪ Supply water sensing
▪ Regulates to front panel selected temperature
▪ Staging indicator lights
▪ DC Power Relays
▪ Hi-limits: 1
st
- automatic reset at 190° F
2
nd
- manual reset at 205° F
▪ Circulator switching relay - 10-amp maximum
▪ Thermostat or end switch connection (R and W)
▪ Utility load control provisions
▪ 6.5 gl. Steel vessel ASME “H” Stamp (20-year warranty*)
▪ Supply temperature/pressure gauge
CLEARANCES
MINIMUM CLEARANCE FROM SUGGESTED MINIMUM
COMBUSTIBLE SURFACES SERVICE CLEARANCE
BACK 0 INCH 0 MM 0 INCH 0 MM
LEFT 1 INCH 25 MM 12 INCHES 305 MM
RIGHT 1 INCH 25 MM 6 INCHES 152 MM
FRONT 1 INCH 25 MM 24 INCHES 610 MM
TOP 1 INCH 25 MM 24 INCHES 610 MM
BOTTOM REQUIRED CLEARANCE - 16 INCHES/406 MM
▪ Safety relief valve (30 PSI)
▪ Standby switch and boiler contact
▪ Made in the USA
Modulating - EB-WX-**
▪ Same as EB-S-**
PLUS
▪ Modulates at a tighter temperature control
▪ Outdoor sensing with outdoor reset capability. The target supply
temperature ramps up as it is colder outside.
Monticello, Minnesota
800.922.4138
www.electromn.com