Install Manual

04/03/2009 2 EI204
Specification Table
Model Number: EH-*10-+ EH-*15-+ EH-*20-+ EH-*25-+
kW Rating 10 15 20 25
Voltage/Phase 240/1 240/1 240/1 240/1
Control Voltage 24 volts
24 volts
24 volts
24 volts
Circuit Breaker 1-60 1-60, 1-30 2-60 2-60, 1-30
Source Feed 1 2 2 3
Elements 4 6 8 10
Min. CFM 650 900 1200 1500
Max. Temp. Rise 50° F 50° F 50° F 50° F
Shipping Weight 34# 36# 38# 42#
Loaded or electric call for heat operating voltage must be between 23 and 28 volts, 60Hz.
This table primarily lists the various specification information at each kW size. The model number shown is the marketing
or catalog number. The inside nameplate has the manufacturer’s model number (example – EH-U20-8 = EM-EU204C8).
Product Dimensions