Make Up Air II Installation Manual
05/21/2019 15 EI914
Basic Setup & Configuration
Control Board Configuration
Temperature Set Point – Located on the back of the control board is a dial labeled “SET POINT”. This
dial is used to set the desired output temperature.
Setting the desired output temperature is completed in three steps. See Figure 1 for temperature ranges.
Step 1 – Determine the required temperature output for the application.
o HINT: Most Make-Up Air applications suggest an output set point typically
around 50°F (10°C).
Step 2 – On the backside of the control module (hinged door) is a jumper labeled “TEMP
RANGE” (J21). This jumper allows for two temperature range options: HI or LO. Place
the jumper to select the correct range based on the determined set point (step 1).
Step 3 – using a small screwdriver, adjust the SET POINT dial according to the desired
operating temperature.
FIGURE 1
NOTE: Factory default:
J21 = LO
Switch position number 6 (50°F/10°C)
SET POINT
Switch Position
HI LO
°F °C °F °C
0 60 13 20 -7
1 65 16 25 -4
2 70 18 30 -1
3 75 21 35 2
4 80 24 40 4
5 85 27 45 7
6 90 29 50 10
7 95 32 55 13