OPERATIONAL TIPS
Energy Selector Switch
If this system does not have a standby operating (gas or oil) boiler, this switch
must always be in the “normal” position.
To activate standby boiler, simply position front panel switch to “standby”.
Monitor Lights, Front Panel
190°F AUTO RESET LIMIT, red – this will only
illuminate when the vessel hi-limit opens due to
excessive high water temperature. This hi-limit is
self-resetting.
BOILER POWER, green – basically this is
illuminated at all times. It represents 24-volt power
source, good fuse, controller logic is operational,
and a good outlet sensor. If the outlet sensor is
inoperative, incorrectly wired, or malfunctioning;
this green monitor LED should be in the blinking or
pulsing mode (see Troubleshooting section).
ELECTRIC MODE, amber – when illuminated the
system is in the electric mode. If it is not
illuminated the utility load control receiver is in the
interrupt or on-peak mode. If there is an optional or
remote standby switch, the status of the standby
switch is also monitored by this amber LED.
THERMOSTAT CALL, red – indicates a remote
switch closure (t-stat or zoning end switch) is
closed between terminals R and W.
Inside Controller Board
STAGES, red – these four LED’s indicate which electric element stages are on and active.
Flow Switch Statement
A flow switch is not included with the boiler. However, one can be added to the LMC circuit. Simply
place the field provided flow switch in series with this circuit.
NOTE: The “L/W” (J3) jumper must be in the “W” position.