Make Up Air II Spec Sheet

8/13/2020 EL922
STANDARD EQUIPMENT
▪ Modelsavailablein350and600CFM
▪ Voltage-240/208VAC,singlephaseor208VAC,threephase
▪ WarmFlo
®
DigitalProportionalElementModulation
▪ Inletandoutletdigitaltemperaturesensorsforprecisesetpoints
▪ Integratedpoweredinletdamper
▪ Washablealuminummeshlter
▪ Currenttransformertechnologyforfullinterlockwithexhaustsystems
▪ IncludedCTdetectsLO/MED/HIexhaustfanlevels
▪ Threespeeds,autoadjustbasedonCTinput
▪ ThreeCTinputsavailableformultiplefanapplications
▪ Multiplecontrolinputs(i.e.endswitches,zonevalves,etc.)
▪ Easyprogrammingformulti-speedkitchenexhaustfans
▪ Multipleinterfacingoptionstoexternalcontrols
▪ Thermostatendswitchconnectionpoint
TEMPERATURE RISE & CFM CHART - Selecting the best model for your application:
1
Choose your desired temperature rise (this is the dierence between the coldest design day temperature and desired duct
air temperature).
2
Move across the chart from your desired temperature rise to the CFM required (you may have to select a model with a
higher CFM and adjust down to your required CFM at installation).
Example:
In an application where your coldest day averages 0° F and you require 50° F duct air, choose 50° F
temperature rise. If you require 500 CFM you would select the MD10.
kW
1 1.6 5 7.2 10 15 20 14.4 21.6
CFM CFM CFM CFM CFM CFM CFM CFM CFM
Required Temp Rise
80° F 39 71 197 277 395 604 790 553 869
70° F 45 81 225 325 451 677 903 632 993
60° F 53 95 260 379 526 790 1053 737 1160
50° F 63 114 316 455 632 948 1264 885 N/A
40° F 79 158 395 568 790 1185 N/A 1130 N/A
30° F 105 168 526 758 1053 N/A N/A N/A N/A
SPECIFICATIONS
Model kW Btu/h Amps
Internal
CB
Motor
FLA
Motor
HP
Phase Voltage
CFM
Max Fuse/
HACR
Duct
Connection
Sound
Noise dB
Unit/
Shipping
Weight lbs
Max Static
EM-MC05-240-1-08
5/3.8 17060/12795 20.8/18.0 N/A
0.4 1/10
1 240/208 350 .50 30 8” 61 55/62
EM-MC00-240-1-08
0 0 0 N/A
0.4 1/10
1 240/208 350 .50 15 8” 61 51/58
EM-MC05-208-3-08
4.8 16378 13.3 N/A
0.4 1/10
3 208 350 .50 20 8” 61 55/62
EM-MD10-240-1-10
10/7.5 34121/25591 41.7/36.1 N/A
0.8 1/5
1 240/208 600 .50 60 10” 70 60/67
EM-MD05-240-1-10
5/3.8 17060/12795 20.8/18.0 N/A
0.8 1/5
1 240/208 600 .50 30 10” 70 56/63
EM-MD00-240-1-10
0 0 0 N/A
0.8 1/5
1 240/208 600 .50 15 10” 70 52/59
EM-MD10-208-3-10
9.6 32756 26.6 N/A
0.8 1/5
3 208 600 .50 35 10” 70 60/67
EM-MD05-208-3-10
4.8 16378 13.3 N/A
0.8 1/5
3 208 600 .50 20 10” 70 56/63
NOTE: Fan data supplied by fan manufacturer.
Specification Sheet - EM-MC/MD* Packaged Electric Make-Up Air
All specications subject to ELECTRO INDUSTRIES STANDARD TERMS
AND CONDITIONS, download at www.electromn.com/terms.pdf.
▪ LCDdisplayprovidesstatusandtemperatures
-RealtimeestimatedCFM
-Desiredtargettemperature
-Incomingandsupplytemperature
▪ LOandHItemperaturesetpointranges,20°Fto55°Fand60°Fto90°F
▪ Hi-limits,automaticandmanualreset
▪ Uniquedesignallowsforsimpliedinstallation
▪ Listedforhorizontalorverticalinstallation
▪ Canbeeasilywall-hung
▪ Includeschainforsuspendedinstallations
▪ Bestintheindustrywarranty:
-20-yearnnedrodelementwarranty
-2-yearpartswarranty
▪ MadeintheUSA
Monticello, Minnesota
800.922.4138
www.electromn.com